Research paperFree to read2024

Extraction of thevenin-based equivalent circuit of multi-cell lead acid battery pack and SoC estimation

Bozok Journal of Engineering and Architecture · Hayri Arabacı, Kemal Erdoğan

A Bozok Journal of Engineering and Architecture paper (2024): modelling a 10 kVA UPS battery string (8 x 12 V in series) as one three-parameter Thevenin circuit gives 99.85% average accuracy in SoC estimation.

On this page

Overview

Lead-acid batteries are common in UPS systems because they are cheap and tolerate overcharge. When the mains fails, runtime depends on battery energy capacity, and estimating the remaining time requires monitoring state of charge (SoC). In practice UPS units cut off discharge by terminal voltage, but the terminal voltage read under load differs from the open-circuit voltage, so the cut-off threshold is set high with a tolerance and battery capacity is used inefficiently.

The paper proposes to address this with a Thevenin equivalent circuit that treats the whole series string as one battery. The experiment used the battery group of a 10 kVA UPS: 8 batteries of 12 V (each rated 9 Ah) in series, charged by the UPS's own charger and discharged through resistors on the battery terminals rather than through the inverter. Voltage was read without isolation, current with a Hall-effect sensor, at a high sampling rate.

Three parameters were extracted from the loading transient: internal resistance Ri = 0.4648 ohm, Rt = 0.2194 ohm and Ct = 24.078 F. The model was checked against SoC computed by current integration during a full discharge. The maximum error was 0.61% and the mean absolute error 0.148%.

The authors note that no constant-current load was available, so fixed resistors were used, that the effect on total error could not be determined, and that constant-current tests would improve verification. The work came from a KOSGEB-supported project and rests on one battery string and one test setup.

Key points

  1. The experiment used the 8 x 12 V series battery group of a 10 kVA UPS; each battery is rated 9 Ah with a 14.9 V charging upper limit.
  2. The entire string is represented by one Thevenin equivalent circuit with only three parameters.
  3. Extracted parameters: Ri = 0.4648 ohm, Rt = 0.2194 ohm, Ct = 24.078 F.
  4. Discharge used fixed resistors instead of the UPS inverter, in cycles of 79 s off and 30 s on.
  5. SoC estimation reaches 99.85% average accuracy, 0.61% maximum error and 0.148% mean absolute error.
  6. The common UPS practice of treating terminal voltage as open-circuit voltage is compared at about 0.96% error and judged acceptable.
  7. Because current changes with falling voltage under a fixed resistor, verification is harder; constant-current tests are recommended.

Using it in design

  • For UPS battery management, consider basing remaining-autonomy estimation on an equivalent-circuit model that corrects open-circuit voltage under load, not only on a terminal-voltage threshold.
  • Parametrising the string as one equivalent battery simplifies monitoring software for many series batteries; measure and record the model parameters at first commissioning.
  • In autonomy calculations, remember that a high end-of-discharge threshold wastes capacity, and ask the supplier how the threshold logic works.
  • In battery acceptance tests use a constant-current load unit where possible; a fixed-resistor load increases measurement error.

Who should read it

Designers, maintenance engineers and software developers working on UPS battery monitoring and autonomy estimation.

Document contents

  1. Introduction
  2. Material and method: test setup and Thevenin parameter extraction
  3. Results and discussion
  4. Conclusions

Publication details

Authors
Hayri Arabacı; Kemal Erdoğan
Publisher
Bozok Journal of Engineering and Architecture
Year
2024
Document number
3(1), 93–100
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected. Free reading is not commercial redistribution permission; metadata and original short summaries only.

Citation

Hayri Arabacı; Kemal Erdoğan (2024). Extraction of thevenin-based equivalent circuit of multi-cell lead acid battery pack and SoC estimation. Bozok Journal of Engineering and Architecture. 3(1), 93–100. https://dergipark.org.tr/en/download/article-file/3894931

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.