Vertiv High Density Reference Design for AI #0019: 1.2 MW NVIDIA GB200 NVL72 SuperPOD (N redundancy)
Vertiv
A prefabricated-module oriented design for one 1.2 MW GB200 NVL72 SuperPOD with only N infrastructure redundancy. It gives the lowest-cost baseline against which 2N or 4-to-make-3 templates can be compared.
On this page
Overview
The design carries 1,176 kW (about 1.2 MW) across 18 racks: eight 132 kW compute racks and ten 12 kW support racks. Cooling is 76% direct-to-chip liquid and 24% from a chilled-water modular fan wall. Infrastructure redundancy is deliberately N, meaning single points of failure are accepted. That makes the document useful as a picture of the minimum system you get once the cost of redundancy is stripped out.
The power chain is lean: a single 1,500 kVA UPS carries the IT load behind a 2,500 A switchboard. A separate 250 kVA UPS serves the mechanical load, running N+1, with a second unit added if the 2N option is chosen. Distribution uses 2 x 500 A busbar per row and 2 x 120 A tap-off boxes per rack, while network and storage racks are fed from 22 kW (32 A) PDUs.
One physical detail feeds straight into layout: the racks are provisioned for a 200 mm depth extension. Manifolds, hoses and cabling in a liquid-cooled rack do not fit in standard rack depth, and the document makes that allowance a design assumption from the start. The prefabricated-module approach also aims to cut on-site labour and commissioning time. The limit is plain: N redundancy only suits environments that do not need maintenance or fault tolerance, or that provide resilience at the software layer. A Tier-style availability target would call for the 2N or 4-to-make-3 templates. The document is copyright vendor material, so its numbers can be cited but its text not copied.
Key points
- IT load 1.2 MW (1,176 kW): 8 x 132 kW + 10 x 12 kW, 18 racks
- Cooling 76% liquid, 24% air via chilled-water fan wall
- Infrastructure redundancy N; IT UPS 1 x 1,500 kVA; 2,500 A switchboard
- Mechanical UPS 250 kVA (second unit for 2N)
- Busbar 2 x 500 A per row; 2 x 120 A tap-off per rack; 22 kW (32 A) PDUs for network/storage racks
- Racks provisioned for 200 mm depth extension
Using it in design
- In the layout engine add 200 mm to rack depth for liquid-cooled AI racks; manifolds and hoses do not fit standard depth.
- Offer an "N (non-redundant)" AI template next to 2N and 4-to-make-3 templates to show the cost versus availability trade-off.
- For a 1.2 MW block, a first sizing check pairs a 1,500 kVA IT UPS, a 250 kVA mechanical UPS and a 2,500 A switchboard.
- Define 2 x 500 A busbar with 2 x 120 A tap-offs per rack as the default AI row configuration.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Designers and budget owners building minimum-cost AI infrastructure at single-SuperPOD scale.
Related standards
- OCP Open Rack V3
- ASHRAE TC9.9 Liquid Cooling Guidelines
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2024
- Document number
- AI Reference Design #0019
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Vertiv (2024). Vertiv High Density Reference Design for AI #0019: 1.2 MW NVIDIA GB200 NVL72 SuperPOD (N redundancy). Vertiv. AI Reference Design #0019. https://vertiv.com/4a1a52/globalassets/products/facilities-enclosures-and-racks/integrated-solutions/vertiv-megamod-coolchip/ai-ready-reference-design-0019.pdf
Events on this subject
- Electricity Eurasia 2027
- NVIDIA GTC
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.