Vertiv 360AI High Density Reference Design #020: 6x 1.2 MW NVIDIA DGX SuperPODs (GB200 NVL72)
Vertiv
The AI hall concept scaled to 7 MW with six GB200 NVL72 SuperPODs, the multi-pod example of the capacity-block idea.
On this page
Overview
This 2025 design reaches 7 MW of solution capacity with six GB200 NVL72 SuperPODs of about 1.15 MW each. Total IT load is 6,912 kW = 6 x 1,152 kW. It holds 48 compute racks at 130 kW and 48 support racks at 14 kW, 108 racks in total including 12 reserved for wire management. Heat leaves 72% through direct-to-chip liquid and 28% through perimeter air.
Power follows the 4-to-make-3 pattern: groups of four UPS modules serve pairs of pods, and the design specifies four 1,200 kVA UPS. Cooling is N+1 with chillers, CRAHs and 1,350 kW CDUs. Racks carry OCP-compliant 33 kW DC power shelves (eight per compute rack); busways are 400 A (8 per pod), with two 60 A tap-offs per compute rack and two 40 A tap-offs per support rack.
The document is internally inconsistent: the design summary says 1,200 kVA UPS while the schematic shows 1,700 kVA modules and 6,000 A main switchboards, and the cooling UPS is 240 kVA 2N in the summary but 600 kVA A/B facility UPS in the schematic. Vendor values should therefore be treated as indicative and recomputed. It notes rack density may trend toward 1 MW per rack.
Key points
- Total IT 6,912 kW = 6 pods x 1,152 kW; solution capacity 7 MW.
- 48 racks at 130 kW + 48 racks at 14 kW; 108 racks including 12 for wire management.
- Cooling split 72% direct-to-chip liquid / 28% perimeter air.
- Power 4-to-make-3, cooling N+1; four 1,200 kVA UPS per pair of pods (schematic shows 1,700 kVA modules and 6,000 A MSBs).
- Rack power shelf 33 kW DC, 8 per compute rack; 2 x 30 A rack PDUs per support rack.
- Busway 400 A (8 per pod); 2 x 60 A tap-off per compute rack, 2 x 40 A per support rack.
- Cooling UPS 240 kVA 2N (schematic shows 600 kVA A/B).
- Vertiv projects AI density growing toward 1 MW per rack.
Using it in design
- Make the capacity block a first-class object: block = UPS group + PDUs + CDUs + chillers sized for N pods, so no power is stranded.
- Use the 1,200 vs 1,700 kVA conflict as a worked warning and always recompute vendor values.
- Default liquid fraction for GB200 NVL72 racks to 0.72-0.78.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Engineers planning multi-pod AI campuses above 5 MW.
Related standards
- OCP Open Rack V3
- Uptime Tier Standard: Topology
- ASHRAE TC9.9 Liquid Cooling Guidelines
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2025
- Document number
- AI Reference Design #020
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Vertiv (2025). Vertiv 360AI High Density Reference Design #020: 6x 1.2 MW NVIDIA DGX SuperPODs (GB200 NVL72). Vertiv. AI Reference Design #020. https://www.vertiv.com/493cf5/globalassets/campaigns/ai-hub/vertiv-reference-design-020-ds-en-na-2024-gr-00109-web.pdf