Ultracapacitor Applications for Uninterruptible Power Supplies (UPS) (Maxwell)

Original title Ultracapacitor Applications for Uninterruptible Power Supplies (UPS)

Maxwell Technologies · Jason Lee

A Maxwell white paper argues that ultracapacitors give 8-14 years of life for 15-30 second bridge power, against 1-5 years for lead-acid, and cut total cost by 18% in a 200 kW, 15-year example.

On this page

Overview

The white paper by Jason Lee of Maxwell Technologies proposes ultracapacitors as energy storage for large-scale UPS. It concentrates on the 15-30 seconds of bridge power needed to transition to a permanent backup source such as a generator or fuel cell; typical system sizes start at 20 kW and scale modularly to MW level. Since the manufacturer describes its own product, the comparisons are the manufacturer's view.

The technology comparison states lead-acid life of 1-5 years, flywheel 20 years and ultracapacitor 8-14 years (elsewhere the text says 8-15). Ultracapacitors offer up to 20 times the power of a battery, maintenance-free operation, no hazardous materials and predictable wear-out, while batteries hold up to 20 times the energy. The paper claims over 3000 times the charge/discharge cycles and 3 to 14 times the calendar life of lead-acid. Battery monitoring can cost up to $20,000 per system, whereas a capacitor needs only simple voltage and current measurement.

The TCO example is 200 kW, 15 years and 30 second discharge: batteries cost $17,000 initially (including $10,000 for monitoring), $4,450 per year and $83,785 in total; the flywheel $48,000, $2,140 per year and $80,150; ultracapacitors $60,000, $550 per year and $68,290. Savings are $15,495 (18%). With annual battery replacement, savings reach about 75% over 15 years; the range is 30-75% depending on replacement frequency.

As a technical note, a battery inverter stops at about 80% of float voltage, so in an existing inverter only 36% of the energy can be used. If operating voltage is lowered to 50% of float (280 V), 75% is used, and at 30% (170 V), 90%. A module supports 10 kW / 56 V for 15 seconds, weighs under 40 lb and can be series-connected up to 750 V.

Key points

  1. Bridge time 15-30 seconds; typical system size 20 kW and above, scalable to MW.
  2. Lead-acid life 1-5 years; flywheel 20 years; ultracapacitor 8-14 years (8-15 elsewhere in the text).
  3. Ultracapacitor claims over 3000 times the cycles and 3-14 times the calendar life of a battery; power density 20 times a battery, energy 20 times lower.
  4. 200 kW, 15-year, 30-second example total cost: battery $83,785, flywheel $80,150, ultracapacitor $68,290 (saving $15,495, 18%).
  5. Savings of 30-75% depending on battery replacement frequency; about 75% with annual replacement.
  6. A battery inverter stops at ~80% of float voltage: drop-in replacement uses 36% of the energy; 75% at 50% and 90% at 30%.
  7. Module 10 kW / 56 V (15 seconds), under 40 lb, series connection up to 750 V.

Using it in design

  • Where bridge time is limited to 15-30 seconds and the generator starts quickly, compare ultracapacitor storage against battery and flywheel at TCO level.
  • In a new UPS design, consider lowering the inverter minimum voltage to 50% of float; in an existing inverter expect only 36% energy use.
  • If minutes of autonomy are required this source does not apply; the paper covers only second-scale bridging.
  • Add battery monitoring cost and maintenance as separate TCO items and recompute the paper's example with your own prices.

Who should read it

Designers selecting UPS energy storage and investment teams carrying out TCO analysis.

Document contents

  1. Introduction: energy storage for UPS
  2. Ultracapacitor background
  3. Technology comparison (Table 1)
  4. Total cost of ownership (Table 2)
  5. Additional capabilities and benefits
  6. Summary

Publication details

Authors
Jason Lee
Publisher
Maxwell Technologies
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Jason Lee Ultracapacitor Applications for Uninterruptible Power Supplies (UPS). Maxwell Technologies. https://maxwell.com/wp-content/uploads/2021/08/whitepaper_application_for_ups.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.