HOPPECKE grid | Xtreme VR PURE Data-Center Technical Data

Original title HOPPECKE grid Xtreme VR PURE data-center technical data

HOPPECKE

The HOPPECKE grid | Xtreme VR PURE is a 12 V VRLA block series for data centres with 99.99% pure lead and 15-year design life; it gives 548.9-1266.4 W per cell at 5 minutes (1.67 V per cell) and conforms to IEC 60896-21/22.

On this page

Overview

The document is the HOPPECKE data sheet for the grid | Xtreme VR PURE series for data-centre use. The series uses 99.99% pure lead to target corrosion resistance and service life under high current and high ambient temperature. Design life is 15 years; it is classified "Very Long Life" under the Eurobat Guide 2015 and designed to comply with IEC 60896-21/22.

Features include a plastic-overmolded dual-pole design (access for impedance measurement), top (TOP) and front (FT) terminal variants for the 12 V blocks, the grid | XtremeStack stacking solution (seismic loads up to UBC Zone 1), optional safeguard-tec (dimensional stability on top-terminal types) and ESS technology (resilience to thermal runaway, charge acceptance and even voltage behaviour). Recommended float voltage is 2.3 V per cell at 20 °C and 2.288 V per cell at 25 °C, operating range -40 to +55 °C, storage time up to 2 years, and no water refilling is needed.

The type table covers 12-80 to 12-170 (top terminal) and 12-100 FT to 12-200 FT (front terminal). For example, 12-80: 641.5 W (5 min), 465.9 W (10 min), 363.5 W (15 min), 25.8 kg; 12-170: 1266.4 W (5 min), 743.3 W (15 min), 51.4 kg; 12-200 FT: 1038.9 W (5 min), 61.2 kg. Maximum discharge current is 1100 A for top-terminal and 1000 A for front-terminal models; short-circuit current runs from 1439 A (12-80) to 3896 A (12-170). Terminal is an M8 insert with 15 Nm torque.

Key points

  1. 99.99% pure lead grids; 15-year design life; Eurobat "Very Long Life"; IEC 60896-21/22 compliant design.
  2. 12 V blocks: 12-80, 12-110, 12-130, 12-150, 12-170 (top terminal); 12-100 FT 19", 12-100 FT 23", 12-150 FT, 12-170 FT, 12-190 FT, 12-200 FT (front terminal).
  3. Constant power (1.67 V per cell): 12-80 gives 641.5 / 465.9 / 363.5 W (5/10/15 min); 12-170 gives 1266.4 / 940.1 / 743.3 W.
  4. Weight from 25.8 kg (12-80) to 61.2 kg (12-200 FT).
  5. Maximum discharge current: 1100 A (top terminal), 1000 A (front terminal); short-circuit current 1439 A (12-80) to 3896 A (12-170).
  6. Float voltage 2.3 V per cell (20 °C), 2.288 V per cell (25 °C); operating -40 to +55 °C.
  7. M8 insert terminal, 15 Nm; XtremeStack stacking suited to seismic loads up to UBC Zone 1.
  8. UL94 V-0 halogen-free ABS-PC; non-spillable and approved as non-hazardous cargo (ADR/IMDG/IATA).

Using it in design

  • For data-centre UPS autonomy, compute the number of blocks from the 5, 10 and 15 minute watts-per-cell values in the table.
  • Compare front-terminal (FT) types for 19" or 23" rack layout and access against top-terminal types with XtremeStack stacking.
  • Use short-circuit current (1439-3896 A) and maximum discharge current in DC protective device breaking capacity and selectivity.
  • Set the charger float to 2.288 V per cell at 25 °C and include the impedance-measurement points in the maintenance plan.

Who should read it

Electrical engineers designing data-centre UPS battery banks.

Document contents

  1. Product features
  2. Construction, installation and operation, standards
  3. Type overview: capacity, dimensions, weights
  4. Maximum discharge and short-circuit current
  5. Constant power discharge ratings

Publication details

Authors
HOPPECKE
Publisher
HOPPECKE
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HOPPECKE HOPPECKE grid Xtreme VR PURE data-center technical data. HOPPECKE. https://www.hoppecke.com/fileadmin/Redakteur/Hoppecke-Main/Products-Import/grid_xtreme_vr_data_sheet_data_center_us.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.