HOPPECKE grid | Xtreme VR PURE Data-Center Technical Data
Original title HOPPECKE grid Xtreme VR PURE data-center technical data
HOPPECKE
The HOPPECKE grid | Xtreme VR PURE is a 12 V VRLA block series for data centres with 99.99% pure lead and 15-year design life; it gives 548.9-1266.4 W per cell at 5 minutes (1.67 V per cell) and conforms to IEC 60896-21/22.
On this page
Overview
The document is the HOPPECKE data sheet for the grid | Xtreme VR PURE series for data-centre use. The series uses 99.99% pure lead to target corrosion resistance and service life under high current and high ambient temperature. Design life is 15 years; it is classified "Very Long Life" under the Eurobat Guide 2015 and designed to comply with IEC 60896-21/22.
Features include a plastic-overmolded dual-pole design (access for impedance measurement), top (TOP) and front (FT) terminal variants for the 12 V blocks, the grid | XtremeStack stacking solution (seismic loads up to UBC Zone 1), optional safeguard-tec (dimensional stability on top-terminal types) and ESS technology (resilience to thermal runaway, charge acceptance and even voltage behaviour). Recommended float voltage is 2.3 V per cell at 20 °C and 2.288 V per cell at 25 °C, operating range -40 to +55 °C, storage time up to 2 years, and no water refilling is needed.
The type table covers 12-80 to 12-170 (top terminal) and 12-100 FT to 12-200 FT (front terminal). For example, 12-80: 641.5 W (5 min), 465.9 W (10 min), 363.5 W (15 min), 25.8 kg; 12-170: 1266.4 W (5 min), 743.3 W (15 min), 51.4 kg; 12-200 FT: 1038.9 W (5 min), 61.2 kg. Maximum discharge current is 1100 A for top-terminal and 1000 A for front-terminal models; short-circuit current runs from 1439 A (12-80) to 3896 A (12-170). Terminal is an M8 insert with 15 Nm torque.
Key points
- 99.99% pure lead grids; 15-year design life; Eurobat "Very Long Life"; IEC 60896-21/22 compliant design.
- 12 V blocks: 12-80, 12-110, 12-130, 12-150, 12-170 (top terminal); 12-100 FT 19", 12-100 FT 23", 12-150 FT, 12-170 FT, 12-190 FT, 12-200 FT (front terminal).
- Constant power (1.67 V per cell): 12-80 gives 641.5 / 465.9 / 363.5 W (5/10/15 min); 12-170 gives 1266.4 / 940.1 / 743.3 W.
- Weight from 25.8 kg (12-80) to 61.2 kg (12-200 FT).
- Maximum discharge current: 1100 A (top terminal), 1000 A (front terminal); short-circuit current 1439 A (12-80) to 3896 A (12-170).
- Float voltage 2.3 V per cell (20 °C), 2.288 V per cell (25 °C); operating -40 to +55 °C.
- M8 insert terminal, 15 Nm; XtremeStack stacking suited to seismic loads up to UBC Zone 1.
- UL94 V-0 halogen-free ABS-PC; non-spillable and approved as non-hazardous cargo (ADR/IMDG/IATA).
Using it in design
- For data-centre UPS autonomy, compute the number of blocks from the 5, 10 and 15 minute watts-per-cell values in the table.
- Compare front-terminal (FT) types for 19" or 23" rack layout and access against top-terminal types with XtremeStack stacking.
- Use short-circuit current (1439-3896 A) and maximum discharge current in DC protective device breaking capacity and selectivity.
- Set the charger float to 2.288 V per cell at 25 °C and include the impedance-measurement points in the maintenance plan.
Who should read it
Electrical engineers designing data-centre UPS battery banks.
Document contents
- Product features
- Construction, installation and operation, standards
- Type overview: capacity, dimensions, weights
- Maximum discharge and short-circuit current
- Constant power discharge ratings
Publication details
- Authors
- HOPPECKE
- Publisher
- HOPPECKE
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HOPPECKE HOPPECKE grid Xtreme VR PURE data-center technical data. HOPPECKE. https://www.hoppecke.com/fileadmin/Redakteur/Hoppecke-Main/Products-Import/grid_xtreme_vr_data_sheet_data_center_us.pdf