Sendon RM31 Series 10-40 kVA product technical table

Sendon

Sendon's RM31 series is a pure online double-conversion UPS family for 380/400/415 V, 50/60 Hz grids: 10-40 kVA, input power factor 0.99, THDi below 3%, 95% efficiency in normal mode and 99% in economy mode.

On this page

Overview

The Sendon (Delta UPS branded) RM31 series product page presents pure online double-conversion UPS for 10-40 kVA. The series supports 380/400/415 V, 50/60 Hz grid systems. The page states strong load adaptability, strong overload and short-circuit capability, a very wide input voltage and frequency range (suitable for diesel generator connection), input power factor of 0.99, input harmonic current below 3% and efficiency above 95%.

Control is fully digital on a DSP (rectifier, inverter, charge and discharge). Digital circulating current control raises paralleling reliability, intelligent battery management extends battery life and all fans are redundant. Mean time between failures (MTBF) is above 200,000 hours and mean time to repair (MTTR) below 0.5 hours. Options are a dust filter, SNMP card, lightning protection module, battery temperature compensator and SMS alarm device.

The table lists six models: SERM10KNTL, SERM15KNTL, SERM20KNTL (8, 12, 16 kW) and HTRM20KVA, HTRM30KVA, HTRM40KVA (16, 24, 32 kW). Input voltage is 380/400/415 V; range +25%/-25% at full load and +25%/-40% with load, derating linearly from 100% to 70%. Output is 208/220/230/240 VAC (±1%) or 380/400/415 VAC (±0.5%), output power factor 0.8, overload 105% continuous, 110% for 1 h, 125% for 10 min, 150% for 1 min and immediate shutdown above 150%. Efficiency is 95% in normal mode and 99% in economy mode; battery voltage is 192 Vdc (240 Vdc customisable) or ±192 to ±240 Vdc (32-40 blocks selectable). Weight is 32-36 kg.

Key points

  1. Pure online double conversion; 380/400/415 V, 50/60 Hz; 10-40 kVA, models 8-32 kW (output PF 0.8).
  2. Input power factor 0.99, input harmonic current below 3%, efficiency above 95%; 95% normal mode, 99% economy mode.
  3. Input voltage range +25%/-25% at full load; +25%/-40% with load, linear derating from 100% to 70%.
  4. Output voltage 208/220/230/240 VAC (±1%) or 380/400/415 VAC (±0.5%).
  5. Overload: 105% continuous, 110% 1 h, 125% 10 min, 150% 1 min, above 150% immediate shutdown.
  6. Battery: 192 Vdc (240 Vdc customisable) or ±192 to ±240 Vdc (32-40 blocks selectable).
  7. MTBF > 200,000 h, MTTR < 0.5 h; redundant fans; fully digital DSP control.
  8. Weight 32-36 kg; options: dust filter, SNMP, lightning protection, battery temperature compensator.

Using it in design

  • Check the model power in watts: with output PF 0.8 the 10 kVA model gives 8 kW; choose the next size for high-PF IT loads.
  • Behind a generator, use the wide input range and the 0.99 PF and 3% THDi in generator sizing; account for load derating at low voltage.
  • Set the battery block count (32-40) from the UPS DC bus voltage and the ±192 to ±240 Vdc range.
  • If ECO mode (99% efficiency) is used, confirm load sensitivity and transfer behaviour with the manufacturer.
  • Use the overload curve (150% for 1 min) as an input to upstream protection and bypass selectivity studies.

Who should read it

Electrical designers selecting online UPS for small and mid-size data rooms.

Document contents

  1. Performance features
  2. Model table (SERM and HTRM)
  3. Input, output, efficiency, battery and physical parameters

Publication details

Authors
Sendon
Publisher
Sendon
Year
Year not stated
Document language
Chinese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only. Original publisher HTTP URL retained as a bibliographic link. Its HTTPS counterpart could not be verified on 2026-11-16; no content was downloaded or redistributed.

Citation

Sendon Sendon RM31 Series 10-40 kVA product technical table. Sendon. http://sendonelec.com/index-en/product-en/63.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.