ENERTRONIC modular SE: Modular Three-Phase UPS Systems

Benning

Benning's modular three-phase UPS brochure: 10, 20 and 40 kW modules, up to 25 per system and 1000 kW, with up to 96% double-conversion and 99% super-efficiency-mode efficiency.

On this page

Overview

The January 2025 Benning Elektrotechnik brochure presents the ENERTRONIC modular SE series for industrial, infrastructure, telecom, oil and gas, and IT or data-centre use. The series is built from 10, 20 and 40 kW modules, each defined as a double-conversion, serial on-line UPS of class VFI-SS-111 under IEC/EN 62040-3. A system holds up to 25 modules, which with 40 kW modules gives up to 1000 kW.

For reliability the brochure rests on three architectural features: redundant critical circuits inside each module, a multi-master scheme in which every module can act as master or slave, and a decentralised parallel architecture. Together these are said to remove single points of failure. Modules are hot-swappable, a module can be replaced in under 10 minutes, and this is tied to a claimed six-nines (99.9999%) availability.

Two operating styles are described for efficiency. In double conversion the brochure gives up to 96%, with 95% and 96% in the two module-size columns of its table. In super efficiency (SE) mode the load is fed through the static bypass until mains voltage or frequency leaves preset tolerances, and 99% is achievable. A power optimisation mode also puts surplus modules to sleep while keeping them ready to take load instantly.

The technical table lists input THDi of 3% or less, input power factor of 0.99 or more, and a battery voltage of 480-576 V (240-288 lead cells), with lead, nickel-cadmium, lithium-ion, ultracapacitor and redox-flow storage named. The brochure prescribes no universal runtime; that depends on the battery chosen. The design value for a data-centre engineer is carrying module limits, power density and overload curves into capacity planning.

Key points

  1. Module ratings are 10, 20 and 40 kW; up to 25 modules per system; system power 10-250, 20-500 or 40-1000 kW (cos phi = 1).
  2. Classification is VFI-SS-111 (IEC/EN 62040-3); safety to IEC/EN 62040-1 and EMC to IEC/EN 62040-2.
  3. Efficiency is up to 96% in double conversion and 99% in SE mode; input THDi is 3% or less at 100% load and input power factor is 0.99 or more.
  4. Inverter overload: 150% for 60 s, 125% for 10 min, 110% for 30 min. Bypass overload: 1000% for 100 ms, 150% for over 10 min, 125% continuous.
  5. Short-circuit response is 400% or 300% (by column) on the inverter and 1000% for 100 ms on the bypass.
  6. Footprint is a 600 x 800 mm cabinet (W x D); power density is 125, 250 and 415 kW/m2 for the 10, 20 and 40 kW module columns.
  7. Operating range is 0-40 C (derating above), 5-95% non-condensing humidity, typical noise under 65 dBA, IP20, and no derating up to 1000 m (maximum 5000 m).
  8. Battery voltage is 480-576 V (240-288 lead cells); lead, NiCd, lithium-ion, ultracapacitor and redox-flow technologies are listed.

Using it in design

  • If load growth is uncertain, install only the modules needed on day one; for N+1, size modules as load plus one (for example in 40 kW units) and check the 25-module limit.
  • Before using SE mode, assess whether the load tolerates short mains disturbances passing through the static bypass; protection in this mode depends on the bypass until the mains tolerance is exceeded.
  • Feed the short-circuit and overload table into the protection coordination study (inverter 400%/300%, bypass 1000% for 100 ms).
  • In layout, use front-only service access and top ventilation to consider wall or corner placement, and derate for ambient temperatures above 40 C.
  • Choose the battery technology and runtime yourself; the brochure gives no runtime, and options outside the 480-576 V battery range need manufacturer confirmation.

Who should read it

Electrical designers selecting and capacity-planning modular UPS systems, specification writers and operations teams.

Document contents

  1. Optimum availability, operating costs and power quality
  2. Maximum availability and lowest MTTR
  3. Pay as you grow scalability
  4. No single points of failure
  5. Highest power quality
  6. Automatic TCO and availability optimisation
  7. Extensive reporting and monitoring with MCU 3000
  8. Technical data
  9. Hot swap modularity to 1,000 kW
  10. Up to 99% efficiency
  11. Power density of 415 kW/m2

Publication details

Authors
Benning
Publisher
Benning
Year
Year not stated
Document number
10167082
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Benning ENERTRONIC modular SE: Modular Three-Phase UPS Systems. Benning. 10167082. https://www.benning.de/files/benning/global_content/downloads/10167082_enertronic_modular_se_en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.