2023 CATL ES Solutions: UPS backup battery rack configurations
CATL
The page of CATL's energy storage brochure that presents its lithium iron phosphate (LFP) UPS battery rack in 8-, 10- and 12-module configurations, with a separate telecom module alongside.
On this page
Overview
The brochure is a general CATL energy storage presentation dated February 2023: company profile, milestones, production and R&D locations, then solutions for generation, grid and commercial applications. The section relevant to data-centre designers is the page titled UPS Backup Battery Solution; beside it sits the 48100 telecom module, a separate product that must not be substituted for the UPS rack.
The UPS rack uses LFP cells. Safety features listed are dual redundancy for BMS control and protection (contactor shunt trip plus moulded case breaker), dual redundancy for short-circuit protection (fuse plus moulded case breaker), redundant auxiliary supply and black start after a grid outage. A faulty rack exits on its own, preserving system availability. Temperature rise at the highest discharge rate is about 20 C, with natural cooling sufficient.
Flexibility is stressed: suitability for three-wire and two-wire UPS systems, a 320-691 V range covering high and low voltage platforms, and 32.768-49.152 kWh per rack. The rack can ship complete or as body and spare parts separately. The table gives cell, module and three rack sizes; rack values must be read together with the module count.
Key points
- Cell: 3.2 V, 20 Ah, 0.064 kWh, 0.53 kg; voltage range 2.5-3.6 V.
- Module (4P16S): 51.2 V, 80 Ah, 4.096 kWh, 50 kg, 480 x 750 x 130 mm (W x D x H); voltage range 40-57.6 V.
- 8 modules (4P128S): 410 V, 32.768 kWh, 600 kg, voltage range 320-461 V.
- 10 modules (4P160S): 512 V, 40.960 kWh, 700 kg, voltage range 400-576 V.
- 12 modules (4P192S): 614 V, 49.152 kWh, 800 kg, voltage range 480-691 V.
- Rack dimensions are given as 600 x 900 x 2000 mm (W x D x H), the same for all three configurations; rated capacity is 80 Ah.
- Dual redundancy in BMS and short-circuit protection, redundant auxiliary supply, black start and single-rack exit are stated.
- The 48100 telecom module is a separate product: LFP, 100 Ah, 51.2 V, 438 x 130 x 450 mm, up to 16 packs in parallel.
Using it in design
- When choosing the UPS DC bus voltage window, match the rack voltage range (320-461, 400-576, 480-691 V) to the UPS battery input.
- In load planning, add 600, 700 or 800 kg per rack and the 600 x 900 x 2000 mm footprint to floor loading and layout.
- Before converting energy (32.768 / 40.960 / 49.152 kWh) into runtime, confirm the selected UPS discharge power and application-specific sizing.
- Reflect the single-rack exit capability in the redundancy scheme (number of racks for N+1).
- Do not use the 48100 telecom module values in place of the UPS rack.
Who should read it
Electrical designers and procurement engineers selecting or comparing lithium-ion UPS batteries.
Document contents
- About CATL
- Company milestones
- Global locations
- UPS backup battery solution
- Telecom backup battery solution
- Energy storage applications
Publication details
- Authors
- CATL
- Publisher
- CATL
- Year
- 2023
- Document number
- ES Solutions
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CATL (2023). 2023 CATL ES Solutions: UPS backup battery rack configurations. CATL. ES Solutions. https://www.catl.com/es/uploads/1/file/public/202304/20230423105614_54trlyqda9.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
