Research paperPDF2026

Reframing Data Center Fire Safety as a Socio-Technical Reliability System: A Systematic Review

Fire (MDPI AG) · Riza Hadafi Punari, Kadir Arifin et al.

This PRISMA systematic review screens 2020-2025 studies of data-centre fire-safety management, benchmarks twelve empirical studies against NFPA 75 and NFPA 76, and shows the literature piles up on technical prevention while response and recovery are little studied.

CC BY 4.0: share with attribution

On this page

Overview

The study asks how holistically academic literature treats fire-safety risk management frameworks for data centres. The search found 806 records (Scopus 330, Web of Science 476); after screening, eligibility and quality appraisal, twelve empirical studies were synthesised and benchmarked against NFPA 75 and NFPA 76. Findings are organised in three themes: strategic management, fire risk and fire preparedness.

The review identifies electrical faults (arc faults, short circuits, overloads, deteriorated wiring) as the predominant cause of data-centre fires. Lithium-ion BESS and UPS equipment are reported to significantly amplify fire potential, especially in high-density and hyperscale halls where energy is concentrated. Evidence from major incidents shows battery management systems and gaseous suppression can be ineffective against self-oxidising Li-ion battery fires, and DC power systems carry combined fire and shock risk from arcs and leakage currents that conventional protection devices find hard to detect.

The imbalance is clear: the literature concentrates on technical prevention and electrical ignition sources, while emergency response, damage control and recovery are far less studied and identified as the critical research gap. The authors note that fire standards require risk-based and performance-based design to consider impaired fire-protection systems and failure scenarios. Benchmarking shows the NFPA standards take a more comprehensive lifecycle approach than the academic literature, and the literature is geographically concentrated in technologically advanced regions, particularly China.

Limits: only twelve empirical studies were synthesised, a small sample, and the search is limited to 2020-2025 and two databases. The conclusion is that data-centre fire safety should be managed as a socio-technical system involving technology, people and organisational processes.

Key points

  1. The search found 806 records (Scopus 330, Web of Science 476); twelve empirical studies were synthesised and benchmarked against NFPA 75 and NFPA 76.
  2. The review identifies electrical faults (arc faults, short circuits, overloads, deteriorated wiring) as the predominant cause of data-centre fires.
  3. Lithium-ion BESS and UPS equipment significantly amplify fire potential, especially in high-density and hyperscale halls.
  4. Evidence from major incidents shows battery management systems and gaseous suppression can be ineffective against self-oxidising Li-ion battery fires.
  5. DC power systems carry combined fire and shock risk from arcs and leakage currents that are hard to detect with conventional protection devices.
  6. Fire standards require risk-based and performance-based designs to consider impaired fire-protection systems and failure scenarios.
  7. Fire preparedness (emergency response, damage control, post-fire recovery) is the critical research gap.

Using it in design

  • Ask for a fire-safety design file that covers a lifecycle plan (aligned with NFPA 75 and NFPA 76) including emergency response, damage control and post-fire recovery, not only prevention and suppression.
  • Add to the design file the scenario in which BMS and gaseous suppression fail against a self-oxidising Li-ion fire in UPS and BESS areas.
  • Assess arc and leakage-current detection in DC power systems separately, beyond conventional protection devices.
  • In risk-based design, analyse impaired fire-protection systems (disabled, failed) as a separate scenario.

Who should read it

Engineers, risk managers and researchers planning data-centre fire-safety management, risk assessment and fire preparedness.

Document contents

  1. 1. Introduction
  2. 2. Methods (2.1 Systematic Searching Strategies: identification, screening, eligibility, quality appraisal; 2.2 Data Extraction and Analysis)
  3. 3. Results (3.1 Thematic Distribution of Findings, 3.2 Strategic Management, 3.3 Fire Risk, 3.4 Fire Preparedness)
  4. 4. Discussion (4.1 Imbalance in Thematic Emphasis, 4.2 Strategic Management Practices and Gaps, 4.3 Electrical Hazards and High-Consequence Fire Risks, 4.4 Fire Preparedness Gaps, 4.5 Systematic Literature Contributions, implications, limitations and research gaps)
  5. 5. Conclusions

Related standards

  • NFPA 75
  • NFPA 76
  • NFPA 855

Read the document

dc-fire-safety-socio-technical-review-2026.pdf

PDF · 1.4 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Riza Hadafi Punari; Kadir Arifin; Mohamad Xazaquan Mansor Ali; Kadaruddin Ayub; Azlan Abas; Ahmad Jailani Mansor
Publisher
Fire (MDPI AG)
Year
2026
Volume
9
Issue
4
Pages
151
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Riza Hadafi Punari; Kadir Arifin; Mohamad Xazaquan Mansor Ali; Kadaruddin Ayub; Azlan Abas; Ahmad Jailani Mansor (2026). Reframing Data Center Fire Safety as a Socio-Technical Reliability System: A Systematic Review. Fire (MDPI AG). 9(4), 151. https://doi.org/10.3390/fire9040151

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.