Acumentrics Rugged UPS 2500/3000 Datasheet (99-0093_C)
Original title Acumentrics Rugged UPS 2500/3000 datasheet 99-0093_C, p.2
Acumentrics
Acumentrics datasheet for the 4U Rugged UPS 2500/3000 on-line double-conversion unit for military use: up to 2400 W continuous, -20 to 55 °C, paralleling to 21.6 kW (9 units) and LFP or VRLA batteries.
On this page
Overview
The datasheet presents the Acumentrics Rugged UPS 2500 and 3000 in a 4U chassis. Continuous output is 2000 W for the 2500 VA model and 2400 W for the 3000 VA model; the unit delivers this from -20 to 55 °C, with derating at the limits. Input can be 80-265 Vac and 47-440 Hz AC or 22-32 Vdc. Input power factor is 0.99 and efficiency is 86% from AC input and 82% from DC input.
The unit works with dual input priority: AC shore power first, then external DC input, then the internal battery; transfer time is zero. The battery pack can be LFP or VRLA and is hot-swappable in the field. At full load (2400 W) run time is 11 minutes on LFP and 6 minutes on VRLA, rising to 48 minutes on LFP at 600 W. Recharge takes 4 to 6 hours. Optional advanced paralleling gives up to 21.6 kW from 9 units.
Listed standards include MIL-STD-810 environmental tests, MIL-STD-461F EMI/EMC, MIL-STD-1275-D and MIL-STD-1399 (shipboard). The chassis is 178 x 432 x 533 mm and weighs 38.6 kg without battery, 46.7 kg with LFP and 61.2 kg with VRLA. Communication is SNMP v3 or RS-232. The product targets military use and is not designed as a data-centre rack product.
Key points
- Continuous output: 2500 VA / 2000 W and 3000 VA / 2400 W, -20 to 55 °C.
- Input: 80-265 Vac, 47-440 Hz or 22-32 Vdc; input power factor 0.99.
- Efficiency: 86% from AC input, 82% from DC input.
- Output 115 or 230 V ±5%, 60 or 50 Hz ±0.5%, sinusoidal; crest factor 2.5.
- Run time at 2400 W: 11 min (LFP) and 6 min (VRLA); at 600 W: 48 min (LFP) and 33 min (VRLA).
- Paralleling of up to 9 units for 21.6 kW.
- 4U, 178 x 432 x 533 mm; 38.6 kg without battery, 46.7 kg (LFP), 61.2 kg (VRLA).
- Operating altitude to 15,000 ft, storage temperature -40 to 65 °C.
Using it in design
- For edge and field cabinets outside data halls, use the wide input range (80-265 Vac, 47-440 Hz) and the DC input option.
- Read autonomy from the load-point table; 11 minutes of LFP at 2400 W needs external battery packs for long runtime.
- Record the 9-unit paralleling limit and the 21.6 kW ceiling in the load-growth plan.
- Use the weight range of 38.6 to 61.2 kg, by battery type, in rack capacity calculations.
Who should read it
Designers looking for a compact UPS for mobile, military or harsh-environment edge systems.
Document contents
- Power portability and key features
- On-line double conversion, Flo-Thru technology
- Specifications: input, output, battery run time, mechanical, environmental
- Standards and options
Publication details
- Authors
- Acumentrics
- Publisher
- Acumentrics
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Acumentrics Acumentrics Rugged UPS 2500/3000 datasheet 99-0093_C, p.2. Acumentrics. https://acumentrics.com/wp-content/uploads/2022/12/99-0093_C.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.