Strengthening Data Center Operations Using Grid-Forming Battery Energy Storage as a Line-Interactive Uninterruptible Power Supply
International Journal of Electrical Power & Energy Systems (Elsevier BV) · Arian Azizi, Samaneh Morovati et al.
An IJEPES 2026 paper: a grid-forming battery storage system acting as a medium-voltage line-interactive UPS smooths millisecond-scale AI load fluctuations at the interconnection point.
On this page
Overview
The paper addresses the millisecond-scale pulsating load fluctuations created by AI workloads. These strain the bulk power system and complicate energy management, interconnection and local generation planning. The study looks at using energy storage to manage this high-frequency load dynamic while keeping the data centre running without interruption.
The method is an electromagnetic transient (EMT) study built on a detailed analysis of AI load characteristics. A grid-forming battery energy storage system is evaluated in grid-connected and islanded modes and in the transitions between them. The proposed approach positions the battery as a medium-voltage, line-interactive UPS while also smoothing load transients at the point of interconnection.
According to the results, the architecture markedly attenuates fast power fluctuations, improves voltage and power quality at the grid interface, and raises overall data-centre reliability. The work is a simulation study; the related standard is IEC 62040-3.
Key points
- AI workloads produce fast, pulsating load fluctuations on a millisecond scale.
- The grid-forming BESS is treated as a medium-voltage line-interactive UPS.
- Grid-connected, islanded and transition modes are examined with electromagnetic transient analysis.
- The architecture attenuates fast power fluctuations and improves voltage and power quality at the grid interface.
- One storage system takes on both the backup-power and the load-smoothing roles.
Using it in design
- For AI halls, include a medium-voltage BESS serving as both UPS and load smoother as a power-chain topology option in the comparison.
- Define allowed power swing and rate of change at the interconnection point together with the millisecond-scale profile of the AI load.
- Require EMT simulation covering grid-connected, islanded and transition modes at design stage.
- For a line-interactive UPS approach, state the output performance explicitly using the IEC 62040-3 classification in the specification.
Who should read it
Electrical engineers designing the power chain and grid connection of AI data centres, and energy storage system designers.
Related standards
- IEC 62040-3
Publication details
- Authors
- Arian Azizi; Samaneh Morovati; Amin Zamani; Joshua Piruzza; David Guo; Zhuoning Liu; Pasi Taimela
- Publisher
- International Journal of Electrical Power & Energy Systems (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Arian Azizi; Samaneh Morovati; Amin Zamani; Joshua Piruzza; David Guo; Zhuoning Liu; Pasi Taimela (2026). Strengthening Data Center Operations Using Grid-Forming Battery Energy Storage as a Line-Interactive Uninterruptible Power Supply. International Journal of Electrical Power & Energy Systems (Elsevier BV). https://doi.org/10.1016/j.ijepes.2026.111638
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.