Requirements/Considerations of Next Generation ORv3 PSU and Power Shelves (OCP EMEA Summit 2025)

Open Compute Project Foundation · Cihan Aydin, Harry Soin

A joint Delta and Advanced Energy talk comparing ORv3, ORv3 HPR and HPR2 power supply units and shelves.

On this page

Overview

This joint Delta and Advanced Energy talk by Cihan Aydin and Harry Soin, given at OCP EMEA Summit 2025 in Dublin (DC Physical Infrastructure track), compares ORv3, ORv3 HPR and HPR2 power supply units and shelves. It tabulates input range, output, efficiency and size, explains the new AC-loss signalling used to hand over to battery backup units (BBUs), and describes pulse-load requirements driven by AI GPUs.

HPR and HPR2 PSUs both accept 180-305 VAC and reach 97.5% peak and 96.5% full-load efficiency including fans. HPR2 doubles output to 49 V/244 A but derates operating ambient to 35 C (HPR: 45 C). Shelf power rises from 33 kW to 72 kW within the same outer dimensions. The ORv3 1OU shelf has six 5.5 kW rectifiers: 33 kW at N+0 or 27.5 kW at N+1, 50 V, 600 A nominal, 20 ms hold-up.

BBU handover is now triggered by an AC_LOSS signal: the BBU starts within 4 ms (bus below 48.5 V for 2 ms plus 2 ms start-up) and can run up to 240 s; PSU hold-up energy is 60 J for loads up to 150%. The pulse-load requirement has been updated for AI GPUs to 160%/136% of rating.

Bench results show power factor and current distortion under dynamic loads: at 277 VAC with 15-160% dynamic load, the PSU measured PF 0.998 and iTHD 2.91%. With the input limit set to 4.5 kW, a peak to 5.5 kW lasting over 100 ms shut the unit down unless auto-adjust raised the limit. A peak-shaving energy-storage shelf is also introduced. As a limitation, this is a conference presentation; copyright belongs to its owner.

Key points

  1. HPR and HPR2 PSUs both accept 180-305 VAC and reach 97.5% peak and 96.5% full-load efficiency including fans.
  2. HPR2 doubles output to 49 V/244 A but derates operating ambient to 35 C (HPR: 45 C).
  3. Shelf power rises from 33 kW to 72 kW within the same outer dimensions.
  4. BBU handover is triggered by AC_LOSS: it starts within 4 ms, runs up to 240 s; PSU hold-up energy is 60 J for loads up to 150%.
  5. Pulse-load requirement updated for AI GPUs to 160%/136% of rating.
  6. ORv3 1OU shelf: six 5.5 kW rectifiers, 33 kW at N+0 or 27.5 kW at N+1, 50 V, 600 A, 20 ms hold-up.
  7. At 277 VAC with 15-160% dynamic load the PSU measured PF 0.998 and iTHD 2.91%.
  8. With the input limit at 4.5 kW, a peak to 5.5 kW over 100 ms shut the unit down unless auto-adjust raised the limit.

Using it in design

  • Give power shelf catalogue items N+0 and N+1 kW ratings, hold-up time, BBU runtime and allowed peak and pulse-load factors.
  • Size shelves for AI racks using the pulse factor (for example 1.6x) rather than average load.
  • Warn when shelf ambient exceeds the PSU's rated inlet temperature.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical and rack designers selecting power distribution and power shelves for high-density AI racks.

Related standards

  • OCP Open Rack V3 Power Shelf
  • OCP ORv3 HPR

Publication details

Authors
Cihan Aydin; Harry Soin
Publisher
Open Compute Project Foundation
Year
2025
Document number
OCP EMEA Summit 2025, DC Physical Infrastructure track
Event
OCP EMEA Summit 2025, Dublin
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Cihan Aydin; Harry Soin (2025). Requirements/Considerations of Next Generation ORv3 PSU and Power Shelves (OCP EMEA Summit 2025). Open Compute Project Foundation. OCP EMEA Summit 2025, DC Physical Infrastructure track. OCP EMEA Summit 2025, Dublin. https://drive.google.com/file/d/1MmMHB9WwnliEr_3gk1VsbuSMPbxfD4qN/view

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.