LS Bus Duct System: GH-P Design and Installation Manual
LS ELECTRIC (legacy LSIS document) · LSIS
This January 2013 catalogue from LSIS (now LS ELECTRIC) combines technical data, component dimensions, route design rules and installation instructions for the GH-P sandwich-type busduct rated 600 A to 6500 A; hangers are spaced at 1.5 m as standard and 2 m at most, and joints may not sit inside walls or floors.
On this page
Overview
The 48-page document has four parts: a description of the GH-P type, technical data, compositions and dimensions, and a design guide with an installation manual. GH-P is a compact busduct whose conductors are insulated with a seamless PVC coating at least 1.5 mm thick and laid tightly together. Rated voltage is AC 660 V and rated current 600 to 5000 A with aluminium conductors or 600 to 6500 A with copper. The indoor type is IP41 to IP42 and the outdoor type IP55 to IP65. The document dates from 2013; IEC 60439-2 is among the applied standards, and the limits given are specific to this product and edition.
The technical data section tabulates line-to-line voltage drop in volts per 100 m for aluminium and copper conductors, at 50 and 60 Hz and power factors from 1.0 to 0.6, at a conductor temperature of 95 °C. Short-time current capacity is given for 1 second: 40 kA at 600 A and 80 kA at 1600 and 2000 A. The allowable conductor temperature is 95 °C at 40 °C ambient, a temperature rise of 55 °C. The current correction factor for ambient temperature is 1.00 at 40 °C, 0.90 at 50 °C, 0.80 at 60 °C and 1.13 at 25 °C.
The design guide asks for present and future load, ambient temperature above 40 °C, voltage drop on long runs and short-circuit strength to be assessed together when choosing a route. Straight runs are preferred, elbows avoided, and spare plug-in positions left for future load. The minimum distance between parallel runs depends on whether joints sit side by side or staggered and on indoor or outdoor use. A joint must be more than 240 mm from a wall surface. Hangers are placed at a standard 1.5 m spacing, never more than 2 m. Use of an expansion unit depends on whether the ends of the run are fixed or free, on branching at each storey and on run length.
The installation manual lists the steps for storage, preparation, laying, jointing, connection to equipment, vertical hangers, housing earthing, testing after laying and maintenance. Joints are made by tightening two bolts alternately until the leaf springs are almost flat, with no torque wrench needed; if clamping is insufficient the joint cover will not fit. Each joint allows a dimensional adjustment of about ±3 mm. Insulation resistance should be measured section by section during laying; in a dry atmosphere a value around 100 MΩ is expected with a 500 V megger, and below 5 MΩ calls for investigation. Annual maintenance covers appearance, environment and joint temperature; leaf-spring joints need no periodic retightening.
Key points
- Ratings: AC 660 V; Al conductor 600 to 5000 A, Cu conductor 600 to 6500 A; 50/60 Hz; service conditions up to 1000 m altitude, -20 to 40 °C ambient, up to 97% humidity.
- Degree of protection: indoor IP41 to IP42, outdoor IP55 to IP65, weather-proof type IP54.
- Routine tests: at least 5 MΩ insulation resistance with a 500 V DC megger, and AC 7000 V withstand for 1 minute.
- Short-time current capacity (1 s): 40 kA at 600 A; 50 kA at 800 and 1000 A; 60 kA at 1200 to 1500 A; 80 kA at 1600 and 2000 A.
- Voltage drop example (copper, 50 Hz, power factor 0.8, 95 °C): 8.10 V per 100 m at 2000 A and 6.56 V per 100 m at 5000 A; aluminium at 2000 A is 8.69 V per 100 m.
- Temperature: allowable conductor temperature 95 °C, a 55 °C rise at 40 °C ambient. Ambient correction factors: 30 °C 1.09; 40 °C 1.00; 45 °C 0.95; 50 °C 0.90; 60 °C 0.80.
- Parallel run spacing (indoor, 600 to 6500 A): 150 mm for 3-wire and 160 mm for 4-wire when joints are side by side; 85 mm and 95 mm when joints are staggered. Outdoor: 200/250 mm and 150/180 mm.
- Joints may not be inside walls or floors; a joint must be more than 240 mm from a wall surface, more than 450 mm from a floor where a vertical spring hanger is used and more than 300 mm with a vertical fixed hanger.
- Hanger spacing is 1.5 m as standard and 2 m at most; the hanger stud is M12. On horizontal runs an expansion unit, where needed, is fitted every 40 to 50 m.
- Clamping torques for equipment connections are tabulated in kg cm: M8 120-150, M10 240-500, M12 420-1020, M16 1050-1300. Made-to-measure pieces take at least 2 weeks to deliver.
Using it in design
- Select the busduct rating with future load included, and derate with the factor table if the data hall or riser ambient exceeds 40 °C (for example 0.90 at 50 °C).
- For long feeder runs, calculate voltage drop from the tabulated V per 100 m value for the load power factor and conductor material.
- Compare the short-circuit current at the transformer output with the busduct's 1-second capacity (for example 80 kA at 2000 A).
- On the route drawing, keep joints out of wall and floor penetrations: at least 240 mm from a wall and 300 or 450 mm from a floor depending on hanger type.
- Leave 85 to 160 mm (indoor) between parallel A and B runs according to joint position, and place hangers at 1.5 m spacing without exceeding 2 m.
- Write section-by-section insulation resistance measurement into the commissioning plan, with an overall measurement against the 5 MΩ lower limit once the run is complete.
Who should read it
Electrical engineers designing low-voltage main distribution and vertical riser feeds with busduct, installation crews and maintenance leads.
Document contents
- Description of GH-P type: features and advantages, structure, ratings, finish color, test
- Technical data of GH-P type Busduct: voltage drop, short time current capacity, impedance, temperature characteristics
- Compositions and dimensions of GH-P type busduct: distribution system, cross section and busbar size, feeder, tap off and plug-in busduct, elbow, tee and offset, flanged end, reducer, end closure, floor and wall flange, hangers, expansion unit, flexible conductor, plug-in and tap boxes
- Design guide: considerations in layout design, reasonable distribution system design, minimum distance between parallel-installed busduct, position of the joint point, minimum clearance to wall and floor, hanger supporting, how to apply the expansion, actual measurement
- Installation manual: general common precautions, jointing procedure, connection with equipment, vertical fixed (spring) hanger, earthing of housing, test and checking after the laying, plug-in box installation sequence, maintenance and checking
- Certificate
Publication details
- Authors
- LSIS
- Publisher
- LS ELECTRIC (legacy LSIS document)
- Year
- 2013
- Document number
- LS Bus Duct System(E) 2004.08/(03) 2013.01
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LSIS (2013). LS Bus Duct System: GH-P Design and Installation Manual. LS ELECTRIC (legacy LSIS document). LS Bus Duct System(E) 2004.08/(03) 2013.01. https://www.ls-electric.com/upload/customer/download/1068/Busduct_GH-P%20Type_E_1301.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
