Hankook Battery UPS application batteries: VGS, KBX, KBA, KB, KR, ITX

Original title UPS application batteries: VGS and KBX

Hankook Battery

The Hankook Battery (Korea) UPS page lists 2 V VRLA gel (VGS) and AGM (KBX, KBA), 12 V AGM (KB, KR) and 12 V MF (ITX) series with capacity, dimension and weight tables; VGS 160 is 160 Ah and 15 kg.

On this page

Overview

The UPS page of Korea-based Hankook Battery (Hankook and Company ES business) presents its industrial battery families by application class. The page is in Korean and was edited in November 2023. Each series has a short feature list, uses and a product table of model name, nominal voltage, capacity (Ah), length, width, height, total height and weight. The manufacturer notes that the tables are subject to change.

The 2 V VRLA products fall in two groups. The VGS gel series is described by its gelled electrolyte (small specific-gravity variation, almost no electrolyte loss, no leakage risk), and can be arranged horizontally or vertically. VGS 160 is 2 V, 160 Ah (10 hour, 1.8 V per cell), 103 x 206 x 354 mm (total height 386 mm) and 15 kg; VGS 200 is 200 Ah and 18.5 kg; VGS 250 is 250 Ah, 124 mm long and 23 kg. KBX and KBA are 2 V AGM series; their tables include capacity columns at different discharge hours such as 10, 5, 3 and 1.

In the 12 V group the KB series promises long life and deep-cycle performance through the country's first full-frame special alloy plate, with uses including stand-by, UPS, telecom, rectifier and switchgear. The KR series is for small and medium 1-100 kWh renewable and ESS applications, and the ITX 12 V MF series for UPS, switchgear, computer backup, emergency lighting and generator starting. For example ITX40 is 12 V, 40 Ah (20 hour), 187 x 127 x 200 mm (total 222 mm). The capacity end voltage must be read according to the selected table.

Key points

  1. VGS: 2 V VRLA gel; VGS 160 = 160 Ah (10 hour, 1.8 V per cell), 103 x 206 x 354 mm (total 386 mm), 15 kg.
  2. VGS 200: 200 Ah, 18.5 kg; VGS 250: 250 Ah, 124 mm length, 23 kg.
  3. KBX and KBA: 2 V VRLA AGM; capacity columns at 10, 5, 3 and 1 hours (end voltages from 1.8 V to 1.6 V per cell).
  4. KB: 12 V AGM, full-frame special alloy plate, deep cycle; UPS and stand-by use.
  5. KR: 12 V AGM for 1-100 kWh renewable/ESS and 1-10 kWh home ESS.
  6. ITX40: 12 V MF, 40 Ah (20 hour), 187 x 127 x 200 mm (total 222 mm).
  7. Uses: UPS, telecom, security and emergency power, backup power, solar and wind energy.

Using it in design

  • In 2 V-cell UPS battery strings, take length, width and total height from the VGS/KBX/KBA tables into the rack design.
  • When comparing capacities keep the table's hour rate (10, 5, 3, 1 hour) and end voltage the same.
  • Since the VGS gel cells can be arranged horizontally or vertically, consider that as a layout option in space-constrained rooms.
  • Do not derive cabinet energy or load-time relations from the page; get them from the manufacturer.

Who should read it

Engineers designing UPS battery rooms and battery purchasing teams.

Document contents

  1. UPS battery page: VGS (2 V gel)
  2. KBX (2 V AGM)
  3. KBA (2 V AGM)
  4. KB (12 V AGM, full frame)
  5. KR (12 V AGM, ESS)
  6. ITX (12 V MF)

Publication details

Authors
Hankook Battery
Publisher
Hankook Battery
Year
Year not stated
Document language
Korean
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Hankook Battery UPS application batteries: VGS and KBX. Hankook Battery. https://www.hankook-battery.com/ko/m/product/ups.do

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.