Distribution and Power Transformers
Matelec Group
Matelec Group's 2014 catalogue is a manufacturer's guide to liquid-filled transformers: it covers selection inputs, accessories, IEC 60076 tests, overload limits, installation and maintenance for oil-immersed distribution units (50 to 3150 kVA, up to 36 kV) and power transformers up to 120,000 kVA and 245 kV.
On this page
Overview
The 44-page catalogue from Matelec, founded in 1974 to make distribution transformers, is written more as a selection guide than a product list. Its stated aim is to help buyers define their needs. Section two treats transformer characteristics under general, electrical and mechanical headings, followed by accessories for distribution and power transformers (bushings, cable boxes, protective devices). Section three covers testing, operation, installation and maintenance. The document dates from 2014 and concentrates on oil-immersed units; dry-type transformers are outside its scope.
The electrical design section lists the inputs to settle before ordering: power rating, primary and secondary voltages, ambient temperature and temperature rise, installation altitude, short-circuit impedance, vector group, no-load and load losses, frequency and tolerances. Short-circuit impedance is usually between 4% and 6% for distribution transformers and above 7% for power transformers, and transformers working in parallel should have equal impedance. The standard design suits altitudes up to 1000 m. For installations with heavy converter loading, the order must say so if total harmonic content is expected to exceed 5% or even harmonic content 1%.
The testing section separates routine, type and special tests under IEC 60076. Routine tests are applied to every unit: winding resistance, voltage ratio and phase displacement, short-circuit impedance and load loss, no-load loss and current, and dielectric tests. The operation section describes the checks before first energisation, an example overload table for 30 °C ambient, inrush current and protection; high-voltage and low-voltage fuse ratings are tabulated by transformer rating and voltage. In the overload table the permitted duration depends on the preceding load level.
The installation section allows pole mounting up to 250 kVA and ground mounting (kiosk, outdoor or indoor) for larger ratings. Indoors and outdoors, an oil collection pit filled with gravel and covered with steel mesh is required under the transformer. An indoor room has two ventilation openings on opposite sides, the inlet at ground level and the outlet at ceiling level. The opening area is calculated from the total losses and the height difference, assuming a 10 °C air temperature rise between inlet and outlet, and the outlet area is 1.15 times the inlet. Maintenance is divided into a visual inspection every three months, oil checks, and an inspection of protective accessories every three years.
Key points
- Oil-immersed distribution transformers: 50 to 3150 kVA, up to 36 kV; power transformers: 3150 to 120,000 kVA, up to 245 kV.
- Short-circuit impedance is usually 4% to 6% for distribution transformers and above 7% for power transformers; higher impedance raises voltage drop and lowers short-circuit current.
- Cooling is identified by a four-letter code (ONAN, ONAF, OFAN, OFAF, OFWF, ODAF); an ONAN/ONAF transformer can run at roughly 25% higher rating in ONAF mode.
- The standard design suits altitudes up to 1000 m, and higher sites must be stated in the order. Basic insulation levels are 75, 95, 125, 170, 200, 325 and 650 kV.
- Limit under heavy converter loading: 5% total harmonic content and 1% even harmonic content; expected excess is taken into the design.
- Example overload table (30 °C ambient, windings at 120 °C at the end): after full load, 15% overload for 120 minutes, 25% for 60 minutes, 50% for 10 minutes; after half load, 25% overload for 120 minutes.
- The inrush current peak can reach the short-circuit current amplitude for a few periods and decays to the nominal value in about one second.
- Ventilation: inlet at ground level and outlet at ceiling level on opposite sides; 10 °C air temperature rise assumed; outlet area 1.15 times the inlet area.
- Pole mounting applies up to 250 kVA; the oil pit capacity must exceed the transformer oil volume and the gravel together.
- Maintenance: visual inspection every three months; oil dielectric strength every three years for hermetically sealed types and yearly for others; Buchholz relay, thermometer and similar accessories every three years.
Using it in design
- Write the catalogue's full input list into the transformer enquiry: rating, voltages, ambient temperature, altitude, short-circuit impedance, vector group, guaranteed no-load and load losses, frequency.
- Calculate the harmonic content of converter loads such as UPS rectifiers; tell the manufacturer if the 5% total or 1% even harmonic limit is exceeded.
- For transformers that will run in parallel, specify equal short-circuit impedance and choose the impedance together with the low-voltage short-circuit current calculation.
- Size the transformer room ventilation openings from the total losses of all equipment in the room; put the inlet at floor level and the outlet at ceiling level on the opposite wall, with the outlet 15% larger.
- Plan an oil collection pit and oil extraction under an oil-immersed transformer, and allow for local electrical authority approval in the design programme.
- In the acceptance documents, separate routine tests (every unit) from type and special tests, and state in the order which tests are required.
Who should read it
Electrical engineers selecting and specifying medium-voltage transformers, teams designing transformer rooms, and operators planning transformer maintenance.
Document contents
- 1. Introduction
- 2. Transformers Characteristics
- 2.1. General Characteristics: standards, application, installation, insulation liquid, cooling method
- 2.2. Electrical Design: power rating, voltage levels, temperature, altitude, short-circuit impedance, vector group, losses, frequencies, tolerances, harmonic components
- 2.3. Mechanical Features: tank, cover, magnetic circuit, winding coils, cooling liquid, painting
- 2.4. Accessories for Distribution Transformers: bushings, cable boxes, other accessories
- 2.5. Accessories for Power Transformers
- 3. Testing, Operation, Installation and Maintenance
- 3.1. Transformer Tests: routine, type and special tests
- 3.2. Distribution Transformer Operation: set up, overloading, inrush current, transformer protection
- 3.3. Distribution Transformer Installation and Maintenance: types of installation, dimensions of installation area, maintenance
Publication details
- Authors
- Matelec Group
- Publisher
- Matelec Group
- Year
- 2014
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Matelec Group (2014). Distribution and Power Transformers. Matelec Group. https://matelec.com/wp-content/uploads/2025/04/2014-Brochure-Catalogue-MATELEC-Transfos.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.