Free Cooling Potential of Turkey for Datacenters
European Journal of Science and Technology · Gül Nihal Güğül
Güğül's 2018 EJOSAT paper: using Ankara measurements, free cooling share and PUE are calculated for six Turkish cities; PUE is 1.23, 1.37 and 1.37 in Erzurum, Ankara and Konya, and Antalya saves 46 percent a year.
On this page
Overview
The paper notes that data centre cooling electricity is 30-50 percent of total consumption and that a location's potential should be known before a free cooling system is installed. It calculates free cooling potential for Ankara, Antalya, İzmir, Erzurum, Konya and Trabzon at supply air temperatures between 15 and 21 °C, using the average of 2015 and 2016 hourly temperature data from the General Directorate of Meteorology.
The method defines three operating modes: free cooling when outdoor temperature is at or below supply temperature, partial free cooling between supply and return temperature, and mechanical cooling at or above return temperature. For example at Tsat 15 °C and Trat 22 °C, Erzurum has 6,381 hours a year in the free cooling zone, Ankara 4,904 and Antalya 2,508. Potential is given as the share of suitable hours in total hours.
For PUE, a data processing centre of the General Directorate of Land Registry and Cadastre in Ankara was measured: a 100 m² cabinet room with 18 cabinets, two UPS rooms and a free cooling chiller, with cabinet consumption measured hourly. The system ran in mechanical mode 70 percent of the time and only on pumps for the remaining 30 percent. PUE values were recalculated as if the same data centre were in the other cities.
Results show free cooling suits Erzurum, Ankara and Konya: PUE values are 1.23, 1.37 and 1.37 and potential is almost 100 percent for eight, six and six months respectively, depending on supply temperature. Beyond cold climates, Antalya at Tsat 19 °C saves 46 percent energy annually. Results rest on temperature data, one data centre's measurements and a two-year meteorological average.
Key points
- Six cities are studied: Ankara, Antalya, İzmir, Erzurum, Konya and Trabzon; supply air temperatures 15-21 °C.
- Free cooling rule: Toat ≤ Tsat full free cooling, Tsat < Toat < Trat partial, Toat ≥ Trat mechanical cooling.
- Hours in the free cooling zone at Tsat 15 °C and Trat 22 °C: Erzurum 6,381, Ankara 4,904, Konya 4,808, Trabzon 4,454, İzmir 3,391, Antalya 2,508 h/year.
- PUE values: Erzurum 1.23, Ankara 1.37, Konya 1.37.
- Potential is almost 100 percent in Erzurum, Ankara and Konya for eight, six and six months respectively (Tsat 17-21 °C).
- Antalya at Tsat 19 °C is calculated to save 46 percent energy annually.
- The measured data centre has 18 cabinets; the system runs in mechanical mode 70 percent of the time.
- Cooling can be 30-50 percent of data centre electricity; in efficient centres this share can fall to about 10 percent.
Using it in design
- For a site considering free cooling chillers or dry coolers, split hourly outdoor temperature into three modes against supply and return temperature to get the annual hour distribution.
- Show how raising supply temperature affects free cooling hours and PUE with sensitivity analysis over 15-21 °C.
- In site selection, compare cold-climate cities (such as Erzurum) on PUE and mechanical mode hours.
- In a hot climate (Antalya), even if saving reaches 46 percent, size mechanical cooling capacity for full load.
- Verify results with typical meteorological year data instead of a two-year average.
Who should read it
Mechanical designers and energy analysts doing data centre site selection and free cooling feasibility.
Document contents
- Introduction
- Methodology (temperature data, free cooling potential calculation, PUE value)
- Results and discussion
- Conclusion
Publication details
- Authors
- Gül Nihal Güğül
- Publisher
- European Journal of Science and Technology
- Year
- 2018
- Document number
- 14, 17–22
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official DergiPark article page read; direct PDF retry returned HTTP 429. Facts here are bounded to the publisher abstract, not uninspected full text.
Citation
Gül Nihal Güğül (2018). Free Cooling Potential of Turkey for Datacenters. European Journal of Science and Technology. 14, 17–22. https://doi.org/10.31590/ejosat.419027
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
