Sanyo Denki SANUPS A11N catalogue P1054B004, 2026-02

Sanyo Denki

Sanyo Denki's manufacturer catalogue for the double-conversion SANUPS A11N single-phase UPS family, expandable in parallel from 5 to 20 kVA, with its model list, technical specifications and dimensions.

On this page

Overview

The SANUPS A11N is a double-conversion on-line single-phase UPS designed for servers, base stations and factory facilities. The catalogue states that up to four 5 kVA units can be paralleled to reach 20 kVA. The rating of the 5 kVA unit is 5 kVA / 4.5 kW (load power factor 0.9); the table gives parallel (N) configurations of 10 kVA / 9 kW, 15 kVA / 13.5 kW and 20 kVA / 18 kW and redundant (N+1) configurations of 5, 10 and 15 kVA. For example, the N+1 capacity of a two-unit system with 10 kVA N capacity is 5 kVA.

For efficiency the catalogue gives 94% (up to 95.1%) for a single 5 kVA unit of the 5-minute backup model. In the 5 kVA technical table the input is single-phase 2-wire, rated voltage 200/208/220/230/240 V, voltage range -40% to +15% of rated voltage, and input power factor 0.95 or greater. Output voltage is selectable between 200 and 240 V (factory setting 200 V), regulation is ±2%, and voltage harmonic distortion at linear load is 3% or less. The IEC classification is VFI-SS-111.

The battery is a small VRLA type, 16 pieces of 12 V; 1200 Wh (3U) for the 5-minute backup model and 1632 Wh (4U) for the 10-minute model. Backup time is quoted at 25 °C and load power factor 0.9 for the 5-minute model and 0.8 for the 10-minute model. Noise at 1 m is 45 dB or less excluding the start of charging, and heat dissipation at rated output is 287 W. UL/CE certified models have no maintenance bypass; the battery cold-start function is selectable at order but not available on UL/CE certified models.

The catalogue also lists types with a power distribution unit (PDU), rack-mount (RM) and free-standing models, larger configurations (25, 35, 45 kVA) and backup time options of 5, 10, 30, 60 and 180 minutes; this page covers the technical data of the 5 and 10 kVA ratings.

Key points

  1. Double-conversion on-line, single-phase; a 5 kVA / 4.5 kW unit, up to 4 in parallel, gives 20 kVA / 18 kW.
  2. N configuration: 5, 10, 15, 20 kVA; N+1 configuration: 5, 10, 15 kVA (a 10 kVA N system has two units and an N+1 capacity of 5 kVA).
  3. Efficiency 94% (up to 95.1%) for a single 5 kVA unit of the 5-minute backup model.
  4. Input 200/208/220/230/240 V, range -40% to +15%, power factor 0.95 or greater; output voltage selectable (factory 200 V), regulation ±2%.
  5. Overload: inverter 110% / 1 min and 118% instantaneous; bypass 200% / 30 s and 800% / 2 cycles.
  6. Battery 16 x 12 V VRLA; 1200 Wh (3U) in the 5-min model, 1632 Wh (4U) in the 10-min model; expected battery life 5 years.
  7. IEC class VFI-SS-111; noise 45 dB or less (1 m), heat dissipation 287 W.
  8. Operating 0 to 40 °C, humidity 10-90%; expected unit service life 10 years (30 °C average).

Using it in design

  • In small and edge room design, read nominal power in kVA and kW together: a 5 kVA unit gives 4.5 kW at power factor 0.9.
  • Where N+1 is needed, a 10 kVA N system built from two 5 kVA units gives 5 kVA of redundant capacity; limit the load accordingly.
  • Compare backup time with the model's conditions (power factor 0.9 for 5 min, 0.8 for 10 min, 25 °C).
  • In the rack layout include the 3U (5 min) and 4U (10 min) sizes and the rack support rails among the options.
  • If a maintenance bypass is needed, remember that UL/CE certified models do not have it.

Who should read it

Electrical and IT infrastructure engineers selecting small UPSs for edge, server rooms and factory facilities.

Document contents

  1. Features: high efficiency, reliability, easy maintenance, space saving
  2. Scalable capacity and load level versus backup time
  3. Lineup
  4. Specifications (5, 10, 15, 20 kVA)
  5. Dimensions

Publication details

Authors
Sanyo Denki
Publisher
Sanyo Denki
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sanyo Denki (2026). Sanyo Denki SANUPS A11N catalogue P1054B004, 2026-02. Sanyo Denki. https://publish.sanyodenki.com/library/books/SANUPS_A11N_E/book/data/SANUPS_A11N_E.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.