Power Sonic PSH Series High-Rate Rechargeable Sealed Lead Acid Batteries

Original title Power Sonic PSH Summary Specification Sheet: model summary table

Power Sonic

The Power Sonic PSH series is a family of high-rate AGM VRLA batteries for UPS: 6 V and 12 V blocks, 5.5-21 Ah, 21-80 W per cell, with a UL94 V-0 flame-retardant case.

On this page

Overview

The summary sheet introduces the PSH series as sealed lead-acid batteries designed for high-rate discharge in UPS, data centre, telecom and fire and security applications. The series uses high-rate VRLA with absorbent glass mat (AGM) technology in a valve-regulated, spill-proof construction that can operate in any orientation except continuous inverted use. Every 6 V and 12 V block has a UL94:V0 flame-retardant ABS case and cover.

The sheet lists a high rate of charge and discharge, high energy density and an impact-resistant case as features. Five models are drawn: PSH-655F1-FR (6 V, 5.5 Ah, 21 W per cell), PSH-1255F2-FR (12 V, 6.0 Ah, 24 W), PSH-1280F2-FR (12 V, 8.5 Ah, 37 W), PSH-12100F2-FR (12 V, 10 Ah, 41 W) and PSH-12180NB-FR (12 V, 21 Ah, 80 W).

Dimensions are given in inches and millimetres; for example the PSH-655F1-FR is 70x47x100 mm (106 mm over terminals), the PSH-1255F2-FR and PSH-1280F2-FR about 151x65x94.5 mm, and the PSH-12180NB-FR 181x77x167 mm. Terminal types are F1 (0.187 in faston), F2 (0.250 in faston) and NB2 (tin-plated brass nut and bolt) with 3.9-5.4 N-m torque for NB2. As a two-page summary it carries no discharge curves.

Key points

  1. Series: PSH, high-rate AGM VRLA for UPS applications.
  2. Models: PSH-655F1-FR (6 V, 5.5 Ah), PSH-1255F2-FR (12 V, 6.0 Ah), PSH-1280F2-FR (12 V, 8.5 Ah), PSH-12100F2-FR (12 V, 10 Ah), PSH-12180NB-FR (12 V, 21 Ah).
  3. Power per cell: 21, 24, 37, 41 and 80 W.
  4. Case and cover UL94:V0 flame-retardant ABS.
  5. Valve regulated and spill proof; operates in any orientation except continuous inverted use.
  6. Terminals: F1 0.187 in faston, F2 0.250 in faston, NB2 nut and bolt; NB2 torque 3.9-5.4 N-m.
  7. Example sizes: PSH-655F1-FR 70x47x100 mm; PSH-12180NB-FR 181x77x167 mm.

Using it in design

  • For small UPS and telecom, match the block to its watts-per-cell rating and the target autonomy.
  • Choose block dimensions and terminal type (faston or bolt) to suit the cabling design on the shelf.
  • Write the 3.9-5.4 N-m torque for NB2 terminals into the maintenance procedure.
  • State the flame-retardant case (UL94:V0) requirement in the specification.
  • Request the full manufacturer datasheet for discharge curves.

Who should read it

Designers selecting VRLA batteries for small UPS, telecom and security systems.

Document contents

  1. Features
  2. Physical dimensions
  3. Terminals
  4. Specifications

Publication details

Authors
Power Sonic
Publisher
Power Sonic
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Power Sonic Power Sonic PSH Summary Specification Sheet: model summary table. Power Sonic. https://cdn.power-sonic.com/documents/PSH%20Summary%20Specification%20Sheet_US.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.