White paperFree to read2017

Cost, Speed, and Reliability Tradeoffs between N+1 UPS Configurations

Schneider Electric · Wendy Torell

A Schneider Electric white paper (WP 234, 2017) comparing three 1 MW UPS designs (1N modular, internally modular N+1 and parallel-redundant N+1) on capex per kW, deployment time, loading and downtime risk.

On this page

Overview

The paper compares three 1 MW UPS designs: a 1N modular frame with four 250 kW modules, an internally modular N+1 frame with a fifth module sharing one backplane and battery plant, and parallel-redundant N+1 using three 500 kW units each with its own batteries. It defines isolated-redundant, parallel-redundant and internally modular N+1, then quantifies capex per kW (materials plus installation), deployment schedule, operating load percentage and qualitative downtime risk for module, DC-bus and maintenance events.

Capex per kW of rated capacity is $453 for 1N, $482 for internal modular N+1 and $660 for parallel-redundant N+1, so internal N+1 is $178/kW (26.9%) cheaper than parallel. The breakdown (1N / internal N+1 / parallel) is UPS $148/$177/$214, bypass cabinet $36/$36/$70, 7-minute battery $98/$98/$148 and installation $163/$163/$213 per kW. The premium is 6.5% from 1N to internal modular and 36.8% from internal modular to parallel. A typical 1 MW UPS installation spans about 6-8 weeks; parallel systems take 1-2 weeks (25-30%) longer because of extra terminations, start-ups, load-bank tests and paralleling checks, and need about 25% more space even with an ideal layout.

At 800 kW load (80% of 1,000 kW), module loading is 80% for 1N (4x250 kW), 64% for internal N+1 (5x250 kW) and 53% for parallel 2+1 (3x500 kW). In internal modular N+1 the common DC (battery) bus and output bus are single points of failure: a battery-bus fault or UPS maintenance puts the load on bypass without battery backup, unlike parallel redundant. The paper ends with a checklist of fault-tolerance features inside a single UPS frame: redundant power modules, fans, controller power supplies, battery strings, communication bus, control system, and a static switch sized above the maximum expected inrush and step loads.

Key points

  1. Capex per kW: 1N $453, internal modular N+1 $482, parallel-redundant N+1 $660.
  2. Internal N+1 is $178/kW (26.9%) cheaper than parallel.
  3. Premiums: 6.5% from 1N to internal modular; 36.8% from internal modular to parallel.
  4. A typical 1 MW installation takes about 6-8 weeks; parallel systems 1-2 weeks (25-30%) longer.
  5. At 800 kW load: module loading 80% (1N), 64% (internal N+1), 53% (parallel 2+1).
  6. Parallel redundant needs about 25% more space even with an ideal layout.
  7. In internal modular N+1 the common DC and output buses are single points of failure; a battery-bus fault puts the load on bypass without battery backup.
  8. Check for redundant modules, fans, controller supplies, battery strings, communication bus and a static switch above expected inrush.

Using it in design

  • Distinguish 'N+1 internal modular', 'N+1 parallel redundant' and 'isolated redundant' instead of a single N+1 flag; for modular frames store module rating, max modules, shared battery bus and redundant controls/fans.
  • Compute per-module load % for the chosen redundancy at design load and evaluate efficiency from the UPS curve at that point.
  • Warn that internal N+1 with a common battery bus does not protect against DC-bus faults or UPS maintenance; flag parallel systems with large N for load-sharing risk; require static-switch rating above expected inrush.
  • In the capex estimator use per-kW UPS, bypass, battery, assembly and installation lines plus a 1-2 week schedule adder and about 25% more plant-room area for parallel redundant designs.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers and decision makers choosing a UPS redundancy configuration.

Related standards

  • IEC 62040-3
  • IEEE 3006.7
  • Uptime Institute Tier Standard: Topology

Publication details

Authors
Wendy Torell
Publisher
Schneider Electric
Year
2017
Document number
WP 234
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Wendy Torell (2017). Cost, Speed, and Reliability Tradeoffs between N+1 UPS Configurations. Schneider Electric. WP 234. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-A84MRT_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.