Exide EHP Top Terminal Series Data Center Batteries Technical Datasheet
Original title Powersafe EHP top-terminal series technical datasheet
Exide Industries
The Exide EHP12 series is a 12 V VRLA battery for data centre UPS: 390-730 W for 15 min (1.67 V per cell), 3.15-4.90 mΩ internal resistance, 2100-4100 A short-circuit current, 13.7 V float.
On this page
Overview
The datasheet presents Exide Industries' EHP12-390W, 440W, 540W and 730W 12 V batteries for data centres. The 15-minute power ratings to 1.67 V per cell are 390, 440, 540 and 730 W, specific power is 65-67 W/kg, and internal resistance is 4.90, 4.35, 3.70 and 3.15 mΩ respectively. Dimensions run from 407x173x235 mm to 536x250x250 mm. The battery can be discharged down to 10.02 V and uses lead-tin-calcium plates, a low-resistance glass fibre separator, double-sealed terminals and a reinforced ribbed container.
Charging parameters: for 20-30 °C ambient, float 13.7 V ±0.1 V and boost 14.1 V ±0.1 V per 12 V unit; temperature compensation -18 mV/°C per 12 V unit at a 25 °C reference; string equalisation in boost mode every three months for 16-24 hours. Charging current minimum/maximum is 10.5-26 A (390W), 12.5-31 A (440W), 15.5-39 A (540W) and 21-53 A (730W). Power varies with temperature: 102% at 40 °C, 100% at 25 °C, 82% at 0 °C and 62% at -15 °C.
The document also supplies design data: hydrogen evolution of 0.00057-0.00111 m3/h per battery, an airflow formula (dilution ratio 24, safety factor for example 5, 4% lower explosive limit) and heat generation during charging of 2.84-5.54 W. Constant-power tables per cell from 10 to 60 minutes at 27 °C for ECV 1.67-1.80 V are given for every model; for the EHP12-390W, 390 W at 1.67 V for 15 min and 142 W for 60 min. Short-circuit current is 2100, 2500, 3100 and 4100 A; terminal torque 12.3 N-m; cable sizing 2 A/mm2 with maximum cable drop below 20 mV/m.
Key points
- Four models: EHP12-390W, 440W, 540W, 730W; 15 min power 390-730 W (1.67 V per cell), specific power 65-67 W/kg.
- Internal resistance 4.90, 4.35, 3.70 and 3.15 mΩ; short-circuit current 2100, 2500, 3100 and 4100 A.
- Float 13.7 V ±0.1 V, boost 14.1 V ±0.1 V (12 V unit, 20-30 °C); temperature compensation -18 mV/°C.
- String equalisation in boost mode every three months for 16-24 hours.
- Temperature effect on power: 40 °C 102%, 25 °C 100%, 0 °C 82%, -15 °C 62%.
- Hydrogen evolution 0.00057-0.00111 m3/h and heat generation on charge 2.84-5.54 W per battery.
- Airflow: d x s x hydrogen evolved; d = 24 (4% lower explosive limit), s for example 5.
- Terminal torque 12.3 N-m; cable sizing 2 A/mm2; maximum cable drop below 20 mV/m.
Using it in design
- Size UPS autonomy from the constant-power tables (ECV 1.67-1.80 V, 10-60 min) and note that the values are reached after 5 charge/discharge cycles.
- Calculate battery room ventilation with the datasheet hydrogen evolution and the d x s formula; add the heat generation to the cooling load.
- Set charger float 13.7 V and boost 14.1 V with temperature compensation.
- Select DC protective device breaking capacity for the 2100-4100 A short-circuit current.
- Account for the capacity loss at low temperature (82% at 0 °C) in room temperature design.
Who should read it
Electrical engineers designing data centre UPS battery systems and battery room ventilation designers.
Document contents
- Product Range
- Features
- Charging Parameters
- Construction
- Effect of temperature on Power
- Gas Evolution and Air Flow Calculation
- Heat Generation
- Constant Power Discharge Rating
- Charging Characteristics and Other Information
Publication details
- Authors
- Exide Industries
- Publisher
- Exide Industries
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Exide Industries Powersafe EHP top-terminal series technical datasheet. Exide Industries. https://docs.exideindustries.com/pdf/industrial-batteries/EHP-Top-Terminal-Series-Technical-Datasheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.