Technical guideFree to read2023

Saft Flex'ion Gen2 Li-ion Battery System

Saft

A November 2023 brochure presenting Saft's Flex'ion Gen2 lithium-ion UPS battery cabinet for mission-critical applications: module, cabinet sizes, lifetime comparison, standards and technical data.

On this page

Overview

The brochure presents Flex'ion Gen2 as a super lithium iron phosphate (SLFP) system for data centres, oil and gas, utility and healthcare. Headline claims are up to 220 kW per cabinet, UL 9540A and UL 1973 safety certification, cobalt below 1 percent and operation at 35 C. The system scales to 4 MW, 838 kWh and 598 VDC and suits 2-wire or 3-wire (midpoint) UPS designs.

Lifetime is compared by ambient temperature: at 20 C Flex'ion lasts 24.5 years against 10 for VRLA; at 25 C 19.1 against 7.0; at 30 C 12.0 against 5.0; at 35 C 10 against 3.8. The higher operating temperature reduces HVAC need and consumption. The cabinet is IP20 and seismically tested and certified, with a 7-inch HMI, a battery-stop button and a main breaker in each string.

The Battery Management Module (BMM) handles safety functions at string level, lets the string discharge even if charging is interrupted, and communicates over Modbus, CanOpen and TCP-IP with the UPS or building management system. Black start is possible because the system is self-powered, and fast recharge after full discharge is stated.

Four cabinet types exist, and maximum module count and voltage depend on height. The technical table gives module (23MFe and 46PFe-G2) values, charge currents and short-circuit current. The brochure separates module ratings from cabinet envelope limits and requires project-specific sizing for load, backup time, temperature and voltage window.

Key points

  1. The 23MFe module is 23 V, 78 Ah, 1792 Wh; the 46PFe-G2 module is 46 V, 28 Ah, 1294 Wh.
  2. Both modules are 445 x 131 x 292 mm and 18.5 kg; short-circuit current is 3500 A (23MFe) and 5400 A (46PFe-G2).
  3. Maximum recharge current: 2C5Ah (23MFe) and 4C5Ah (46PFe-G2) with intelligent charging; 0.2C5Ah with conventional charging.
  4. Cabinet types: heights 1300/1850/2050/2310 mm, width 610 mm, depth 520 mm; weights 100/128/138/150 kg.
  5. Cabinet voltage and modules: 230 V and 5 modules, 414 V and 9, 506 V and 11, 598 V and 13.
  6. System limits: 4 MW, 838 kWh, 598 VDC; up to 220 kW per cabinet.
  7. Lifetime (Flex'ion / VRLA): 24.5 / 10 years at 20 C, 19.1 / 7.0 at 25 C, 12.0 / 5.0 at 30 C, 10 / 3.8 at 35 C.
  8. Standards include UL 1973, UL 9540A, UL 991, UL 1998, IEC 62619, IEC 62620, NFPA 855, UN 3480 and seismic IBC 2018, IEEE 693, Bellcore GR-63 zone 4.
  9. 5-year warranty, 6 times lighter than VRLA, cabinets can ship with modules installed.

Using it in design

  • Weigh operation up to 35 C against the HVAC budget for the battery room, and use the lifetime table for the chosen temperature.
  • Match cabinet voltage (230-598 V) to the UPS DC bus range and module count to the required energy.
  • Keep module ratings (for example 23 V / 78 Ah) separate from cabinet envelope limits; ask the manufacturer for sizing to get backup time.
  • Take the short-circuit current values (3500 and 5400 A) into DC protection and selectivity calculations.
  • Define UPS and BMS communication (Modbus, CanOpen, TCP-IP) in the design documents.
  • For seismic projects, check the cabinet seismic certification (IBC 2018, IEEE 693, Bellcore GR-63).

Who should read it

Electrical designers selecting lithium-ion UPS batteries and operations engineers evaluating a move from VRLA.

Document contents

  1. Main benefits
  2. From cell to module and system
  3. Flex'ion Gen2 system
  4. Key differentiators
  5. Product range
  6. Compliance to standards
  7. Technical data

Publication details

Authors
Saft
Publisher
Saft
Year
2023
Document number
22171-1123-2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Saft (2023). Saft Flex'ion Gen2 Li-ion Battery System. Saft. 22171-1123-2. https://www.standbypowersys.com/wp-content/uploads/2025/04/Saft-Flexion-Brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.