Haze HZB12-100 Product Sheet: 12 V AGM Valve-Regulated Lead-Acid Battery (p.1)

Original title Haze HZB12-100 product sheet: p.1

Haze Battery

The Haze HZB12-100 is a 12 V, 115 Ah (C20) AGM valve-regulated lead-acid battery with a 12-year design life, float voltage of 2.25-2.30 V per cell, internal resistance of 3.4 mΩ and weight of 29.7 kg.

On this page

Overview

The document is the product sheet for Haze Battery's HZB12-100. The battery is presented as a 12 V AGM valve-regulated lead-acid unit for stand-by power, with a 12-year design life, maintenance-free, sealed and spill-proof construction. Production to IEC 896-2, DIN 43534, BS 6290 Pt4 and Eurobat, FAA and IATA classification as non-hazardous, and multi-position use are stated.

Specifications: nominal 12 V, 115 Ah (C20), calcium/tin lead alloy grid, flat pasted plates, absorbent glass mat separator, ABS case (V0 on request), operating temperature -30 to +50 °C. Float charge voltage is 2.25-2.30 V per cell at 25 °C and cyclic charging 2.35-2.40 V per cell; maximum ripple 0.05C. Terminal is a 16 mm insert with M6 thread and recommended torque 5-7 Nm. Size is 306 x 168 mm footprint and 211 mm height including terminals; weight is 29.7 kg.

The characteristics section gives, to 1.7 V per cell, 115.8 Ah at 20 h, 109.7 Ah at 10 h, 100.5 Ah at 5 h, 72.6 Ah at 1 h and 48.4 Ah at 15 min. Constant-power (W per cell) and constant-current tables run from 5 minutes to 20 hours for several end voltages. Capacity is 102% at 40 °C, 85% at 0 °C and 65% at -15 °C; self-discharge leaves 98% after 1 month, 94% after 3 months and 86% after 6 months at 20 °C. Short-circuit current is 2900 A.

Key points

  1. Nominal 12 V, 115 Ah (C20); 12-year design life; AGM, valve regulated.
  2. Float 2.25-2.30 V per cell (25 °C); cyclic 2.35-2.40 V per cell; maximum ripple 0.05C.
  3. Capacity (to 1.7 V per cell): 115.8 Ah (20 h), 109.7 Ah (10 h), 100.5 Ah (5 h), 72.6 Ah (1 h), 48.4 Ah (15 min).
  4. Internal resistance 3.4 mΩ; short-circuit current 2900 A; impedance 1300 S.
  5. Size 306 x 168 x 211 mm; weight 29.7 kg; M6 terminal, torque 5-7 Nm.
  6. Temperature correction (C20): 102% (40 °C), 100% (20 °C), 85% (0 °C), 65% (-15 °C).
  7. Capacity after storage: 98% at 1 month, 94% at 3 months, 86% at 6 months (20 °C).
  8. Operating temperature -30 to +50 °C; conforms to IEC 896-2, DIN 43534, BS 6290 Pt4, Eurobat; UL recognised component.

Using it in design

  • For autonomy, read the constant-power (W per cell) table at the target duration and end voltage, and check UPS DC bus power divided by cell count.
  • Set charger float within 2.25-2.30 V per cell with temperature compensation.
  • Use the 2900 A short-circuit current as input for battery protection (fuse or DC breaker) breaking capacity and selectivity.
  • Correct the 12-year design life for actual temperature and tighten the replacement plan at high temperature.

Who should read it

Electrical engineers designing UPS battery banks and maintenance teams.

Document contents

  1. Innovative features
  2. Specifications
  3. Characteristics (capacity, internal resistance, temperature, self-discharge)
  4. Constant power discharge table
  5. Constant current discharge table
  6. Ampere-hour table

Publication details

Authors
Haze Battery
Publisher
Haze Battery
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Haze Battery Haze HZB12-100 product sheet: p.1. Haze Battery. https://hazebattery.com/wp-content/uploads/2024/06/HZB12-100-061112.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.