EAG 100 Series 6-10 kVA single-phase UPS technical specifications

Original title EAG 100 Serisi 6–10 kVA tek faz KGK teknik özellikleri

EAG / Enerji Ankara

EAG 100 series 1/1-phase online UPS: 6 kVA/5.4 kW and 10 kVA/9 kW, output PF 0.9, 94% on-line and 98% eco-mode efficiency, 248 x 500 x 616 mm, 59 and 63 kg.

On this page

Overview

The document is the technical table for EAG-branded 6 and 10 kVA single-phase, high-frequency true double-conversion online UPSs. Ratings are 6000 VA/5400 W and 10000 VA/9000 W with an output power factor of 0.9. DSP technology, input power factor correction, a wide 110-300 V input range, cold start from battery, eco mode and advanced battery management are among the main features.

Input is 208/220/230/240 V, 50/60 Hz. The voltage window is 185-275 V +/-5 V at 100% load and 120-185 V +/-5 V at 50% load; frequency range is 40-70 Hz and input power factor 0.99 or higher. Output voltage is selectable on the LCD at 208/220/230/240 V, regulation +/-1%, full sine waveform, crest factor 3:1, THD at most 2% on linear and 4% on non-linear load, and mains-to-battery transfer 0 ms.

Overload capability is 1 minute at 105-125%, 30 seconds at 125-150% and 0.5 seconds at 150%. Efficiency is 94% or more in on-line mode and 98% or more in eco mode. The internal battery is 15 units for 6 kVA and 16 units for 10 kVA of 7-9 Ah; standard charge current is 1.2 A, 4 A on the long-run (L) model, with 90% capacity in 7 hours. Options include maintenance bypass, EPO, SNMP/Modbus/AS400 card and up to 3 units in parallel.

Physical data: 248 x 500 x 616 mm (W x D x H), net weight 59 and 63 kg, gross 65 and 68 kg; IP20, noise below 50 dB at 1 m, operation 0-40 C, altitude 0-3000 m (1% power loss per 100 m). In frequency-converter mode power drops by 60%. Standards are CE and IEC/EN 62040, EMI class C3. Warranty is 2 years with 10 years of spare-part availability.

Key points

  1. Power: 6 kVA/5.4 kW and 10 kVA/9 kW; output power factor 0.9.
  2. Input voltage window 185-275 V at 100% load, 120-185 V at 50% load; input power factor 0.99 or higher.
  3. Output selectable 208/220/230/240 V; +/-1% regulation, THD at most 2% (linear) and 4% (non-linear).
  4. Efficiency: 94% or more on-line; 98% or more in eco mode.
  5. Overload: 1 min at 105-125%, 30 s at 125-150%, 0.5 s at 150%.
  6. Internal battery 15 or 16 units of 7-9 Ah; charge current 1.2 A (4 A on L model); 90% in 7 h.
  7. 248 x 500 x 616 mm; net 59 and 63 kg; IP20; below 50 dB.
  8. Altitude to 3000 m with 1% loss per 100 m; up to 3 units in parallel (optional).
  9. Frequency-converter mode reduces power by 60%.

Using it in design

  • Check the load in kW at 0.9 power factor: 5.4 kW for 6 kVA and 9 kW for 10 kVA.
  • If standard internal battery autonomy is limited, consider the long-run (L) model and an external battery unit.
  • If eco mode will be used, compare the protection level in that mode with load sensitivity.
  • Carry weight and size (59-63 kg, 248 x 500 x 616 mm) into the layout; add altitude derating above 3000 m.
  • Write the SNMP/Modbus card and EPO options into the specification for monitoring.

Who should read it

Electrical designers selecting small single-phase UPSs and network or server-room engineers.

Document contents

  1. General features
  2. Rear panel
  3. Technical specifications: input, output, efficiency, battery
  4. Interface and options
  5. Environment and standards
  6. Accessories and dimensions

Publication details

Authors
EAG / Enerji Ankara
Publisher
EAG / Enerji Ankara
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EAG / Enerji Ankara EAG 100 Serisi 6–10 kVA tek faz KGK teknik özellikleri. EAG / Enerji Ankara. https://enerjiankara.com/uploads/docs/5beeb8a697ab9f40-1784184170.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.