EPC SLI / SL-P series technical specifications

EPC Enerji

EPC Enerji's SLI / SL-P is a 1-20 kVA single-phase, DSP-controlled double-conversion UPS: 12 model codes, 87-95% efficiency, THD of 2% or less and a 110-288 VAC input range.

On this page

Overview

EPC Enerji's product page describes the SLI / SL-P series as a single-phase input, single-phase output (1:1), fully DSP-controlled true double-conversion on-line UPS. The series covers 1-20 kVA in tower form and is recommended for IT, server and network infrastructure. The tables fall into two groups: 1-3 kVA (1 kVA/900 W, 2 kVA/1.8 kW, 3 kVA/2.7 kW) and 6-20 kVA (6 kVA/6 kW, 10 kVA/10 kW, 15 kVA/13.5 kW, 20 kVA/18 kW).

Model codes separate battery scope: SLI1101S, 1102S and 1103S have internal batteries; SLI1101L, 1102L and 1103L have none; for 6 and 10 kVA, SLI1106XS and 1110XS include batteries and 1106XL and 1110XL do not; 15 and 20 kVA are offered without batteries only (SLI1115XL, SLI1120XL). In the 1-3 kVA class the battery is 12 VDC/7 Ah blocs on a 36, 72 or 96 VDC bus; in the 6-20 kVA class it is 192 VDC (adjustable) with 12 VDC/7 Ah or 9 Ah blocs.

Common characteristics: input voltage range of 110-288 VAC, input frequency of 40-70 Hz, output of 220/230/240 VAC, voltage regulation of +/-1%, crest factor of 3:1 and automatically adjusted output frequency. The accepted lower input voltage falls as load falls; for example above 176 VAC at 100% load and above 110 VAC at 50% load. Input power factor lies in the 0.97-0.99 band, and output power factor is 0.9 or 1 by model.

Inverter-mode overload in the 1-3 kVA class is bypass after 1 minute at 105-130% and after 30 seconds at 150%. For 6-20 kVA the page gives 10 minutes at 110%, 1 minute at 125% and 30 seconds at 150%. Interfaces are RS232 as standard with SNMP, USB, dry contact, parallel kit and ECO kit as options; surge protection and manual bypass are optional hardware. Columns without a stated output rating or an unclear footprint are not derived from this page.

Key points

  1. Capacities: 1 kVA/900 W, 2 kVA/1.8 kW, 3 kVA/2.7 kW, 6 kVA/6 kW, 10 kVA/10 kW, 15 kVA/13.5 kW, 20 kVA/18 kW; single-phase input and output.
  2. Model codes: suffix S means with batteries, L means without; 15 and 20 kVA are battery-less only (XL).
  3. Input voltage is 110-288 VAC; above 176 VAC at 100% load and above 110 VAC at 50% load (1-3 kVA class).
  4. Efficiency is 87-95%: 87%, 90% and 91% in the 1-3 kVA class and 93.5% and 95% in the 6-20 kVA class.
  5. THDu is 1-2% or less on linear load and 5-5.5% or less on non-linear load; voltage regulation +/-1%; crest factor 3:1.
  6. Battery: 12 VDC/7 Ah blocs on 36/72/96 VDC for 1-3 kVA; 192 VDC (adjustable) with 16-24 blocs for 6-20 kVA.
  7. Dimensions (WxDxH): 1 kVA is 145x353x222 mm; 6 kVA is 190x510x705 mm; 15-20 kVA is 250x562x650-710 mm; 1-3 kVA weights lie in a 6-22 kg band in the table.
  8. Overload (6-20 kVA, inverter): 10 min at 110%, 1 min at 125%, 30 s at 150%; in battery mode it shuts down within 200 ms above 130%.

Using it in design

  • Size capacity from output power (W), not apparent power (kVA); the 15 kVA model delivers 13.5 kW and the 20 kVA model 18 kW.
  • Keep the battery-included (S) and battery-less (L) model codes apart; for XL models needing external batteries, calculate the 192 VDC bank voltage and runtime separately.
  • Judge the input voltage range, together with its load-dependent lower limits (176 and 110 VAC), against a poor mains or generator supply.
  • Compare the bypass and shutdown times in overload (for example 30 s at 150%) with the load's inrush behaviour.
  • A single-phase series suits only small, IT-room-scale loads in a three-phase facility; check phase balance in the design.

Who should read it

Electrical designers and purchasers choosing single-phase UPS for small data rooms and IT rooms.

Document contents

  1. Features
  2. 1-3 kVA parameters
  3. 6-20 kVA parameters
  4. Documents

Publication details

Authors
EPC Enerji
Publisher
EPC Enerji
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EPC Enerji EPC SLI / SL-P series technical specifications. EPC Enerji. https://epcas.com.tr/en/products/sli-sl-p-series/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.