Leoch LHR and LHRF High-Rate VRLA AGM Parameter Tables
Original title Leoch LHR and LHRF high-rate VRLA AGM parameter tables
Leoch
Leoch's LHR and LHRF page lists high-rate VRLA AGM 2 V cells and 6 V and 12 V monoblocs for data centres (IDC) and UPS, with W/15 min and 10-hour ratings.
On this page
Overview
The page introduces Leoch's LHR and LHRF high-rate lead-acid battery series. Applications named are bank and finance markets, emergency power systems, industrial process control, facility control and data centres (IDC). Special grid and plate manufacturing technology and an automatic production line raise life and uniformity; a three-dimensional structure and fine mesh grid provide more surface area for high power output.
The parameter list is split into three tables: 6 V and 12 V monoblocs, 2 V cells, and the front-terminal (LHRF) series. Each row gives rated voltage, the 15-minute watt rating at 1.67 V per cell (W15), the 10-hour capacity at 1.80 V per cell, length, width, height, total height, gross weight and terminal type. Height and total height are separate columns.
The 6 V and 12 V table spans LHR619W(A) (6 V, 19 W/cell, 4.68 Ah, 0.77 kg) to LHR121000W (12 V, 1000 W/cell, 250 Ah, 79.5 kg). The 2 V table runs from LHR500W (500 W, 150 Ah, 8.4 kg) to LHR2900W (2900 W, 900 Ah, 57.3 kg). The front-terminal series runs from LHR12390FT (390 W, 95 Ah, 34 kg) to LHR121000FT (1000 W, 250 Ah, 82.2 kg). Terminal types are T1/T2, T6, T11, T7, T18 and T13-C.
The document is at component level: cell, monobloc or front-terminal block values do not define a battery-connected cabinet. Horizontal and vertical installation is possible; the compact structure allows installation in the same room as equipment. The leak-free, acid-fog-free sealed design prevents environmental pollution. The page also links to Leoch's data-centre and UPS battery solution and its AI data-centre energy solution.
Key points
- LHR and LHRF high-rate VRLA AGM series; applications: IDC, bank and finance, emergency power, industrial process control.
- Three tables: 6 V and 12 V monobloc, 2 V cell, 12 V front-terminal (LHRF).
- Power and capacity ratings: W/15 min (1.67 V per cell) and 10-hour (1.80 V per cell).
- 12 V range: from LHR1217W(A) to LHR121000W; largest 12 V block 1000 W, 250 Ah, 79.5 kg.
- 2 V cells: from LHR500W (500 W, 150 Ah, 8.4 kg) to LHR2900W (2900 W, 900 Ah, 57.3 kg).
- Front-terminal 12 V: from LHR12390FT (390 W, 95 Ah, 34 kg) to LHR121000FT (1000 W, 250 Ah, 82.2 kg).
- Height and total height are separate columns; terminal types T1/T2, T6, T11, T7, T18, T13-C.
- Horizontal and vertical installation; compact structure can sit in the same room as equipment.
- Sealed, leak-free and acid-fog-free design; corrosion-resistant case.
Using it in design
- When sizing a battery bank with the W/15 min values, use the UPS end-of-discharge voltage per cell (1.67 V) and its load.
- Where front-access layout is needed, use the LHRF front-terminal series and account for its 508-560 mm length in rack layout.
- Calculate the difference between height and total height (for example 213 and 216 mm) separately for rack height and terminal clearance.
- Do not read component data as cabinet energy or load-time calculation; have the manufacturer run a project-based calculation.
- Write bus bars or cable connectors suited to the terminal type (T6, T11, T18 and so on) into the specification.
Who should read it
Electrical designers sizing data-centre and UPS battery banks, and engineers preparing battery rack layouts.
Document contents
- LHR and LHRF high-rate series introduction
- Key features
- Parameter list: 6 V and 12 V
- Parameter list: 2 V
- Parameter list: front-terminal (LHRF) series
- Data centre and UPS battery solution
Publication details
- Authors
- Leoch
- Publisher
- Leoch
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Leoch Leoch LHR and LHRF high-rate VRLA AGM parameter tables. Leoch. https://www.leoch.com/products/lead-acid/high-rate-lhr-lhrf-series
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.