The June 2017 owner's manual from Juice Goose (LynTec) for the JGJr, JG8LED, JG9, JG9-NS, JG11-15A and JG11-20A rack power distribution units. The units are built for 120 VAC, 60 Hz, with 12 A per outlet and a 15 A total limit (20 A on the JG11-20A).
On this page
Overview
This four-page manual covers the safety precautions, front and rear panel items, internal protection components and troubleshooting steps for the JG series of rack power distribution units made for the North American market. Six models share the document: JGJr, JG8LED, JG9, JG9-NS, JG11-15A and JG11-20A. The products provide basic outlet multiplication and overcurrent protection; no metering, remote switching or network monitoring function is described.
The electrical limits are stated plainly. Every model is designed for a 120 VAC, 60 Hz supply, and operation at other voltages is flagged as a damage and injury risk. Each NEMA 5-15R outlet on the rear panel carries up to 12 A at 120 V. The combined current of all outlets is limited to 15 A on every model except the JG11-20A, which is limited to 20 A. The power cord follows the same split: a NEMA 5-15P plug on the 15 A models and a NEMA 5-20P plug on the JG11-20A.
The most important operational distinction is between switched and unswitched outlets. The lighted front switch controls only the switched outlets on the rear panel; the unswitched front outlet on the JG9 and JG11 stays live with the switch off. The JG9-NS has no front switch. Unplugging the power cord is given as the way to remove power from the unit completely. Grounding is mandatory, and defeating the ground pin on the plug is prohibited.
For protection, the units carry a fast-acting metal oxide varistor between hot and neutral and a line capacitor that reduces high-frequency line noise. The circuit breaker is built into the power switch on the JGJr, sits on the front panel of the JG11, and is on the rear panel of the JG8LED, JG9 and JG9-NS. The sequence after an overload trip is defined: switch off, cut the load to within the rated current, wait about 30 seconds, reset the breaker and switch back on. There are no user-serviceable parts inside.
Key points
- Models covered: JGJr, JG8LED, JG9, JG9-NS, JG11-15A and JG11-20A; the manual is dated 6-17 (June 2017).
- Design supply is 120 VAC, 60 Hz; operating at other voltages risks damage and injury.
- Each NEMA 5-15R outlet is rated for loads up to 12 A at 120 V.
- Total current is limited to 15 A; only the JG11-20A has a 20 A breaker and a 20 A cord with a NEMA 5-20P plug.
- The front switch does not disconnect the unswitched outlets; full isolation means unplugging the cord.
- After an overload trip, reduce the load, wait about 30 seconds and reset the breaker.
- Internal protection consists of a metal oxide varistor and a line capacitor between hot and neutral.
- The JG8LED has two pull-out, dimmable, rotatable LED light tubes.
Using it in design
- Use this series only on 120 V, 60 Hz single-phase circuits; exclude it from selection for 230 V or 208 V rack feeds.
- In the rack load calculation check both limits together: 12 A per outlet and 15 A per unit (20 A for the JG11-20A).
- Do not treat the front switch as an isolation point in maintenance procedures; because the unswitched outlet stays live, write unplugging the cord as an explicit step.
- Match the branch circuit and receptacle to the model: NEMA 5-15 for the 15 A models and NEMA 5-20 for the JG11-20A.
- Treat the varistor and capacitor as basic protection; plan a separate surge protection and UPS layer for critical IT loads.
Who should read it
System integrators and field technicians fitting out audio, video and small IT racks in North America, and designers selecting in-rack power distribution.
Document contents
- Safety Precautions
- Cautions
- Disclaimer
- Front Panel
- Rear Panel
- Internal Protection Components
- Trouble Shooting
- Repair
- Other High Quality Products
Publication details
- Authors
- Juice Goose
- Publisher
- Juice Goose / LynTec
- Year
- 2017
- Document number
- 6-17
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Juice Goose (2017). JG Series Power Distribution: Owner’s Manual. Juice Goose / LynTec. 6-17. https://lyntec.com/wp-content/uploads/2026/06/jg-series-manual-2017.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.