Artronic Alfa Pro Plus 3-Phase UPS, 60 kW to 1.2 MW
Original title ARTronic Alfa Pro Plus 3-phase selection guide, p.2
ARTronic
Artronic Alfa Pro Plus three-phase on-line UPS selection guide: 60-300 kVA (kW = kVA) cabinets, up to 4 units in parallel, 95-96% double-conversion and 98-99% ECO efficiency, input THDi below 4-5%.
On this page
Overview
The brochure presents Artronic's modular Alfa Pro Plus range from 60 kVA to 300 kVA in eight cabinet sizes (60K, 80K-A, 100K, 120K, 180K, 200K, 240K, 300K); the heading indicates up to 1.2 MW with four units in parallel. In each cabinet kVA equals kW. The product has dual mains inputs, four built-in switches (mains input, bypass input, output, maintenance bypass) and external batteries; hot-swappable power modules and front access aim to reduce MTTR.
The selection table gives input of 3x380/400/415 Vac, 110-300 V at 50% load or 184-276 V at full load, 40-70 Hz, input PF 0.99 and THDi below 4-5%. Output regulation is ±1% on balanced and ±2% on unbalanced load, THD 2% on linear and 4% on non-linear load. Overload: 110% for 1 hour, 111-125% for 10 min, 126-150% for 1 min, above 150% for 200 ms. Efficiency is 95-96% in AC mode, 98-99% in ECO mode and 94-95.5% in battery mode. Battery is ±192 to ±240 V (32-40 blocks of 12 V), float 2.28 V/cell, boost 2.35 V/cell, maximum charge current 18 to 90 A.
Physical data vary by model: 60K is 1000x320x800 mm and 94 kg, 300K is 1100x600x1475 mm and 396 kg (D x W x H). Protection is IP20 (IP31 optional), operation 0-40 °C, nominal power below 1000 m and 1% derating per 100 m above. Backfeed detection is included; the unit is generator compatible, has a 50/60 Hz frequency-converter mode and is compatible with Li-ion batteries. Standards are IEC/EN 62040-1 and -2 (C3).
Key points
- Eight cabinets: 60, 80, 100, 120, 180, 200, 240, 300 kVA (kW = kVA), three-phase in and out.
- Up to 4 units in parallel with a common battery; up to 1.2 MW per the heading.
- Input PF 0.99 (full load), THDi <4-5%; input 184-276 V at full load, 110-300 V at 50% load.
- Efficiency: AC mode 95-96%, ECO 98-99%, battery mode 94-95.5%.
- Overload: 110% 1 h, 111-125% 10 min, 126-150% 1 min, >150% 200 ms.
- Battery ±192 to ±240 V (32-40 blocks of 12 V), float 2.28 V/cell, maximum charge 18-90 A.
- 60K: 94 kg, 1000x320x800 mm; 300K: 396 kg, 1100x600x1475 mm.
- Operation 0-40 °C; 1% derating per 100 m above 1000 m; IP20 (IP31 option).
- Backfeed detection, 7-inch touch screen, Li-ion compatibility, frequency-converter mode.
Using it in design
- For a data hall, weigh the 4-unit paralleling and shared battery against the redundancy decision (n+1).
- Use input PF 0.99 and THDi <4-5% in generator sizing.
- When selecting on ECO efficiency, account for the changed protection class in that mode.
- Set the battery block count (32-40) together with charge current and autonomy requirements.
- Apply the 1% per 100 m derating for sites above 1000 m.
Who should read it
Electrical designers selecting three-phase UPS units for medium and large data centres.
Document contents
- Features and product outlook
- Selection guide: input, output, efficiency, bypass, battery, physical, environment
- Management and standards
Publication details
- Authors
- ARTronic
- Publisher
- ARTronic
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ARTronic ARTronic Alfa Pro Plus 3-phase selection guide, p.2. ARTronic. https://www.artronic.com.tr/Upload/ProductBrochure/76ccf32cccdb45d398c6e8a676736ca1-alfaplus%2060kw.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.