Technical guideFree to read2025

Vertiv 360AI High Density Reference Design #020: 6x 1.2 MW NVIDIA DGX SuperPODs (GB200 NVL72)

Vertiv

The AI hall concept scaled to 7 MW with six GB200 NVL72 SuperPODs, the multi-pod example of the capacity-block idea.

On this page

Overview

This 2025 design reaches 7 MW of solution capacity with six GB200 NVL72 SuperPODs of about 1.15 MW each. Total IT load is 6,912 kW = 6 x 1,152 kW. It holds 48 compute racks at 130 kW and 48 support racks at 14 kW, 108 racks in total including 12 reserved for wire management. Heat leaves 72% through direct-to-chip liquid and 28% through perimeter air.

Power follows the 4-to-make-3 pattern: groups of four UPS modules serve pairs of pods, and the design specifies four 1,200 kVA UPS. Cooling is N+1 with chillers, CRAHs and 1,350 kW CDUs. Racks carry OCP-compliant 33 kW DC power shelves (eight per compute rack); busways are 400 A (8 per pod), with two 60 A tap-offs per compute rack and two 40 A tap-offs per support rack.

The document is internally inconsistent: the design summary says 1,200 kVA UPS while the schematic shows 1,700 kVA modules and 6,000 A main switchboards, and the cooling UPS is 240 kVA 2N in the summary but 600 kVA A/B facility UPS in the schematic. Vendor values should therefore be treated as indicative and recomputed. It notes rack density may trend toward 1 MW per rack.

Key points

  1. Total IT 6,912 kW = 6 pods x 1,152 kW; solution capacity 7 MW.
  2. 48 racks at 130 kW + 48 racks at 14 kW; 108 racks including 12 for wire management.
  3. Cooling split 72% direct-to-chip liquid / 28% perimeter air.
  4. Power 4-to-make-3, cooling N+1; four 1,200 kVA UPS per pair of pods (schematic shows 1,700 kVA modules and 6,000 A MSBs).
  5. Rack power shelf 33 kW DC, 8 per compute rack; 2 x 30 A rack PDUs per support rack.
  6. Busway 400 A (8 per pod); 2 x 60 A tap-off per compute rack, 2 x 40 A per support rack.
  7. Cooling UPS 240 kVA 2N (schematic shows 600 kVA A/B).
  8. Vertiv projects AI density growing toward 1 MW per rack.

Using it in design

  • Make the capacity block a first-class object: block = UPS group + PDUs + CDUs + chillers sized for N pods, so no power is stranded.
  • Use the 1,200 vs 1,700 kVA conflict as a worked warning and always recompute vendor values.
  • Default liquid fraction for GB200 NVL72 racks to 0.72-0.78.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Engineers planning multi-pod AI campuses above 5 MW.

Related standards

  • OCP Open Rack V3
  • Uptime Tier Standard: Topology
  • ASHRAE TC9.9 Liquid Cooling Guidelines

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2025
Document number
AI Reference Design #020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Vertiv (2025). Vertiv 360AI High Density Reference Design #020: 6x 1.2 MW NVIDIA DGX SuperPODs (GB200 NVL72). Vertiv. AI Reference Design #020. https://www.vertiv.com/493cf5/globalassets/campaigns/ai-hub/vertiv-reference-design-020-ds-en-na-2024-gr-00109-web.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.