Thermal Impact Analysis of Circulating Current in High Power Modular Online Uninterruptible Power Supplies Application
Energies (MDPI AG) · Chi Zhang, Josep Guerrero et al.
The paper studies modular online (double-conversion) UPS systems in which several DC/AC inverter modules share a common DC bus and AC critical bus, validates module rotation against IEC 62040-3 limits, and uses PLECS to show how zero-sequence circulating current unbalances semiconductor losses and junction temperatures.
CC BY 4.0: share with attribution
On this page
Overview
The study asks whether paralleling modules in a modular UPS has thermal and control side effects beyond simple N+1 redundancy arithmetic. On a laboratory set-up with three inverter modules, plug-and-play module rotation (normal and emergency cycles) was demonstrated and the output voltage transients checked against IEC 62040-3 limits. The module model is 200 kW nominal, 5 kHz switching, 700 V DC side, 230 V bus voltage, 290 A bus current, a three-phase H-bridge with LC filter (1.8 mH, 27 µF).
Transient time requirements are tabulated for linear and nonlinear loads: 14% voltage variation allowed for 20-40 ms, 12% for 40-60 ms, 11% for 60-100 ms and 10% for 100-1000 ms. The authors recommend keeping overshoot or sag on module switching within 10% of nominal critical-bus voltage. During module rotation the measured overshoot was 8.77% or 8.92%, with a transient time of about three and a half utility periods (70 ms).
In the thermal analysis, unsynchronised PWM and module-to-module differences in filters and control parameters cause zero-sequence circulating current that unbalances losses and junction temperatures between semiconductor devices. Citing prior work, the authors note DC/AC modules are normally designed to work at 50% to 75% load, so the thermal study spans 50-100% load. A 30% filter-inductor mismatch between modules plus unsynchronised PWM produced an obvious circulating current with a DC component and unequal device losses and temperatures.
To suppress the circulating current, synchronisation and zero-vector time regulation were applied, but this raised the temperature and losses of T2 (T2 higher than T1, and D1 higher than D2). Limits: thermal results rest on PLECS simulation, and experimental validation is limited to the module-rotation transient.
Key points
- Modelled module rating: 200 kW nominal, 5 kHz switching, 700 V DC side, 230 V bus voltage, 290 A bus current, three-phase H-bridge with LC filter (1.8 mH, 27 µF).
- Transient time requirements for linear and nonlinear loads: 14% voltage variation allowed for 20-40 ms, 12% for 40-60 ms, 11% for 60-100 ms and 10% for 100-1000 ms.
- The authors recommend keeping overshoot or sag on module switching within 10% of nominal critical-bus voltage.
- During module rotation the measured overshoot was 8.77% or 8.92%, with a transient time of about three and a half utility periods (70 ms).
- Citing prior work, DC/AC modules are normally designed to work at 50% to 75% load, so the thermal study spans 50-100% load.
- A 30% filter-inductor mismatch between modules plus unsynchronised PWM produced an obvious circulating current with a DC component and unequal device losses and temperatures.
Using it in design
- For paralleled modules in a modular UPS, do not look only at the N+1 redundancy count; add to the design check that module-to-module filter and control parameter differences cause circulating current and thermal imbalance.
- Verify output voltage overshoot at module commissioning and rotation against IEC 62040-3 transient limits (for example 14% for 20-40 ms) and a 10% target.
- Before choosing a circulating-current suppression method, check the thermal balance of modules in the typical 50%-75% load range and the way PWM synchronisation redistributes losses (higher T2 and D1 temperatures).
Who should read it
Power-electronics and UPS engineers working on modular UPS paralleling, control and thermal design.
Document contents
- 1. Introduction
- 2. System Control Mechanism (2.1 Single Module Control, 2.2 Power Balance among Modules, 2.3 Voltage Amplitude and Phase Synchronized, 2.4 Cycle and Plug'n'Play Control)
- 3. Experimental Results (3.1 Modules, 3.2 Cycle Control Transient Performance)
- 4. Thermal Analysis Results (4.1 Single DC/AC Module, 4.2 DC/AC Modules with Zero Sequence Circulating Current, 4.3 DC/AC Modules with Suppressed Zero Sequence Circulating Current)
- 5. Conclusions
Related standards
- IEC 62040-3
Read the document
modular-ups-circulating-current-thermal-2017.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Chi Zhang; Josep Guerrero; Juan Vasquez
- Publisher
- Energies (MDPI AG)
- Year
- 2017
- Volume
- 10
- Issue
- 1
- Pages
- 50
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.11 states the article is distributed under the Creative Commons Attribution (CC-BY) license (http://creativecommons.org/licenses/by/4.0/).
Citation
Chi Zhang; Josep Guerrero; Juan Vasquez (2017). Thermal Impact Analysis of Circulating Current in High Power Modular Online Uninterruptible Power Supplies Application. Energies (MDPI AG). 10(1), 50. https://doi.org/10.3390/en10010050
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.