Preventing arc flash incidents by design
Consulting-Specifying Engineer · Bruce W. Young
Bruce W. Young's article explaining the drivers of arc-flash incident energy and how labelling, maintenance settings and design choices reduce the hazard in critical facilities.
On this page
Overview
In this 2012 article in Consulting-Specifying Engineer, Bruce W. Young explains the drivers of arc-flash incident energy: available fault current and protective device characteristics. He then shows how labelling, maintenance settings and design choices reduce the hazard in critical facilities. The article is practice-oriented engineering writing, not a standard. The article therefore offers designers a way to reduce the hazard at design stage rather than after the calculation.
It starts from hazard and injury data: incident energy above 1.2 cal/cm2 can cause second-degree burns, and IEEE 1584 suggests a 2 s maximum arcing exposure time. Higher available fault current can reduce hazard because it shortens device clearing time. A main device may need separate line-side and load-side labels because its line side stays energized when open. Dual power paths let equipment be fully de-energized for work while operations continue.
The worked example is a 1,600 A, 480 V solid-state trip breaker. With coordinated settings, clearing takes about 13-19 s, the boundary is 105 in. and incident energy is 22 cal/cm2 (Category 3); with temporary maintenance settings it falls to 0.02 s, 15 in. and 0.86 cal/cm2. The author cautions that changing settings can nuisance-trip critical loads. A field incident on a 20-year-old switchboard illustrates the danger of forcing equipment that will not operate.
Key points
- Incident energy above 1.2 cal/cm2 can cause second-degree burns; IEEE 1584 suggests a 2 s maximum arcing exposure time.
- Higher available fault current can reduce hazard because it shortens device clearing time.
- A main device may need separate line-side and load-side labels because its line side stays energized when open.
- 1,600 A/480 V example: coordinated settings give about 13-19 s clearing, 105 in. boundary, 22 cal/cm2 (Category 3); maintenance settings give 0.02 s, 15 in., 0.86 cal/cm2.
- Dual power paths let equipment be fully de-energized for work while operations continue.
- Changing settings can nuisance-trip critical loads.
Using it in design
- Arc-flash outputs should label both line and load sides of mains and compare normal versus maintenance-mode settings.
- Recommend maintenance switches or ERMS on large LV mains.
- Recommend dual-path topologies so work can be done de-energized.
- Record in the report the risk that maintenance settings may nuisance-trip critical loads.
Who should read it
Data centre electrical designers, engineers who run protection and selectivity studies and maintenance managers.
Related standards
- NFPA 70E
- IEEE 1584
Publication details
- Authors
- Bruce W. Young
- Publisher
- Consulting-Specifying Engineer
- Year
- 2012
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Bruce W. Young (2012). Preventing arc flash incidents by design. Consulting-Specifying Engineer. https://www.csemag.com/articles/preventing-arc-flash-incidents-by-design/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.