Powertek GIGA Board v5.0 User's Guide (Intelligent PDU)

Original title Powertek GIGA Board User’s Guide Version 5.0

Powertek Industries

Powertek GIGA Board v5.0 user guide for an intelligent PDU monitoring and switching up to 42 outlets, daisy-chaining up to 16 PDUs, 8 EMD31 sensors, SNMP v1/2/3, SSL v3 and SSH v2, with a hot-swappable controller.

On this page

Overview

The guide describes the hardware and web interface of the GIGA controller board in Powertek's intelligent PDU. The PDU monitors input and circuit-breaker consumption, emails a daily history report automatically and lets network equipment be power-managed remotely through a console or Ethernet. Up to 8 EMD31 environmental monitoring devices (temperature and humidity) can be cascaded on the console port, with two alarms that trigger when a sensor reads unusual values. Models are available for 220-250 V, 380-415 V, 120-208 V and 208 V.

Features include hourly and daily accumulated power calculation, detailed data logging, daisy-chaining of up to 16 power strips, sequential outlet power-up, event or schedule based switching, SNMP trap and email notification, up to 42 outlets controllable in several ways, and a per-outlet over-current watchdog with warning and alert thresholds. Management is by web browser, NMS and SNMP v1/2/3; Secure Socket Layer v3 and Secure Shell v2 are supported, with administrator and multi-user password protection and address-specific IP masks.

The hardware chapters cover the inlet, breaker, OLED display and mounting options, earthing, rack mounting, the Power Share adaptor and cable, the address DIP-switch and LAN/WAN connection. The web chapters cover the system overview, alarm list, inlet configuration, outlet control, grouping, schedule, environment monitoring and the TCP/IP, LDAP, Radius, SNMP and Syslog settings. The guide also describes the residual current monitoring (RCM) and surge protection monitoring (SPD) options and the hot-swappable IEX GIGA controller; among the safety notes, maximum ambient temperature for rack mounting is 60 °C.

Key points

  1. One PDU controls and monitors up to 42 outlets; up to 16 power strips can be daisy-chained.
  2. Up to 8 EMD31 environmental monitoring devices (temperature, humidity) with two alarm outputs.
  3. Management: web browser, NMS, SNMP v1/2/3; SSL v3 and SSH v2; LDAP, Radius and Syslog settings.
  4. Hourly and daily accumulated energy logging; a daily history report is emailed.
  5. Sequential outlet start-up, scheduling and per-outlet over-current thresholds (warning and alert).
  6. Optional residual current monitoring (RCM) and surge protection monitoring (SPD).
  7. Hot-swappable GIGA controller: replaced without powering the PDU off.
  8. Models for 220-250 V, 380-415 V, 120-208 V and 208 V; maximum rack ambient temperature 60 °C.

Using it in design

  • When selecting rack PDUs, write sequential start-up and per-outlet over-current thresholds into the operating procedure (inrush on power restore).
  • Use daisy-chaining (16 PDUs) and Power Share to reduce network port count and IP address plan size.
  • Place EMD31 sensors at the cold aisle inlet and connect temperature and humidity alarms to DCIM.
  • Enable SSL, SSH, LDAP and Radius per security policy and restrict the accessible IP masks.
  • Add the RCM and SPD monitoring options to the specification where residual current and surge protection monitoring are required.

Who should read it

Data centre operators installing rack PDUs and engineers responsible for monitoring and network configuration.

Document contents

  1. Preface: About this Manual, Safety Instructions, Safety Notices
  2. Introduction: Features, Package Contents, Hardware Components
  3. Getting Started: earth ground, rack mounting, hot-swap controller
  4. Making Connections: input power, output devices, EMD31, DIP-switch addressing, daisy chain, Power Share, LAN/WAN
  5. LCM operation, RCM and SPD monitoring
  6. Using the Web Interface: summary overview, outlet control, grouping, schedule, environment monitoring
  7. Settings: TCP/IP, network access protection, LDAP, Radius, SNMP, Syslog

Publication details

Authors
Powertek Industries
Publisher
Powertek Industries
Year
Year not stated
Document number
UG004, Version 5.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Powertek Industries Powertek GIGA Board User’s Guide Version 5.0. Powertek Industries. UG004, Version 5.0. https://www.powertekpdus.com/wp-content/uploads/2023/09/UG004-GIGA-Board-v5.0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.