Technical guideFree to readYear not stated

EverExceed Ultra High Rate VRLA/AGM battery: technical table

EverExceed

EverExceed's UHR series of 12 V VRLA/AGM batteries is rated in 15-minute watts per cell to 1.67 V/cell (21-880 W), certified to UL1989, IEC 61427 and IEC 60896, with 12-year design life.

On this page

Overview

EverExceed's product page presents the 12 V UHR (Ultra High Rate) series, designed for high-current discharge in UPS, emergency lighting, switchgear, telecom and industrial DC power. The series is listed with UL1989, IEC 61427, IEC 60896 and CE certificates. Rated capacity is given not in Ah but as watts per cell (WPC) over 15 minutes to a 1.67 V/cell end voltage; the model names on the page carry this watt value (for example UHR 12-480W). Amp-hours are not inferred from the model names.

The table lists 25 rows with the same columns, and 15-minute power per 12 V bloc runs from 21 W to 880 W. Each row gives UL model code, short-circuit current, internal resistance, terminal type, weight and dimensions. The smallest, UHR 12-21W, has 250 A short-circuit current, 45 mOhm internal resistance, a Faston Tab 187 terminal, 1.60 kg and 90 x 70 x 102 mm; the largest, UHR 12-880W, has 6600 A, 2.5 mOhm, an F-M8 terminal, 70.0 kg and 520 x 238 x 220 mm.

On construction the page states low-calcium, high-tin lead alloy plates, a highly porous glass micro-fibre separator, a reinforced ABS container (UL 94 HB) and silver-plated copper female terminal inserts. A flame-retardant UL 94 V-0 ABS option with an oxygen index above 28% is available. Design life is 12 years at 25 C, self-discharge is below 3% per month and the operating temperature range is -40 to 70 C; these are manufacturer statements.

The page also carries a general explanation of AGM batteries and their maintenance. Chemistry and capacity test conditions should be taken from the relevant table of the document, which gives length, width and height in mm and inches. Cabinet energy, runtime and loss calculations are not on the page and must be made separately.

Key points

  1. 12 V UHR series; rated capacity is watts per cell over 15 minutes (WPC) to 1.67 V/cell end voltage, spanning 21-880 W.
  2. Certificates: UL1989, IEC 61427, IEC 60896, CE; flame-retardant UL 94 V-0 ABS optional.
  3. UHR 12-21W: 250 A short circuit, 45 mOhm, 1.60 kg, 90 x 70 x 102 mm; UHR 12-880W: 6600 A, 2.5 mOhm, 70.0 kg, 520 x 238 x 220 mm.
  4. UHR 12-480W: 4600 A, 3.4 mOhm, F-M8 terminal, 35.5 kg, 408 x 175 x 230 mm.
  5. Design life is 12 years at 25 C; self-discharge below 3% per month; operating temperature -40 to 70 C.
  6. Construction: low-calcium/high-tin lead alloy, glass micro-fibre separator, fixed-orifice plate pasting.
  7. Terminals are Faston Tab 187 on small models and F-M8 on large ones, as silver-plated copper female inserts.
  8. Applications: UPS, switchgear, emergency lighting, overhead cranes, telecom, alarm and security, industrial DC power.

Using it in design

  • Select batteries from the target load power and the 15-minute WPC value instead of Ah: derive the total watts per cell from cell count and UPS DC bus voltage.
  • Feed the short-circuit current and internal resistance columns into DC protection, fuse and cable selectivity calculations.
  • In rack layout, check terminal type (Faston or F-M8) and weight (1.6-70 kg) along with length, width and height.
  • The 15-minute rating depends on a 1.67 V/cell end voltage; request the discharge table from the manufacturer for other durations or end voltages.
  • For hot-aisle data-centre conditions, derate the life claim (12 years at 25 C) against the actual operating temperature.

Who should read it

Electrical engineers designing UPS battery banks and teams writing battery specifications.

Document contents

  1. Technical features and advantages
  2. Construction
  3. Model table (WPC, short-circuit current, internal resistance, terminal, weight, dimensions)
  4. AGM battery FAQ

Publication details

Authors
EverExceed
Publisher
EverExceed
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EverExceed EverExceed Ultra High Rate VRLA/AGM battery: technical table. EverExceed. https://www.everexceed.com/ultra-high-rate-vrla-agm-battery-for-ups-and-data-center_p390.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.