Variable Water Flow and Understanding Refrigerant-Water Heat Exchangers

Original title Variable Water Flow and Understanding Refrigerant–Water Heat Exchangers

Munters · Robert Young

Munters' 2026 technical application article compares DX, flooded and brazed-plate evaporators and stresses that variable flow must respect evaporator minimum flow and velocity limits.

On this page

Overview

The article, published by Munters' data-centre division, compares refrigerant-water heat exchanger types (DX, flooded and brazed-plate evaporators). It then examines how variable water flow interacts with turbulence, pump head and chiller staging.

Its main message is that variable-flow control must respect the evaporator's minimum flow and velocity requirements, otherwise heat transfer is lost and operation becomes unstable. These requirements are manufacturer-specific. The article recommends assessing pressure drop and chiller sequencing together with pump energy savings.

Key points

  1. DX, flooded and brazed-plate evaporator types are compared.
  2. Variable-flow control must respect evaporator minimum flow and velocity.
  3. Below minimum flow, heat transfer is lost and operation becomes unstable.
  4. Minimum flow requirements are manufacturer-specific.
  5. Pressure drop and chiller sequencing should be assessed together with pump energy savings.

Using it in design

  • In variable-flow chilled water pumping, write the manufacturer's evaporator minimum flow and velocity into the control logic as a lower limit.
  • When calculating pump energy savings, model evaporator pressure drop and chiller staging sequence together.
  • Confirm flow-change tolerance by evaporator type (DX, flooded, brazed-plate) with the manufacturer.
  • Make the decision to reduce running chillers at low load together with the minimum flow limit.

Who should read it

Mechanical and controls engineers designing chilled water systems and pump control.

Publication details

Authors
Robert Young
Publisher
Munters
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Publisher article opened with TinyFish; byline Robert Young and July 23, 2026 are visible. Publisher legal notice also opened at https://datacenter.munters.com/legal-notice/; neither grants open redistribution rights. Technical article, not a separately issued white paper.

Citation

Robert Young (2026). Variable Water Flow and Understanding Refrigerant–Water Heat Exchangers. Munters. https://datacenter.munters.com/resources/insights/variable-water-flow-and-understanding-refrigerant-water-heat-exchangers/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.