ESTAP DC-Book: Data Center Guide and Product Catalogue
Original title DC-BOOK by ESTAP
Estap
Estap's 82-page DC-Book catalogue: Uptime Tier I-IV summary, PUE measurement (1.91 in the worked example), contained cold aisle and air leakage measures, plus cabinet, corridor and monitoring part numbers.
On this page
Overview
The DC-Book is a data centre guide and product catalogue from the Turkish manufacturer Estap. Opening sections cover, briefly and in general terms, why data centres are needed, business models (operator, colo room and service provider, managed service provider), the Uptime Institute Tier I-IV levels and stakeholder concerns (CEO, CFO, facility manager, IT). Tier I is summarised as dedicated non-redundant infrastructure, Tier II as redundant capacity components, Tier III as concurrent maintainability and Tier IV as fault tolerance.
The power and PUE section explains PUE as total facility power divided by IT equipment power and proposes three measurement levels: basic (UPS output against facility input), professional (rack PDU measurement) and advanced. In the worked example facility input between two dates is 1,100.5 MWh and UPS output 575,997 kWh, giving a PUE of about 1.91; a traditional server room design is said to yield about 2.0. PUE reduction tips include contained cold aisles, free cooling (which does not pay off if poorly tuned), reduced air leakage, fan speed adjustment and higher set points.
The cooling section says rising rack density overloads classic CRAC systems and names airflow and space as the main challenges. Airflow inefficiency comes from static pressure difference, bypass under racks and recirculation; remedies include sealing around CRAC units, raising the raised-floor height, sealing cable openings, using blanking panels and keeping contained cold aisle pressure below 5-7 Pa. Perforated tiles go at least 2 m from CRAC units. Most of the book is a product catalogue: cabinets (W600, W800, W300), corridor solutions, monitoring, intelligent PDUs and KVM.
Key points
- Tier I: non-redundant dedicated infrastructure; Tier II: redundant capacity components; Tier III: concurrently maintainable; Tier IV: fault tolerant (Uptime Institute launched the standards in 2005).
- PUE = total facility power / IT equipment power; a traditional server room is about 2.0 or higher and efficiency improves as it nears 1.0.
- Worked example: facility input 1,100.5 MWh, UPS output 575,997 kWh, PUE of about 1.91.
- Measurement levels: basic (UPS output and facility input), professional (rack PDU), advanced and master PUE.
- PUE reduction: contained cold aisle, free cooling (tuned correctly), less air leakage, lower fan speed, higher set point and controlling CRAC on supply rather than return temperature.
- Contained cold aisle pressure should not exceed 5-7 Pa; if it does, the setup has a fault.
- Perforated tiles go at least 2 m from CRAC units and cable openings are sealed completely.
- Server heat output is said to be ten times that of ten years earlier, overloading classic CRACs at high density.
- Catalogue sections: W600/W800/W300 cabinets, high-density cabling, colocation cabinets, corridor solutions, environmental monitoring, intelligent PDUs and KVM.
Using it in design
- Fix the target Tier level, and the redundancy it implies (redundant components, concurrent maintenance, fault tolerance), at the start of design.
- Plan PUE metering at design stage as meter points (facility input, UPS output, rack PDU).
- Write containment sealing details into the specification (blanking panels, sealed side panels, cable gland seals, self-closing doors) and use the 5-7 Pa limit as an acceptance criterion.
- Evaluate the PUE gain from moving CRAC control from return to supply air temperature and raising set points.
- Include commissioning and tuning steps for free cooling in the contract scope.
Who should read it
Founders of small and mid-size data centres, designers selecting cabinets and containment, and operators starting PUE measurement.
Document contents
- Why do we need data centers
- Business models in data center
- Tier levels
- Stakeholders and their concerns
- Key elements of data center
- Power in data center and PUE
- Cooling solutions
- Operational excellence
- Cabinets
- Corridor solutions
- Environmental monitoring solutions
- Intelligent power distribution units
- Consoles with KVM switch
- Estap product part numbers
Publication details
- Authors
- Estap
- Publisher
- Estap
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official85-page PDF read at selected application pages. Publication year not established from the inspected PDF; URL/upload timestamps not substituted. EN-body exclusion from R2 removed; no source-language mislabelling.
Citation
Estap DC-BOOK by ESTAP. Estap. https://estap.com.tr/mobile/en/pdf/DC-Book-by-Estap-catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
