ABM Technology and Battery Testing in Eaton UPS Products
Eaton
Describes an opportunistic charging scheme for VRLA UPS batteries as an alternative to continuous float charging, which accelerates positive-grid corrosion.
On this page
Overview
VRLA batteries marketed with a 10-year design life are replaced every 4-5 years on average in UPS service and can be about 30% of UPS cost. ABM addresses this with a three-stage cycle: charge, float with an automatic battery test, and a long rest with the charger off and open-circuit voltage monitored.
Charge mode uses constant voltage at float level with current above 0.1C, up to a 100-hour limit, then 48 h of float with an automatic battery test after 24 h. Rest mode turns the charger off for about 28 days; charging restarts after an outage longer than 15 s, low open-circuit voltage, timer expiry or battery replacement.
The battery test discharges at about 15% load for up to 6 minutes then at 50% load for 45 s, and compares voltage to a load-dependent end-of-life threshold. On day 27 of rest, a 15-minute battery still provides all but about 30 seconds of its runtime. Calculated service life at 25 C increases by about six years versus float charging.
The paper presents accelerated-life and long-term test evidence, and states when to disable the scheme: with wet-cell batteries.
Key points
- VRLA batteries marketed with a 10-year design life are replaced every 4-5 years on average in UPS service and can be about 30% of UPS cost.
- Charge mode: constant voltage at float level, current above 0.1C, up to 100 hours; then 48 h float with an automatic test after 24 h.
- Rest mode turns the charger off for about 28 days; an outage over 15 s, low open-circuit voltage, timer expiry or battery replacement restarts charging.
- The test discharges at ~15% load for up to 6 minutes then 50% load for 45 s against a load-dependent end-of-life threshold.
- On day 27 of rest a 15-minute battery still gives all but about 30 seconds of runtime.
- Calculated service life at 25 C rises by about six years versus float charging.
Using it in design
- For battery/UPS selection, record charging method (float, opportunistic/ABM, Li-ion BMS) and automatic battery test capability.
- Default the VRLA replacement interval to 4-5 years unless managed charging is specified.
- Warn if opportunistic charging is applied to flooded or wet-cell batteries.
- Include a 2-3% runtime derating at the end of the rest period in the autonomy margin.
Who should read it
UPS designers and facility operators planning VRLA battery life and maintenance.
Related standards
- IEEE 1188
- IEC 60896-21
Publication details
- Authors
- Eaton
- Publisher
- Eaton
- Year
- 2018
- Document number
- WP09-18 (AP162001EN)
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Eaton (2018). ABM Technology and Battery Testing in Eaton UPS Products. Eaton. WP09-18 (AP162001EN). https://itpccit.com/wp-content/uploads/2022/02/Eaton-ABM-White-Paper-AP162001EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.