SHVP512120A01 / C01 lithium UPS battery rack specification
Shoto
Shoto's summary specification for a 512 V, 120 Ah (61.44 kWh) LiFePO4 UPS battery rack: 272 kW constant power for 10 minutes, 121 kW for 30 minutes, 15-year design life.
On this page
Overview
The document is a two-page summary specification of Shoto's LiFePO4 battery rack for UPS and energy storage use. The SHVP512120A01 model ships with the battery management unit (BAU) and HMI, while the SHVP512120C01 ships without them. The rack is built from 3.2 V 40 Ah cells in a 160-series, 3-parallel arrangement and gives 120 Ah at a nominal 512 V, which is 61.44 kWh of nominal energy.
The operating window is 432-568 V: 432 V is the discharge cut-off and 568 V the charge voltage, with a recommended charge current of at most 120 A. Charge temperature is 0-45 °C, discharge temperature -20 to 45 °C and relative humidity 5-95%. Cooling is natural. The rack is described as compatible with common 2-wire and 3-wire UPS designs, and up to 16 racks may be paralleled.
The performance table gives constant-power and constant-current values for three durations: 272 kW (630 A) for 10 minutes, 243 kW (563 A) for 15 minutes and 121 kW (282 A) for 30 minutes. Each module contains a perfluorohexane fire-extinguishing device, high-precision insulation monitoring, voltage and temperature sampling accurate to +/-3 mV and +/-1 °C, and passive balancing of up to 100 mA.
The rack measures 600x1000x2000 mm (W x D x H) and weighs about 850 kg. Communication runs over RS485, TCP and CAN, with 6 dry-contact inputs and 6 outputs. Certifications are UL1973, IEC62619, UN38.3 and UL9540A. The sheet is a short product description, and the manufacturer notes that parameters may change without notice.
Key points
- Cell 3.2 V 40 Ah in 160S3P; nominal 512 V, 120 Ah, 61.44 kWh.
- Voltage range 432-568 V; recommended charge current at most 120 A.
- Constant power: 10 min 272 kW (630 A), 15 min 243 kW (563 A), 30 min 121 kW (282 A).
- Charge 0-45 °C, discharge -20 to 45 °C, humidity 5-95%; natural cooling.
- Size 600x1000x2000 mm, weight about 850 kg.
- Up to 16 racks in parallel; RS485/TCP/CAN plus 6 dry-contact inputs and 6 outputs.
- 15-year design life; UL1973, IEC62619, UN38.3 and UL9540A certifications.
- In-module perfluorohexane extinguisher, insulation monitoring and 100 mA passive balancing.
Using it in design
- Compare the load with the 10, 15 and 30 minute table points; a load above 121 kW for 30 minutes cannot be met by one rack, so size the number of parallel racks accordingly.
- Confirm that the UPS DC bus voltage fits the 432-568 V window and the 120 A recommended charge current.
- Calculate battery room floor loading from the roughly 850 kg rack weight on a 600x1000 mm footprint.
- Keep room temperature within the 0-45 °C charge limit, and obtain in writing the ambient and ageing conditions that the power table assumes.
- If more than 16 racks are needed, plan separate DC distribution and battery groups; state in the specification whether the A01 (with BAU) or C01 (without BAU) variant carries the supervisory function.
Who should read it
Electrical designers selecting UPS battery systems, engineers planning lithium battery rooms, and procurement teams writing specifications.
Document contents
- Rack specification summary
- Performance data (10, 15, 30 min)
- Characteristics and protections
- Rack module size
- Characteristic curves
Publication details
- Authors
- Shoto
- Publisher
- Shoto
- Year
- Year not stated
- Document number
- V2.4
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Shoto SHVP512120A01 / C01 lithium UPS battery rack specification. Shoto. V2.4. https://www.shuangdeng.com.cn/userfiles/4cd5d807dc514b838f58401c8f3a3e9f/files/SHVP%E7%B3%BB%E5%88%97%E8%8B%B1%E6%96%87/SHVP512120A01%28512V120Ah%29%20specification-EN-V2_4-2000-2025_1_14.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.