Numeric Onfiniti+ 1-10 kVA FM/FMI Brochure (February 2025)
Original title Numeric Onfiniti+ 1-10 kVA FM/FMI brochure, February 2025
Numeric
A Numeric brochure comparing the FM and FMI versions of the Onfiniti+ single-phase 230 V double-conversion on-line UPS family across seven ratings from 1 to 10 kVA.
On this page
Overview
The brochure presents a compact single-phase UPS family aimed at residential, small office, commercial, healthcare, infrastructure and education segments. Highlighted features include a small footprint, an LCD display, a wide input voltage range, an optional built-in galvanic isolation transformer, solar and generator compatibility and efficiency of up to 94%. All models are on-line double conversion, classified VFI-SS-111.
It contains two technical tables: the FM version and the FMI version with an isolation transformer. Both are defined for 1, 2, 3, 5, 6, 7.5 and 10 kVA, with active output power of 800, 1600, 2400, 4000, 4800, 6000 and 8000 W respectively. Input voltage is 230 VAC and input frequency is 50-60 Hz plus or minus 8% with auto-sensing. The input voltage range is 160-300 VAC at full load (176-300 VAC on larger models) and falls to 110-300 VAC at reduced load; input power factor is 0.99 or higher at full linear load.
On the output, voltage is 230 VAC (adjustable 220/230/240 VAC), frequency 50/60 Hz plus or minus 0.1 Hz, crest factor 3:1, voltage THD below 3% at full linear load and below 5% at full non-linear load. AC-AC efficiency at full load ranges from at least 87% to 93% on FM and from at least 80% to 87% on FMI; ECO mode is given as 97%. Overload capacity is stepped by model group (for example 10 minutes at 105-110%, 2 minutes at 111-130%, 30 seconds at 131-150%). Battery voltage ranges from 36 VDC to 192-240 VDC, and battery types are VRLA, tubular or lithium-ion.
Communication is by RS232 and USB, with SNMP, MODBUS and dry contacts optional. Protection is IP20, relative humidity up to 95% non-condensing, and standards are IEC 62040-1, -2, -3 and IS 16242. The document is a product brochure; the measurement condition of the efficiency headlines is left to the detailed data sheet, so no load curve should be derived.
Key points
- Seven ratings: 1, 2, 3, 5, 6, 7.5 and 10 kVA; output power 800, 1600, 2400, 4000, 4800, 6000 and 8000 W.
- Double-conversion on-line, class VFI-SS-111; sinusoidal output waveform.
- Input: 230 VAC, 50-60 Hz plus or minus 8%; 160-300 VAC (176-300 VAC on larger models) at full load, 110-300 VAC at reduced load; input power factor at least 0.99.
- Output 230 VAC (adjustable 220/230/240), THD below 3% (linear) and below 5% (non-linear), crest factor 3:1.
- AC-AC efficiency at full load: FM at least 87% to 93%, FMI at least 80% to 87%; ECO mode 97% (not available on larger models).
- Battery voltage from 36 VDC to 192/204/216/228/240 VDC; VRLA, tubular or lithium-ion; capacity depends on external batteries.
- Relative humidity 0-95% non-condensing, IP20, operating temperature 0-40 or 0-50 degrees C by model, noise at 1 m below 50 to 58 dBA.
- Standards IEC 62040-1, -2, -3 and IS 16242 (Part 1): 2014.
Using it in design
- Enter only the seven discrete ratings and two versions (FM, FMI) published in the document into the catalogue; do not derive models from a continuous range.
- Check the VFI-SS-111 class and 0.99 input power factor against the specification for small critical loads; if isolation is needed choose FMI and account for its lower efficiency.
- Use active power (W) separately from kVA: the 10 kVA model outputs 8000 W.
- At sites with large mains voltage swings, verify the lower input limit at full load (160 or 176 VAC) and the 110 VAC limit at reduced load.
- Match battery type (VRLA, tubular, lithium-ion) and the number of series blocks to the model's battery voltage.
Who should read it
Engineers selecting single-phase UPS for small and medium critical loads and teams preparing a product catalogue.
Document contents
- Features and segments
- Why Onfiniti+
- Technical specifications: Onfiniti+ 1-10 kVA FM
- Technical specifications: Onfiniti+ 1-10 kVA FMI
Publication details
- Authors
- Numeric
- Publisher
- Numeric
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Numeric (2025). Numeric Onfiniti+ 1-10 kVA FM/FMI brochure, February 2025. Numeric. https://cms.numericups.com/sites/default/files/2025-02/OnfinitiPlus_Brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.