Technical guideFree to read2025

NVIDIA DGX SuperPOD: Next Generation Scalable Infrastructure for AI Leadership - Reference Architecture featuring NVIDIA DGX GB200

NVIDIA

NVIDIA's reference architecture (RA-11338-001 V01) for a SuperPOD built from DGX GB200 NVL72 racks gives facility designers the per-Scalable-Unit power envelope, the required availability class and the power-shelf configuration per rack.

On this page

Overview

The architecture is built around the Scalable Unit (SU) of eight DGX GB200 NVL72 racks. Each SU requires 1.2 MW of TDP, and a SuperPOD can scale to 128 racks (9,216 GPUs) and beyond, with the fabric design supporting up to 16 SUs. The document walks through the rack internals (compute trays, NVLink switch trays, power shelves), the InfiniBand compute fabric, the Ethernet storage and management fabrics, storage requirements and the recommended rack layout.

Each rack holds 18 compute trays and 9 NVLink switch trays that form a single 72-GPU NVLink domain. On the power side every rack carries eight power shelves, each with six 5.5 kW PSUs delivering up to 33 kW. Cooling is hybrid: GPUs and CPUs are direct-liquid-cooled while other components stay air-cooled, which means the liquid and air fractions must be sized separately for the CDU and the air side.

The one hard facility requirement is availability: the data centre should meet or exceed Uptime Tier 3, TIA-942-B Rated 3 or EN 50600 Availability Class 3, meaning concurrent maintainability and no single point of failure. This is a vendor reference. It puts its weight on network and software detail and leaves floor plans, redundant power topology and mechanical piping to the facility designer.

Key points

  1. Each SU (8 DGX GB200 NVL72 racks) requires 1.2 MW TDP.
  2. Facility should meet or exceed Uptime Tier 3, TIA-942-B Rated 3 or EN 50600 Class 3, with concurrent maintainability and no single point of failure.
  3. Hybrid cooling: GPUs and CPUs direct-liquid-cooled, other components air-cooled.
  4. Eight power shelves per rack, each with 6 x 5.5 kW PSUs delivering up to 33 kW.
  5. 18 compute trays and 9 NVLink switch trays per rack form one 72-GPU NVLink domain.
  6. Scales to 128 racks (9,216 GPUs) and beyond; fabric design supports up to 16 SUs.

Using it in design

  • Define the cluster template with SU = 8 NVL72 racks at 1.2 MW IT; auto-place SUs in rows following the reference rack layout, allocating ~150 kW per compute rack plus network racks.
  • When a project contains DGX SuperPOD, enforce Tier III / Rated-3 / Class 3 topology checks (concurrent maintainability, no single point of failure).
  • Add the NVL72 rack with 8 x 33 kW power shelves and its liquid/air cooling split to the catalog, and base CDU and air-side sizing on that split.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Facility and power designers planning a hall for a DGX GB200 SuperPOD.

Related standards

  • TIA-942-B
  • EN 50600
  • Uptime Institute Tier Standard: Topology

Publication details

Authors
NVIDIA
Publisher
NVIDIA
Year
2025
Document number
RA-11338-001 V01
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

NVIDIA (2025). NVIDIA DGX SuperPOD: Next Generation Scalable Infrastructure for AI Leadership - Reference Architecture featuring NVIDIA DGX GB200. NVIDIA. RA-11338-001 V01. https://docs.nvidia.com/dgx-superpod/reference-architecture-scalable-infrastructure-gb200/latest/_downloads/238ab33ee345a7241fc2f15eedc2ff6c/RA11338001-DSPGB200-ReferenceArch.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.