FVH Series Stationary Valve-Regulated Lead-Acid Batteries (Furukawa Battery)

Original title FVH stationary valve-regulated lead-acid batteries

Furukawa Battery

Furukawa Battery's FVH series is the high-rate discharge variant of its MSE stationary VRLA range, aimed at UPS use with a stated float life of about 7-9 years at 25 °C.

On this page

Overview

The page introduces the FVH series in Furukawa Battery's industrial stationary battery catalogue. The series is described as the high-rate discharge version of the MSE series, with UPS use named as the application. Expected float life is about 7-9 years (25 °C, 3.3C 10 A condition).

Listed features are strong high-rate discharge characteristics through better current collection and lower separator resistance, which allows a smaller battery capacity for the same duty (space saving), easier installation through nut-insert terminal posts (except the 50 Ah unit), and a fire-code certified product (MSE-R). The batteries hold type approval from the battery equipment approval committee.

The table gives for each model the nominal voltage, 10-hour capacity, 10-minute capacity and current, approximate dimensions and mass. Monobloc types (FVH-100-12 and FVH-150-8) offer economy, smaller battery panels, lower mass and fewer tightening operations thanks to nut-insert terminals. The page is published in Japanese and points to a free catalogue.

Key points

  1. FVH is the high-rate discharge type of the MSE series and targets UPS applications.
  2. Expected float life is about 7-9 years (25 °C, 3.3C 10 A).
  3. FVH-50-12: 12 V, 50 Ah (10 h), 28.3 Ah and 170 A for 10 minutes, about 25 kg.
  4. FVH-100-12: 12 V, 100 Ah, 55.3 Ah and 332 A for 10 minutes, about 50 kg; FVH-150-8: 8 V, 150 Ah, 83 Ah and 498 A, about 49 kg.
  5. 2 V cells: FVH-200 (200 Ah, 680 A for 10 min, 18 kg) and FVH-300 (300 Ah, 1020 A for 10 min, 25 kg).
  6. FVH-100-12 approximate size: 353 mm overall height, 322 x 165 mm footprint.
  7. Nut-insert posts (except 50 Ah) reduce installation effort; a fire-code certified MSE-R option exists.

Using it in design

  • For UPS batteries, use the 10-minute current value (A) to set cell count at short autonomy and high power.
  • Compare monobloc (12 V/8 V) and 2 V cell options on battery panel size and weight.
  • Include the 7-9 year float life in the battery replacement plan and total cost of ownership.
  • State tightening torque and connection procedure in the installation plan according to the nut-insert terminal.

Who should read it

Electrical designers selecting UPS batteries and engineers comparing stationary battery families for the Japanese market.

Publication details

Authors
Furukawa Battery
Publisher
Furukawa Battery
Year
Year not stated
Document language
Japanese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Furukawa Battery FVH stationary valve-regulated lead-acid batteries. Furukawa Battery. https://corp.furukawadenchi.co.jp/ja/products/indust/fvh.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.