Gutor PEW Product Brochure: Electrical Table p.2 and Battery-Voltage/Rating Matrix p.3
Original title Gutor PEW product brochure, electrical table p.2 and battery-voltage/rating matrix p.3
Gutor
Gutor PEW is a single-phase industrial double-conversion UPS with galvanic isolation, a thyristor-controlled rectifier and IGBT-PWM inverter, battery levels of 110/125/220/400 VDC and efficiency up to 91%.
On this page
Overview
The document is the product brochure for the Gutor PEW single-phase industrial on-line double-conversion UPS. It is designed for harsh environments: transformer-based full galvanic isolation, an industrial enclosure up to IP42/NEMA 2, seismic design up to 1.0 g, operation up to 55 °C, coated boards and optional tinned copper bars. Controller firmware and hardware are stated to comply with IEC 60880 for nuclear power plant applications.
In the technical table, rectifier input is 380/400/415/480/600/690 V (and others), frequency 50/60 Hz ±8% and the DC link is 110/125/220/400 VDC. The rectifier is sized to supply 100% load and boost-charge the battery at the same time; float voltage is programmable 100-115% and boost 100-125%. Output static regulation is 1%, dynamic 4%, regulation time under 25 ms, overload 105% continuous, inverter 125% for 10 min and 150% for 1 min, bypass 1,000% for 100 ms and inverter short-circuit 200% for 100 ms. THD is 3% on linear load and 5% or less on non-linear load per IEC 62040-3.
The matrix on page 3 pairs battery voltage with UPS rating: 5, 10, 15, 20, 30, 40 and 50 kVA at 110/125/220 VDC; additionally 60, 80 and 100 kVA at 220 VDC; and 120, 150 and 200 kVA at 400 VDC. Higher ratings and other voltages are on request. General data give efficiency up to 91% depending on type, noise 60-75 dBA, IP20 protection, -10/+55 °C operation and altitude to 1,000 m without derating. Standards are IEC/EN 62040-1, -2, -3, UL 1778 and NEMA PE-1.
Key points
- Single-phase double-conversion UPS; thyristor-controlled rectifier and IGBT-PWM inverter; input and output transformers standard.
- Battery voltage levels 110, 125, 220 and 400 VDC; rating matrix: 5-50 kVA (110/125/220 VDC), 60-100 kVA (220 VDC), 120-200 kVA (400 VDC).
- Efficiency up to 91% depending on type.
- Static output regulation 1%, dynamic 4% (100% load surge), regulation time under 25 ms.
- Overload: 105% continuous, inverter 125% for 10 min and 150% for 1 min; bypass 1,000% for 100 ms.
- Output THD 3% on linear and 5% or less on non-linear load; allowed load PF 0.4 lag to 0.9 lead.
- Operating temperature -10/+55 °C, storage -20/+70 °C, 1,000 m without derating, noise 60-75 dBA.
- IP20 standard (up to IP42/NEMA 2 optional), seismic 1.0 g; lead-acid, NiCd, Li-ion and sodium-nickel batteries supported.
Using it in design
- Match battery voltage (110/125/220/400 VDC) to UPS rating from the matrix and check that the kVA and voltage combination exists.
- Use the efficiency (up to 91%, type dependent) per type in heat-loss and cooling calculations.
- Feed the galvanic isolation transformer and inverter short-circuit value (200% for 100 ms) into the selectivity and earthing scheme.
- For long autonomy and other battery chemistries, match rectifier boost settings (100-125%, 1-24 h) to the battery maker's values.
Who should read it
Electrical engineers designing critical DC/AC power for industrial, energy and process plants.
Document contents
- Product description and key features
- Technical data (input, DC link, output, general)
- Standards
- Single-line drawing and configuration options
- Battery voltage and UPS rating matrix
- Human-machine interface
Publication details
- Authors
- Gutor
- Publisher
- Gutor
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Gutor Gutor PEW product brochure, electrical table p.2 and battery-voltage/rating matrix p.3. Gutor. https://www.gutor.com/wp-content/uploads/2023/07/Gutor-PEW-Product-Brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.