J. Schneider MLT C: Online UPS with Ultracapacitors, Ratings and Backup Time Table
Original title J. Schneider MLT C online UPS with ultracapacitors, ratings and backup time table
J. Schneider Elektrotechnik
J. Schneider's MLT C page presents a 10-20 kVA three-phase online UPS that stores energy in ultracapacitors instead of batteries, with 7-13 seconds of backup at full load.
On this page
Overview
The page introduces the MLT C series from the German manufacturer J. Schneider Elektrotechnik. The series is an online UPS system of class VFI-SS-111 according to IEC/EN 62040-3. Energy is stored in ultracapacitors, which suit short-term buffer operation, are maintenance-free and are barely affected by temperature. Stated features include sinusoidal output voltage in all operating modes, an LCD display, RS232 and USB interfaces, two communication-card slots, an alarm and an emergency-stop function. Shutdown software for Windows, Novell and Linux is included. Up to 6 systems can be paralleled. The operating mode can be set to on-line, line-interactive or Smart Active, and use as an emergency (standby) supply is possible.
Technical data: nominal input voltage is 380/400/415 V (3+N), frequency of 50 or 60 Hz is detected automatically, and output voltage is 400 V AC. The models are MLT C 10 (10 kVA/9 kW), 12 (12 kVA/10.8 kW), 15 (15 kVA/13.5 kW) and 20 (20 kVA/18 kW). The power factor is therefore 0.9, and the usable kW value should drive selection rather than the kVA figure.
Backup times are in the order of seconds: the MLT C 10 gives 13 seconds at full load and 26 seconds at half load; the MLT C 12 gives 10 and 10 seconds; the MLT C 15 gives 9 and 17 seconds; and the MLT C 20 gives 7 and 13 seconds. These times show the system is meant as a short bridge until a generator starts, or as a buffer that complements an existing energy source.
Key points
- Four models: MLT C 10 (10 kVA/9 kW), 12 (12/10.8), 15 (15/13.5), 20 (20/18).
- Class VFI-SS-111 (IEC/EN 62040-3); sinusoidal output in all operating modes.
- Energy store is ultracapacitors: maintenance-free, barely temperature-dependent, suited to short-term buffering.
- Backup at full load: 13 s (10 kVA), 10 s (12), 9 s (15), 7 s (20).
- Backup at half load: 26 s (10 kVA), 10 s (12), 17 s (15), 13 s (20).
- Input 380/400/415 V (3+N), automatic frequency detection; output 400 V AC.
- Up to 6 systems in parallel; modes on-line, line-interactive, Smart Active and standby.
- Two communication-card slots, RS232 and USB, emergency stop, shutdown software.
Using it in design
- With backup measured in seconds, compare the generator start time and ATS transfer with that figure.
- Where battery maintenance and temperature sensitivity are unwanted, compare the ultracapacitor solution with a battery alternative.
- Confirm from the table that the 12 kVA model's half-load backup equals its full-load backup (10 s).
- For parallel redundancy, plan the 6-system limit and the shared operating mode.
- Match the communication-card slots to the building management system protocol.
Who should read it
Electrical designers seeking short-time bridging or battery-free UPS solutions, and industrial facility engineers.
Document contents
- MLT C online UPS system (VFI-SS-111)
- Technical data
- Rating and back-up time of the MLT C models
- Datasheet download
Publication details
- Authors
- J. Schneider Elektrotechnik
- Publisher
- J. Schneider Elektrotechnik
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
J. Schneider Elektrotechnik J. Schneider MLT C online UPS with ultracapacitors, ratings and backup time table. J. Schneider Elektrotechnik. https://j-schneider.de/en/products/uninterruptible-power-supplies/ac-ups/ac-ups-with-ultracapacitors/mlt-c
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.