Sanyo Denki SANUPS A11N catalogue P1054B004, 2026-02
Sanyo Denki
Sanyo Denki's manufacturer catalogue for the double-conversion SANUPS A11N single-phase UPS family, expandable in parallel from 5 to 20 kVA, with its model list, technical specifications and dimensions.
On this page
Overview
The SANUPS A11N is a double-conversion on-line single-phase UPS designed for servers, base stations and factory facilities. The catalogue states that up to four 5 kVA units can be paralleled to reach 20 kVA. The rating of the 5 kVA unit is 5 kVA / 4.5 kW (load power factor 0.9); the table gives parallel (N) configurations of 10 kVA / 9 kW, 15 kVA / 13.5 kW and 20 kVA / 18 kW and redundant (N+1) configurations of 5, 10 and 15 kVA. For example, the N+1 capacity of a two-unit system with 10 kVA N capacity is 5 kVA.
For efficiency the catalogue gives 94% (up to 95.1%) for a single 5 kVA unit of the 5-minute backup model. In the 5 kVA technical table the input is single-phase 2-wire, rated voltage 200/208/220/230/240 V, voltage range -40% to +15% of rated voltage, and input power factor 0.95 or greater. Output voltage is selectable between 200 and 240 V (factory setting 200 V), regulation is ±2%, and voltage harmonic distortion at linear load is 3% or less. The IEC classification is VFI-SS-111.
The battery is a small VRLA type, 16 pieces of 12 V; 1200 Wh (3U) for the 5-minute backup model and 1632 Wh (4U) for the 10-minute model. Backup time is quoted at 25 °C and load power factor 0.9 for the 5-minute model and 0.8 for the 10-minute model. Noise at 1 m is 45 dB or less excluding the start of charging, and heat dissipation at rated output is 287 W. UL/CE certified models have no maintenance bypass; the battery cold-start function is selectable at order but not available on UL/CE certified models.
The catalogue also lists types with a power distribution unit (PDU), rack-mount (RM) and free-standing models, larger configurations (25, 35, 45 kVA) and backup time options of 5, 10, 30, 60 and 180 minutes; this page covers the technical data of the 5 and 10 kVA ratings.
Key points
- Double-conversion on-line, single-phase; a 5 kVA / 4.5 kW unit, up to 4 in parallel, gives 20 kVA / 18 kW.
- N configuration: 5, 10, 15, 20 kVA; N+1 configuration: 5, 10, 15 kVA (a 10 kVA N system has two units and an N+1 capacity of 5 kVA).
- Efficiency 94% (up to 95.1%) for a single 5 kVA unit of the 5-minute backup model.
- Input 200/208/220/230/240 V, range -40% to +15%, power factor 0.95 or greater; output voltage selectable (factory 200 V), regulation ±2%.
- Overload: inverter 110% / 1 min and 118% instantaneous; bypass 200% / 30 s and 800% / 2 cycles.
- Battery 16 x 12 V VRLA; 1200 Wh (3U) in the 5-min model, 1632 Wh (4U) in the 10-min model; expected battery life 5 years.
- IEC class VFI-SS-111; noise 45 dB or less (1 m), heat dissipation 287 W.
- Operating 0 to 40 °C, humidity 10-90%; expected unit service life 10 years (30 °C average).
Using it in design
- In small and edge room design, read nominal power in kVA and kW together: a 5 kVA unit gives 4.5 kW at power factor 0.9.
- Where N+1 is needed, a 10 kVA N system built from two 5 kVA units gives 5 kVA of redundant capacity; limit the load accordingly.
- Compare backup time with the model's conditions (power factor 0.9 for 5 min, 0.8 for 10 min, 25 °C).
- In the rack layout include the 3U (5 min) and 4U (10 min) sizes and the rack support rails among the options.
- If a maintenance bypass is needed, remember that UL/CE certified models do not have it.
Who should read it
Electrical and IT infrastructure engineers selecting small UPSs for edge, server rooms and factory facilities.
Document contents
- Features: high efficiency, reliability, easy maintenance, space saving
- Scalable capacity and load level versus backup time
- Lineup
- Specifications (5, 10, 15, 20 kVA)
- Dimensions
Publication details
- Authors
- Sanyo Denki
- Publisher
- Sanyo Denki
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sanyo Denki (2026). Sanyo Denki SANUPS A11N catalogue P1054B004, 2026-02. Sanyo Denki. https://publish.sanyodenki.com/library/books/SANUPS_A11N_E/book/data/SANUPS_A11N_E.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.