Technical guideFree to readYear not stated

Surtas general catalogue: line interactive and on-line UPS technical tables (1-phase/1-phase, 3-phase/3-phase 10-600 kVA)

Original title Surtaş Trafo general catalogue, online UPS 1/1, p.47

Surtaş Elektrik Cihazları (Surtaş Trafo)

The UPS section of the Surtas A.S. general catalogue: 0.65-2 kVA line interactive, 1-10 kVA single-phase on-line and 10-600 kVA three-phase on-line models; 0 ms transfer time, THD below 3%.

On this page

Overview

The catalogue introduces the product range of Surtas Elektrik Cihazlari San. ve Tic. A.S., founded in 1977 in Karakoy, Istanbul: servo and static voltage regulators, on-line uninterruptible power supplies, cable lugs, battery charger rectifiers, transformers and other electrical products. It is bilingual (Turkish and English), and the UPS section sits between the transformer, regulator and charger sections. Stated usage areas are offices, hospitals, power plants, telecommunications, information technology, homes and factories.

The line interactive UPS comes in 650, 1000, 1400 and 2000 VA. Input is 170-270 VAC single phase, tolerance +/-10% and power factor above 98%. Transfer time is 0 ms, output is 220 VAC sine wave, and THD is below 3% on linear and below 5% on non-linear load. Dimensions run from 130x223x350 mm for 0.65 kVA to 145x360x453 mm for 2 kVA. Operating temperature is 0-40 °C, protection is IP20 and communication is RS-232, with SNMP, dry contact, USB card and external manual bypass optional.

The single-phase in/single-phase out on-line UPS series covers 1, 2, 3, 6 and 10 kVA (and 10-30 kVA) with the same input and output values; dimensions run from 130x223x390 mm for 1 kVA to 215x590x780 mm for 10 kVA. Efficiency is given as '<92%' and weight as 18-23-40 kg. The battery is fully closed, dry type and maintenance-free, with a battery working temperature below 25 °C. Protections are short circuit, over temperature, overload, high voltage and low battery level. Standards are EN 62040-1-1 (safety) and EN 62040-2 (EMC).

The three-phase in/out on-line UPS runs from 10 kVA to 600 kVA. Input is 3-phase 270-380 VAC +/-10% with input power factor above 98%, output is 220-380 VAC (240-415 VAC optional), power factor 0.8, THD below 3%/5% and efficiency '<94%'. Overload is 10 min at 100-125% load, 1 min at 125-150% and static bypass at 150%. The user interface is an LCD panel, LED panel and optional graphic touchscreen; inputs are EPO, battery panel and generator; the alarm record holds 192 events (512 optional); and there are 2 RS-232 ports with 4 standard and 8 optional dry alarm contacts. Dimensions grow from 425x800x1040 mm for 10-20 kVA to 890x1150x1900 mm for 200-600 kVA.

Key points

  1. Line interactive: 650, 1000, 1400, 2000 VA; transfer time 0 ms; THD <3% (linear), <5% (non-linear).
  2. Single-phase/single-phase on-line: 1-10 kVA and 10-30 kVA; input 170-270 VAC +/-10%; input PF above 98%.
  3. Three-phase/three-phase on-line: 10-600 kVA; output power factor 0.8; output 220-380 VAC (240-415 VAC optional).
  4. Three-phase overload: 10 min at 100-125%, 1 min at 125-150%, static bypass at 150%.
  5. Efficiency is stated as '<92%' for single-phase and '<94%' for three-phase models.
  6. Battery: fully closed, dry type, maintenance-free; battery working temperature below 25 °C.
  7. Three-phase cabinet size: 10-20 kVA 425x800x1040 mm; 200-600 kVA 890x1150x1900 mm.
  8. Standards EN 62040-1-1 (safety) and EN 62040-2 (EMC); communication RS-232, SNMP and dry contact options.

Using it in design

  • With output power factor 0.8, compare three-phase models in kW (kVA x 0.8); for example the 100 kVA model gives 80 kW.
  • Because efficiency is given as '<92%' and '<94%', ask the manufacturer for a load-point efficiency curve for energy and cooling calculations.
  • With a battery working temperature below 25 °C, keep the battery room below this limit; add cabinet dimensions (for example 890x1150x1900 mm) to the electrical room layout.
  • Add the generator input and EPO input to the control diagram; compare overload limits (10 min at 125%) with the design load.
  • Verify that the input voltage windows (170-270 VAC single phase; 270-380 VAC three phase, +/-10%) suit the grid conditions.

Who should read it

Electrical designers, facility engineers and procurement teams looking for domestic UPS in the Turkish market.

Document contents

  1. Company profile
  2. Line interactive UPS 650-2000 VA
  3. On-line UPS single-phase in/out 1-30 kVA
  4. On-line UPS three-phase in/single-phase out 10-30 kVA
  5. On-line UPS three-phase in/out 10-600 kVA
  6. Battery chargers, transformers and regulators

Publication details

Authors
Surtaş Elektrik Cihazları (Surtaş Trafo)
Publisher
Surtaş Elektrik Cihazları (Surtaş Trafo)
Year
Year not stated
Document language
Multilingual
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Surtaş Elektrik Cihazları (Surtaş Trafo) Surtaş Trafo general catalogue, online UPS 1/1, p.47. Surtaş Elektrik Cihazları (Surtaş Trafo). https://www.surtastrafo.com.tr/Content/assets/SURTA%C5%9E%20A.%C5%9E.%20KATALOG%20.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.