Generation of Real World Maintenance Data of Data Center Uninterruptible Power Supply Systems and Failure Prediction
IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)) · L. Frederick, M. M. Manohara Pai
An IEEE Access (2025) paper by Frederick and Manohara Pai: a GenAI pipeline that processes CRM records and field service reports to predict UPS failures reaches weighted accuracy and precision above 90% and an F1 score of 0.91.
On this page
Overview
As data-centre demand grows, so does reliance on UPS systems for continuous power. The study argues that predicting UPS failures from structured and unstructured data requires careful data preparation, and presents techniques for processing both data types with a generative AI (GenAI) model to produce actionable insight.
The model uses two feature sets: records from the customer relationship management (CRM) system and service completion reports written by field service representatives. The key innovation is the use of instructional prompts and a rule set made of keyword mappings and acronym references so that domain-specific language is read correctly. The study also captures global performance insights for UPS systems and adds data visualisation.
The visualisations support identifying failure patterns, including symptomatic and asymptomatic service-order categories, failure origin, failure type and criticality, which enables proactive maintenance strategies. Model validation shows weighted accuracy and precision above 90% and an F1 score of 0.91.
Key points
- The model works from two feature sets: CRM records and field service completion reports.
- Domain language is interpreted through a rule set of instructional prompts, keyword mappings and acronym references.
- Failure patterns are identified by service category, failure origin, failure type and criticality.
- Validation gives weighted accuracy and precision above 90% and an F1 score of 0.91.
- The paper appears in IEEE Access volume 13 (2025) under a CC-BY licence.
Using it in design
- Enrich UPS reliability inputs with field service data; keep failure origin and criticality in structured fields.
- Make sure the reliability library in your tooling accepts site-specific failure rates.
- Use a standard keyword and acronym vocabulary in service reports so automated analysis is possible later.
- Prioritise the preventive maintenance plan by failure category and criticality level.
Who should read it
Operations engineers managing UPS maintenance and reliability programmes, and data analytics and maintenance planning teams.
Publication details
- Authors
- L. Frederick; M. M. Manohara Pai
- Publisher
- IEEE Access (Institute of Electrical and Electronics Engineers (IEEE))
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/legalcode (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
L. Frederick; M. M. Manohara Pai (2025). Generation of Real World Maintenance Data of Data Center Uninterruptible Power Supply Systems and Failure Prediction. IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)). https://doi.org/10.1109/access.2025.3605758
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.