Technical guideFree to read2026

ORV3 HVDC-LVDC 100 kW Power Shelf Design Specification v1.0.0

Open Compute Project · Sanket Sapre, Dmitriy Shapiro et al.

This 2026 OCP specification defines a 100 kW Open Rack V3 power shelf fed from a +/-400 V DC (800 V) high-voltage DC bus that delivers the narrow-range 48 V rack busbar. It reflects the move toward HVDC distribution for AI racks above 100 kW.

On this page

Overview

The shelf uses six 18 kW PSU slots; together they add up to 108 kW, but input power is 100 kW and it is the input connector, not the PSU sum, that sets that limit. With one PSU out, the remaining five deliver 90 kW, so in redundant operation usable power per shelf falls below 100 kW. Input is HVDC at a nominal +/-400 to +/-410 V DC through two 6-pin connectors.

The output is a narrow-range 48 V system, and ripple and noise must stay below 500 mV peak-to-peak. The 48 V return is floating, not bonded to the shelf chassis, which makes the grounding scheme and ground-fault protection an explicit decision in facility design. Busbar clip temperature is monitored with two thermistors, so connector heating can be detected inside the rack and a loosening busbar contact at high current can be spotted early.

The specification is an equipment-level statement of how high-voltage DC attaches to the ORv3 architecture; the upstream rectifier, DC busway and protection design are outside its scope. For those, sources such as the Siemens and NVIDIA paper on 800 VDC protection are needed. The document is one sign of the move toward HVDC distribution for AI racks above 100 kW. The 48 V distribution inside the rack is kept; only the voltage entering the rack changes.

Key points

  1. Input power 100 kW, limited by the input connector; 6 x 18 kW PSU slots.
  2. HVDC input: nominal +/-400 to +/-410 V DC through 2 x 6-pin connectors.
  3. Output: narrow-range 48 V system; ripple and noise under 500 mV peak-to-peak.
  4. 48 V return floating, not bonded to the shelf chassis.
  5. Busbar clip temperature sensed with two thermistors.
  6. Reflects the move to HVDC distribution for AI racks above 100 kW.

Using it in design

  • Add an '800 VDC (+/-400 V) to rack' electrical topology option: facility rectification upstream, DC busway, and rack HVDC shelves of 100 kW each.
  • Make this option the default for rack-density presets above 100 kW and show a DC arc-flash and protection review warning.
  • Record the floating 48 V return grounding scheme and ground-fault protection decision explicitly in project records.
  • Model power shelves as 6 x 18 kW per shelf and take the input limit as 100 kW.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers planning HVDC distribution for AI racks above 100 kW.

Related standards

  • OCP Open Rack V3
  • IEC 60364
  • NFPA 70E

Publication details

Authors
Sanket Sapre; Dmitriy Shapiro; Zuhir Sras; John Fernandes; Ben Kim; Baby Neil Escuadro; Siu Lam; Mingchun Xu
Publisher
Open Compute Project
Year
2026
Document number
v1.0.0
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Sanket Sapre; Dmitriy Shapiro; Zuhir Sras; John Fernandes; Ben Kim; Baby Neil Escuadro; Siu Lam; Mingchun Xu (2026). ORV3 HVDC-LVDC 100 kW Power Shelf Design Specification v1.0.0. Open Compute Project. v1.0.0. https://www.opencompute.org/documents/orv3-hvdc-lvdc-100kw-power-shelf-spec-1-0-0-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.