Technical guideFree to read2009

Circuit Breaker Selective Trip Coordination in 225A and 400A Distribution Panelboards

Uptime Institute / LayerZero Power Systems · Anthony Pinkey

A technical paper written by LayerZero Power Systems for the Uptime Institute's 2009 symposium explaining why selectivity is lost in data-centre distribution panelboards: a 300 kVA, 3.5% impedance transformer delivers 23,820 A of fault current at a 208 V secondary, and conventional branch breakers cannot trip selectively against the main above about 6,000 A.

On this page

Overview

The paper appeared in the proceedings of the Uptime Institute's Green Enterprise IT Symposium of 13 to 16 April 2009 as a contribution from a research-underwriting manufacturer, and the Institute states that it does not endorse the opinions or products in it. The subject is the data-centre distribution panelboard in which a 225 A or 400 A main breaker feeds up to 42 branch breakers, typically rated 10 A to 100 A. Selective tripping is defined as only the nearest upstream breaker opening when a fault occurs.

The problem starts with growing transformer ratings. Until the early 2000s, distribution transformers on the data-centre floor were generally rated up to 125 kVA; with 3.5% impedance and a 208 V secondary the fault current is 9,925 A, and branch breakers with 10,000 A interrupting capacity were adequate. From 2005, high power density brought 225 kVA and 300 kVA transformers. By the same calculation a 300 kVA unit delivers 23,820 A. As a result the main breaker trips instead of, or together with, the branch breaker, and every load on the panel loses power.

The author stresses an important distinction: a 22 kA main breaker with branch breakers series-rated for 22 kA is a safety arrangement only. A series rating says that the main breaker will protect a branch breaker from fire or explosion when the branch device cannot handle the fault current; it says nothing about the fault being cleared by the branch breaker alone. Thermal-magnetic breakers that wait for a zero crossing cannot extinguish the arc before the next current zero. According to the figure reported in the paper, such a 10,000 A branch breaker trips selectively when available fault current is below about 6,000 A.

The proposed solution is a current-limiting branch breaker. It does not wait the 8 to 9 ms for a zero crossing: a linear magnetic mechanism opens the contacts within 1 ms and the fault current is cleared in about 2 ms. The paper states that this design trips selectively up to 35 kA. Fast clearing also shortens the time the other critical circuits on the same bus are exposed to the voltage disturbance. The paper dates from 2009 and comes from a manufacturer; selectivity for a specific breaker pair is demonstrated with current manufacturer coordination tables.

Key points

  1. Selective tripping: on a fault, only the nearest upstream breaker opens, with no other breaker between it and the fault.
  2. In a data-centre panelboard a 225 A or 400 A main breaker feeds up to 42 branch breakers, typically rated 10 A to 100 A.
  3. A 125 kVA, 3.5% impedance transformer with a 208 V secondary delivers 9,925 A of fault current.
  4. A 300 kVA transformer at the same impedance delivers 23,820 A at the secondary; fault currents of 16,000 to 30,000 A are seen in data centres.
  5. A series rating (22 kA, for example) is a safety protection only and does not demonstrate selective tripping.
  6. A zero-crossing branch breaker with 10,000 A interrupting capacity trips selectively against the main when fault current is below about 6,000 A; above that the main trips as well.
  7. A current-limiting branch breaker opens its contacts within 1 ms, clears the fault in about 2 ms and, according to the paper, trips selectively up to 35 kA.

Using it in design

  • Calculate secondary fault current for every panelboard from transformer rating and impedance, and repeat the coordination study whenever transformer size grows.
  • Do not accept a series rating as proof of selectivity in the specification; ask for the manufacturer's selectivity table or a time-current curve study for the main and branch breaker pair.
  • Where fault current at the panel bus exceeds about 6,000 A, consider current-limiting branch breakers or smaller transformers with higher impedance.
  • Add to the availability analysis, as a common failure point, that a single branch fault can drop up to 42 circuits.
  • During commissioning, compare each breaker setting on site with the settings in the coordination study.

Who should read it

Electrical engineers designing data-hall power distribution, protection coordination specialists, and specifiers of PDUs and remote power panels.

Document contents

  1. Introduction
  2. History: A Change In Transformers Affects Mission Critical Systems
  3. Recognizing The Problem: Circuit Breakers Are Not Coordinated Properly
  4. Zero-crossing Circuit Breaker Design Is Not Sufficient
  5. Solution
  6. Conclusion

Publication details

Authors
Anthony Pinkey
Publisher
Uptime Institute / LayerZero Power Systems
Year
2009
Event
Uptime Institute Green Enterprise IT Symposium, New York, April 13–16, 2009
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Anthony Pinkey (2009). Circuit Breaker Selective Trip Coordination in 225A and 400A Distribution Panelboards. Uptime Institute / LayerZero Power Systems. Uptime Institute Green Enterprise IT Symposium, New York, April 13–16, 2009. https://www.layerzero.com/documentation/selective-trip-coordination.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.