ZTE ZXESM E213 UPS lithium battery cabinet specifications

ZTE

ZTE's ZXESM E213 fire-resistant high-voltage lithium battery cabinet: 512 VDC, 170 Ah, up to 500 kW for 10 minutes of backup per cabinet, up to 6 cabinets in parallel, and UL 9540A and UL 1973 certifications.

On this page

Overview

The ZXESM E213 is an immersion-cooled lithium iron phosphate (LFP) battery cabinet that provides backup energy for a UPS power system. The cabinet comprises high-voltage power distribution and immersed lithium battery PACKs; each group holds 8 PACKs and up to 2 groups can be installed. The product page lists high energy density, cost-effective and convenient configuration, intelligent management and safety as its main headings.

On power and scalability, a single cabinet supports up to 500 kW at 10 minutes of backup with 6C high-rate discharge. The cabinet can be configured for half or full cabinet operation and expanded up to 6 cabinets in parallel in single-cabinet operation mode. PACKs need no maintenance for 10 years. Management uses a three-tier BMS architecture with remote monitoring and remote upgrade; communication is Modbus TCP.

For safety, immersion cell technology is used to eliminate ignition points, with thermal runaway detection and adaptive charging strategies, and the product holds dual UL 9540A and UL 1973 certification. The page gives cabinet-level and PACK-level values separately; PACK energy and mass should not be read as whole-cabinet values. It is an undated manufacturer product page.

Key points

  1. Cabinet dimensions 2200 x 800 x 1100 mm (H x W x D); protection rating IP20; natural cooling.
  2. Rated capacity 170 Ah, rated voltage 512 VDC, operating voltage range 432-552 VDC.
  3. 8 PACKs per group, up to 2 groups; maximum 6 cabinets in parallel; communication Modbus TCP.
  4. A single cabinet supports up to 500 kW at 10 minutes of backup; PACK discharge is 6C and recharge 1C.
  5. PACK: LFP, 64 V and 85 Ah, 5440 Wh, voltage range 50-73 V, temperature difference at most 3 degrees C; 290 x 965 x 160 mm; 70 kg (including immersion fluid); IP67; coolant is a custom hydrocarbon synthetic oil.
  6. Operating temperature 0-40 degrees C, storage 0-55 degrees C, altitude 0-4000 m, relative humidity 5-95%.
  7. Safety: UL 9540A and UL 1973 certification, thermal runaway detection and adaptive charging strategy.
  8. PACKs need no maintenance for 10 years.

Using it in design

  • Set the cabinet count from the 500 kW for 10 minutes backup target and the 6-cabinet parallel limit; do not mix cabinet and PACK values.
  • Compare the DC bus voltage range (432-552 VDC) with the UPS battery voltage window.
  • For the IP20 cabinet, plan the battery room environment (0-40 degrees C, 5-95% humidity) and the heat dissipation of natural cooling.
  • In the fire-safety specification require the UL 9540A and UL 1973 reports, thermal runaway detection and BMS communication (Modbus TCP) integration.
  • Include the 70 kg PACK weight and immersion fluid handling in the maintenance and transport plan.

Who should read it

Electrical designers and investment decision makers selecting lithium battery cabinets for UPS backup energy.

Document contents

  1. Features (high energy density, cost-effective and convenient, intelligent management, safe and reliable)
  2. Technical specifications (product parameters, PACK, environment)

Publication details

Authors
ZTE
Publisher
ZTE
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ZTE ZTE ZXESM E213 UPS lithium battery cabinet specifications. ZTE. https://www.zte.com.cn/global/solutions_latest/aidc/zxesm_e213_en.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.