Dataprobe iBoot-PDU User Manual v251007w
Dataprobe
A manufacturer manual for the four- and eight-outlet switched and metered iBoot-PDU family covering installation, web, CLI and API management, automation and specifications, plus the model-to-inlet and outlet mapping in Appendix A.
On this page
Overview
The manual presents the iBoot-PDU series as intelligent, switched and metered PDUs managed remotely through a web browser interface. Each unit has four or eight independently switchable outlets; dual-input models (-2N15, -2N20, -2C10, -2C20) have two AC lines, with line A feeding outlets 1-4 and line B feeding outlets 5-8, and either line can power the unit's electronics. Dual inputs can be used to double the current for higher-current devices or to feed dual-power-supply devices from two separate sources. Pairs of outlets can be grouped so that one command powers down devices with dual power supplies.
Content covers installation (rack mounting, Ethernet, power source), the web interface (dashboard, global view, history, groups, sequences), device setup (email, outlets, remotes, IP, webhook, time, device log), automation (analog triggers, AutoPing, scheduling), management (users, cloud service, Fail2ban, whitelist, NMS, update), the command line interface, the RESTful API, the DMP protocol and USB interfaces (temperature monitor, modem, serial port, battery backup). The default IP address comes from DHCP or is 192.168.1.254 if no DHCP server is found; in versions 1.39 and above the default password includes the last three segments of the MAC address.
The specifications section gives 1U height, 11.0 in width for 4-outlet versions and 19.0 in for 8-outlet versions, 6 in depth and 3.25 kg weight. Operating temperature is 0 to 55 degrees C for IEC versions and up to 60 degrees C for NEMA versions; storage is minus 10 to 85 degrees C, altitude 2000 m and relative humidity 0-95% non-condensing. The input table covers N15 (115 VAC, 15 A total), N20 (115 VAC, 20 A), C14 (100-240 VAC, 10 A total at 240 V maximum) and C20 (100-240 VAC, 20 A total at 240 V maximum) inputs; outlets are N15 (115 VAC, 12 A maximum) and C13 (100-240 VAC, 10 A maximum). Safety compliance is UL 62368-1, IEC 62368-1 and CAN/CSA C22.2 No. 62368-1-14.
Appendix A lists for each SKU and model name the inlet plug, outlet type and outlet count, and distinguishes dual network ports and Rev A hardware, which has no fan in order to meet the specification ratings. Dual network ports and the power inlet arrangement are shown as separate features. It is a product manual; it provides model mapping that can validate PDU selection and does not expand configuration templates.
Key points
- Four- or eight-outlet, independently switched and metered PDU; managed by web, Telnet/serial CLI, RESTful API and DMP protocol.
- On dual-input models (-2N15, -2N20, -2C10, -2C20), line A feeds outlets 1-4 and line B feeds outlets 5-8; either line can power the electronics.
- Input ratings: N15 115 VAC 15 A total, N20 115 VAC 20 A, C14 100-240 VAC 10 A maximum (240 V), C20 100-240 VAC 20 A maximum (240 V).
- Outlet ratings: N15 115 VAC 12 A maximum, C13 100-240 VAC 10 A maximum.
- C10 variants (C14 input) are rated at 10 A total at 240 V maximum.
- Operating temperature 0-55 degrees C for IEC versions and 0-60 degrees C for NEMA versions; storage minus 10 to 85 degrees C; altitude 2000 m; humidity 0-95% non-condensing.
- Size: 1U height, 6 in depth; width 11.0 in for 4-outlet and 19.0 in for 8-outlet versions; weight 3.25 kg.
- Default IP is DHCP or 192.168.1.254; in versions 1.39 and above the default password is admin plus the last three MAC segments.
- Safety compliance UL 62368-1, IEC 62368-1, EN 62368-1 and CAN/CSA C22.2 No. 62368-1-14; warranty three years.
- Appendix A lists models with inlet plug, outlet type, dual network port and Rev A hardware (fanless) distinction.
Using it in design
- When selecting a rack PDU, use the Appendix A inlet-outlet mapping: compare N15/N20 and C14/C20 inputs with mains voltage (115 V or 100-240 V) and total current.
- If a dual-input model is chosen, connect lines A and B to two separate sources; take the two feeds of dual-supply servers from different lines and use outlet grouping to switch them off with one command.
- Limit operating temperature to 55 degrees C on IEC variants and 60 degrees C on NEMA variants; note that Rev A hardware has no fan, with respect to ratings.
- Limit the C14-input (C10) model to 10 A total at 240 V; carry the 10 A (C13) and 12 A (N15) per-outlet limits into the load calculation.
- For network security, add default password, IP, Fail2ban, whitelist and user settings to the commissioning checklist.
Who should read it
Electrical and IT infrastructure engineers designing in-rack power distribution and remote power management.
Document contents
- Important safety information
- General overview
- Quick start
- Installation
- Basic operation: web browser
- Device setup
- Automation
- Management
- Command line interface
- RESTful API
- DMP protocol
- USB interfaces
- Troubleshooting
- Specifications
- Compliance statements
- Technical support and warranty
- Appendix A: Models and configuration
- Appendix B: Time zone codes
Publication details
- Authors
- Dataprobe
- Publisher
- Dataprobe
- Year
- 2025
- Document number
- v251007w
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document. Metadata and original short summary only; no full text reproduced in library.
Citation
Dataprobe (2025). Dataprobe iBoot-PDU User Manual v251007w. Dataprobe. v251007w. https://cdn.shopify.com/s/files/1/0859/9181/7492/files/iboot-pdu_v251007w.pdf?v=1761598833
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
