Technical guideFree to read2012

Preventing arc flash incidents by design

Consulting-Specifying Engineer · Bruce W. Young

Bruce W. Young's article explaining the drivers of arc-flash incident energy and how labelling, maintenance settings and design choices reduce the hazard in critical facilities.

On this page

Overview

In this 2012 article in Consulting-Specifying Engineer, Bruce W. Young explains the drivers of arc-flash incident energy: available fault current and protective device characteristics. He then shows how labelling, maintenance settings and design choices reduce the hazard in critical facilities. The article is practice-oriented engineering writing, not a standard. The article therefore offers designers a way to reduce the hazard at design stage rather than after the calculation.

It starts from hazard and injury data: incident energy above 1.2 cal/cm2 can cause second-degree burns, and IEEE 1584 suggests a 2 s maximum arcing exposure time. Higher available fault current can reduce hazard because it shortens device clearing time. A main device may need separate line-side and load-side labels because its line side stays energized when open. Dual power paths let equipment be fully de-energized for work while operations continue.

The worked example is a 1,600 A, 480 V solid-state trip breaker. With coordinated settings, clearing takes about 13-19 s, the boundary is 105 in. and incident energy is 22 cal/cm2 (Category 3); with temporary maintenance settings it falls to 0.02 s, 15 in. and 0.86 cal/cm2. The author cautions that changing settings can nuisance-trip critical loads. A field incident on a 20-year-old switchboard illustrates the danger of forcing equipment that will not operate.

Key points

  1. Incident energy above 1.2 cal/cm2 can cause second-degree burns; IEEE 1584 suggests a 2 s maximum arcing exposure time.
  2. Higher available fault current can reduce hazard because it shortens device clearing time.
  3. A main device may need separate line-side and load-side labels because its line side stays energized when open.
  4. 1,600 A/480 V example: coordinated settings give about 13-19 s clearing, 105 in. boundary, 22 cal/cm2 (Category 3); maintenance settings give 0.02 s, 15 in., 0.86 cal/cm2.
  5. Dual power paths let equipment be fully de-energized for work while operations continue.
  6. Changing settings can nuisance-trip critical loads.

Using it in design

  • Arc-flash outputs should label both line and load sides of mains and compare normal versus maintenance-mode settings.
  • Recommend maintenance switches or ERMS on large LV mains.
  • Recommend dual-path topologies so work can be done de-energized.
  • Record in the report the risk that maintenance settings may nuisance-trip critical loads.

Who should read it

Data centre electrical designers, engineers who run protection and selectivity studies and maintenance managers.

Related standards

  • NFPA 70E
  • IEEE 1584

Publication details

Authors
Bruce W. Young
Publisher
Consulting-Specifying Engineer
Year
2012
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Bruce W. Young (2012). Preventing arc flash incidents by design. Consulting-Specifying Engineer. https://www.csemag.com/articles/preventing-arc-flash-incidents-by-design/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.