Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements

IEC · IEC TC 22

IEC 62040-2:2016 is a type-test EMC product standard for UPS used in residential, commercial, light-industrial or industrial environments. Its 2016 third edition added network port limits and clarified immunity performance criteria.

On this page

Overview

The standard is a type-test EMC product standard for UPS used in residential, commercial, light-industrial or industrial environments. It applies to UPS with port voltages up to 1 500 V DC or 1 000 V AC that include an energy storage device. This record rests on the publisher's public catalogue abstract and product metadata; the full text of the paid standard was not read.

Edition 3 was published on 25 November 2016; it runs to 141 pages including the redline version and includes Interpretation Sheet 1 (2018). According to the abstract, this edition adds network port limits in Tables 1 and 2 and Annex C, changes the quasi-peak limit for category C3 UPS in Table 2, and clarifies immunity performance criteria in Table 4.

For design the significance is that a UPS's EMC category (C1, C2, C3) determines its suitability for an environment. A C3 UPS, suited to industrial settings, may cause electromagnetic interference if placed on a supply shared with residential or light-commercial users without filtering.

Related sources in the record are IEC 62040-1, IEC 62040-3 and TS EN 62040-2. Because the abstract gives no numerical emission limits, the standard itself should be consulted for them.

Key points

  1. Type-test EMC product standard for UPS in residential, commercial, light-industrial or industrial environments.
  2. Applies to UPS with port voltages up to 1 500 V DC or 1 000 V AC that include an energy storage device.
  3. Network port limits added in Tables 1, 2 and Annex C.
  4. Quasi-peak limit for category C3 UPS changed in Table 2; immunity performance criteria clarified in Table 4.
  5. Edition 3 published 2016-11-25; 141 pages including redline.
  6. Interpretation Sheet 1 (2018) is included.
  7. Related: IEC 62040-1, IEC 62040-3 and TS EN 62040-2.

Using it in design

  • Store the EMC category (C1/C2/C3) in the UPS catalog.
  • Warn when a C3 (industrial) UPS is placed on a supply shared with residential or light-commercial users without filtering.
  • Check EMC compliance together with the safety (IEC 62040-1) and performance (IEC 62040-3) standards when selecting a UPS.
  • Consider the network port limits when designing UPS monitoring and communication links.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Engineers selecting UPS and designing electrical installations, and teams checking product compliance.

Related standards

  • IEC 62040-1
  • IEC 62040-3
  • TS EN 62040-2

Publication details

Authors
IEC TC 22
Publisher
IEC
Year
2016
Document number
IEC 62040-2:2016
Document language
English
Source type
Standard
Access
Citation only
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document
Original licence note

Paid standard. Record built only from the publisher's public catalogue abstract and product metadata; full text not redistributed.

Citation

IEC TC 22 (2016). Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements. IEC. IEC 62040-2:2016. https://webstore.iec.ch/en/publication/59482

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.