Makelsan Powerpack SE RT 6-10 kVA Online UPS Datasheet

Original title Makelsan Powerpack SE RT 6-10 kVA datasheet

Makelsan

Makelsan Powerpack SE RT, at 6 kVA / 5400 W and 10 kVA / 9000 W, is a 1:1 phase rack/tower double-conversion VFI UPS with efficiency of at least 92% in AC mode and 98% in ECO mode.

On this page

Overview

The Makelsan Powerpack SE RT series is a high-frequency, true double-conversion online UPS family in 6 and 10 kVA, single-phase in and single-phase out, usable as rack or tower. The sheet classifies the unit as VFI type with an output power factor of 0.9, so the 6 kVA model gives 5400 W and the 10 kVA model 9000 W. Listed features include DSP technology, input power factor correction (PFC), cold start, frequency auto-sensing and output voltage selectable on the LCD.

Input voltage range is 115 to 295 ±5 VAC at half load and 165 to 295 ±5 VAC at full load, frequency 40 to 70 Hz and power factor at least 0.99. Output voltage is selectable at 208/220/230/240 VAC with ±1% regulation, and THD is at most 2% on linear and 5% on non-linear load. Transfer time from mains to battery and from inverter to bypass is 0 ms. Overload is 3 minutes at 105 to 125%, 30 seconds at 125 to 150% and 1 second above 150%.

Efficiency is at least 92% in AC mode, 91% in battery mode and 98% in ECO mode. Battery voltage is 192 VDC; the internal battery is 16 x 7 Ah or 16 x 9 Ah with an 8-hour recharge time, and long-time models offer 1/3/5/8 A charging. A built-in isolation transformer, parallel card and USB/SNMP communication are optional. Noise is at most 55 dB at 1 m. The document is a product sheet.

Key points

  1. 6 kVA / 5400 W and 10 kVA / 9000 W; output power factor 0.9; VFI type.
  2. Input: 165 to 295 ±5 VAC at full load, 115 to 295 ±5 VAC at half load; 40 to 70 Hz; power factor ≥0.99.
  3. Output voltage 208/220/230/240 VAC set on LCD; regulation ±1%; THD ≤2% (linear), ≤5% (non-linear).
  4. Transfer time 0 ms from mains to battery and inverter to bypass.
  5. Overload: 3 min at 105 to 125%, 30 s at 125 to 150%, 1 s above 150%.
  6. Efficiency: AC mode ≥92%, battery mode ≥91%, ECO mode ≥98%.
  7. Battery 192 VDC, 16 x 7 Ah or 16 x 9 Ah; 8 h recharge; long-time model charges at 1/3/5/8 A.
  8. 440 x 555 x 132 mm; net weight 16.4 to 17.1 kg (UPS), battery module 43.6 to 49.6 kg.

Using it in design

  • With a 0.9 power factor, the 6 kVA model's real capacity is 5.4 kW; check loads in kW.
  • The wide input range (down to 165 VAC at full load) reduces dependence on a generator at sites with weak mains.
  • For extended autonomy, size the external battery bank for 192 VDC and the selectable charging current.
  • ECO mode feeds the load from bypass; consider keeping it off for sensitive loads.
  • If galvanic isolation is required, write the built-in isolation transformer option into the specification.

Who should read it

Electrical engineers selecting rack/tower UPS units for server rooms and small data centres.

Document contents

  1. Features
  2. Input
  3. Output
  4. Efficiency
  5. Batteries
  6. Alarms
  7. Environment
  8. Management
  9. Physical

Publication details

Authors
Makelsan
Publisher
Makelsan
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Makelsan Makelsan Powerpack SE RT 6-10 kVA datasheet. Makelsan. https://www.makelsanjenerator.com.tr/katalog/powerpack-se-rt-series-6-10-kva.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.