Artronic Alfa Pro Plus 3-Phase UPS, 60 kW to 1.2 MW

Original title ARTronic Alfa Pro Plus 3-phase selection guide, p.2

ARTronic

Artronic Alfa Pro Plus three-phase on-line UPS selection guide: 60-300 kVA (kW = kVA) cabinets, up to 4 units in parallel, 95-96% double-conversion and 98-99% ECO efficiency, input THDi below 4-5%.

On this page

Overview

The brochure presents Artronic's modular Alfa Pro Plus range from 60 kVA to 300 kVA in eight cabinet sizes (60K, 80K-A, 100K, 120K, 180K, 200K, 240K, 300K); the heading indicates up to 1.2 MW with four units in parallel. In each cabinet kVA equals kW. The product has dual mains inputs, four built-in switches (mains input, bypass input, output, maintenance bypass) and external batteries; hot-swappable power modules and front access aim to reduce MTTR.

The selection table gives input of 3x380/400/415 Vac, 110-300 V at 50% load or 184-276 V at full load, 40-70 Hz, input PF 0.99 and THDi below 4-5%. Output regulation is ±1% on balanced and ±2% on unbalanced load, THD 2% on linear and 4% on non-linear load. Overload: 110% for 1 hour, 111-125% for 10 min, 126-150% for 1 min, above 150% for 200 ms. Efficiency is 95-96% in AC mode, 98-99% in ECO mode and 94-95.5% in battery mode. Battery is ±192 to ±240 V (32-40 blocks of 12 V), float 2.28 V/cell, boost 2.35 V/cell, maximum charge current 18 to 90 A.

Physical data vary by model: 60K is 1000x320x800 mm and 94 kg, 300K is 1100x600x1475 mm and 396 kg (D x W x H). Protection is IP20 (IP31 optional), operation 0-40 °C, nominal power below 1000 m and 1% derating per 100 m above. Backfeed detection is included; the unit is generator compatible, has a 50/60 Hz frequency-converter mode and is compatible with Li-ion batteries. Standards are IEC/EN 62040-1 and -2 (C3).

Key points

  1. Eight cabinets: 60, 80, 100, 120, 180, 200, 240, 300 kVA (kW = kVA), three-phase in and out.
  2. Up to 4 units in parallel with a common battery; up to 1.2 MW per the heading.
  3. Input PF 0.99 (full load), THDi <4-5%; input 184-276 V at full load, 110-300 V at 50% load.
  4. Efficiency: AC mode 95-96%, ECO 98-99%, battery mode 94-95.5%.
  5. Overload: 110% 1 h, 111-125% 10 min, 126-150% 1 min, >150% 200 ms.
  6. Battery ±192 to ±240 V (32-40 blocks of 12 V), float 2.28 V/cell, maximum charge 18-90 A.
  7. 60K: 94 kg, 1000x320x800 mm; 300K: 396 kg, 1100x600x1475 mm.
  8. Operation 0-40 °C; 1% derating per 100 m above 1000 m; IP20 (IP31 option).
  9. Backfeed detection, 7-inch touch screen, Li-ion compatibility, frequency-converter mode.

Using it in design

  • For a data hall, weigh the 4-unit paralleling and shared battery against the redundancy decision (n+1).
  • Use input PF 0.99 and THDi <4-5% in generator sizing.
  • When selecting on ECO efficiency, account for the changed protection class in that mode.
  • Set the battery block count (32-40) together with charge current and autonomy requirements.
  • Apply the 1% per 100 m derating for sites above 1000 m.

Who should read it

Electrical designers selecting three-phase UPS units for medium and large data centres.

Document contents

  1. Features and product outlook
  2. Selection guide: input, output, efficiency, bypass, battery, physical, environment
  3. Management and standards

Publication details

Authors
ARTronic
Publisher
ARTronic
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ARTronic ARTronic Alfa Pro Plus 3-phase selection guide, p.2. ARTronic. https://www.artronic.com.tr/Upload/ProductBrochure/76ccf32cccdb45d398c6e8a676736ca1-alfaplus%2060kw.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.