System Efficiency Analysis in Pump Applications (10th Pump, Valve, Compressor Congress, 2020)
Original title Pompa Uygulamalarında Sistem Verimliliği Analizi: 10. Pompa, Vana, Kompresör Kongresi
POMSAD, Türk Pompa ve Vana Sanayicileri Derneği · Bahri Sonel, Orhan Odabaşı
A KSB engineers' paper at the POMSAD 2020 congress: the S.E.S. measurement device examines 4 duty plus 2 standby condensate pumps; cutting 4 pumps to 2 lowers energy 24 percent with a 0.61 year payback.
On this page
Overview
The paper was presented at the 10th Pump, Valve, Compressor Congress in Ankara on 13-14 February 2020 by Bahri Sonel and Orhan Odabaşı of KSB Pompa Armatür (pages 167-168 of the proceedings). It describes the S.E.S. (System Efficiency Service) device designed to analyse system efficiency in pump applications and a field study at an industrial plant. Besides efficiency, the device helps detect possible pump faults in advance and supports predictive maintenance.
The setup measures and logs one data point per second. Precise pressure sensors cover -1 to 9 bar on suction and 0 to 100 bar on discharge, and magnetic vibration sensors cover 0-25 mm/s; vibration is taken on three axes at the bearing bracket and on the motor horizontal axis. A power analyser records motor power profiles, synchronised with hydraulic data. Each pump was measured for 6-7 hours.
The system studied is 4 duty and 2 standby volute-casing centrifugal condensate pumps running on demineralised water at 90 °C and 0.965 kg/dm³. The operator reported insufficient flow and vibration above standard and unstable. Measurements showed suction and discharge pressure fluctuations and related vibration increases; the pumps ran far from their best efficiency point, causing efficiency loss and shortened pump life.
As a result, 2 new pumps meeting the required flow and pressure were proposed in place of the existing 4, and the operator implemented the decision. The old installation uses about 866,457 kWh/year and the new about 658,400 kWh/year; annual gain is about 208,057 kWh (about 24 percent), annual saving about 14,563 €, initial investment about 8,872 € and payback about 0.61 years (7.3 months). The work concerns condensate pumps, not a data centre; the method adapts to chilled water pumps.
Key points
- The S.E.S. device logs one data point per second with -1 to 9 bar suction and 0 to 100 bar discharge pressure sensors and 0-25 mm/s vibration sensors.
- Each pump was measured for 6-7 hours, with power analyser data synchronised with hydraulic data.
- The system is 4 duty and 2 standby volute-casing centrifugal condensate pumps; fluid is demineralised water at 90 °C, 0.965 kg/dm³.
- Pumps ran far from their best efficiency point; pressure fluctuations and increased vibration were detected.
- 4 pumps were replaced by 2 new pumps; energy use fell from 866,457 to 658,400 kWh/year.
- Annual gain is about 208,057 kWh (about 24 percent) and about 14,563 €.
- Initial investment is about 8,872 € and payback about 0.61 years (7.3 months).
Using it in design
- On chilled water and condenser pumps, compare the actual duty point from pressure, power and vibration measurement with the pump curve.
- Where several pumps run in parallel, check whether fewer suitable pumps meet the required flow and pressure.
- Set up a measurement programme in commissioning and operation that tracks deviation from the best efficiency point; use rising vibration as early warning.
- Keep standby pump count (N+1) while sizing the duty pump count to the load profile.
- Present initial investment and payback together in an energy saving report.
Who should read it
Mechanical engineers operating and commissioning pump systems, energy efficiency consultants and maintenance teams.
Document contents
- Abstract
- Introduction
- Introduction of the test setup
- Measurement results (suction-discharge graph, operating analysis)
- Conclusion and energy saving calculation
Publication details
- Authors
- Bahri Sonel; Orhan Odabaşı
- Publisher
- POMSAD, Türk Pompa ve Vana Sanayicileri Derneği
- Year
- 2020
- Document number
- 10. Pompa, Vana, Kompresör Kongresi 2020, pp.167–168
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Bahri Sonel; Orhan Odabaşı (2020). Pompa Uygulamalarında Sistem Verimliliği Analizi: 10. Pompa, Vana, Kompresör Kongresi. POMSAD, Türk Pompa ve Vana Sanayicileri Derneği. 10. Pompa, Vana, Kompresör Kongresi 2020, pp.167–168. https://pomsad.org.tr/wp-content/uploads/2026/06/10.-KONGRE-BILDIRILER-KITABI.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
