Ritar Battery Catalogue: HR Series, pp.21-22
Original title Ritar Battery Catalogue: HR Series, pp.21–22
Ritar
Ritar's HR (High Rate) series catalogue pages list 6 V/12 V VRLA batteries from 4.5 to 240 Ah for UPS and EPS, with 15-minute watts per cell (1.67 V) and dimension, weight, resistance and short-circuit tables.
On this page
Overview
The HR (High Rate) series pages of Ritar's catalogue describe sealed lead-acid (VRLA) batteries with AGM separators designed for heavy-load discharge applications. The catalogue says the series gives 30% more power output than the standard range and suits UPS/EPS with high current loads. Capacity ranges from 4.5 Ah to 240 Ah in 6 V and 12 V classes.
Float design life is 5 years for 28 Ah and below and 10 years above 28 Ah. Listed features include self-discharge of 3% per month or less, gas recombination efficiency of 99% or more, flat pasted plates with a high-rate active material formula, low internal resistance from short inter-cell connectors, a flame-arrester safety valve and heat-sealed lids. The case is ABS (UL94-HB) with UL94-V0 optional.
The main parameter table gives, per model, watts per cell at 15 minutes (1.67 V/cell), nominal voltage, nominal capacity, weight (lb and kg), terminal type, dimensions (mm and inch), internal resistance (mOhm) and short-circuit current (A). Capacity is at the 20-hour rate below 33 Ah and the 10-hour rate at 33 Ah and above. For example, HR12-16W is 16 W/cell, 4.5 Ah, 1.4 kg and 35 mOhm, while HR12-125W is 125 W/cell, 33 Ah, 10.2 kg and 9 mOhm.
The catalogue lists conformity with GB/T19638.2-2005, YD/T799-2002, JIS C8704-2006 and IEC 60896-21/22, and ISO 9001, ISO 14001, OHSAS 18001, UL and CE certification. The document is manufacturer literature and table values may change without notice.
Key points
- HR series VRLA/AGM: 6 V and 12 V, 4.5-240 Ah; 30% more power output than the standard range is claimed.
- Float design life: 5 years for 28 Ah and below, 10 years above 28 Ah; self-discharge 3% per month or less.
- Gas recombination efficiency 99% or more; ABS case (UL94-HB), UL94-V0 optional.
- Power at 1.67 V/cell for 15 min: HR12-16W 16 W, HR12-48W 45 W, HR12-125W 125 W, HR12-350W 340 W, HR12-580W 586 W.
- HRL12-780W (12 V, 240 Ah, 74.5 kg, 522 x 240 x 219 mm) and HRL12-650W (200 Ah, 62.5 kg) are the largest blocks; the 780W has 4200 A short-circuit current and 3.6 mOhm resistance.
- HR12-16W (4.5 Ah) has 35 mOhm and 225 A short-circuit current; HR12-200W (55 Ah) has 6.8 mOhm and 1350 A.
- Capacity reference: C20 below 33 Ah, C10 at 33 Ah and above.
- Standards: IEC 60896-21/22, JIS C8704, GB/T19638.2, YD/T799; ISO 9001/14001, OHSAS 18001, UL, CE.
Using it in design
- For UPS batteries with about 15 minutes of backup, compare the catalogue W/cell (1.67 V) with the value derived from UPS DC power and cell count; power, not Ah capacity, governs.
- Set the series block count from the UPS DC bus voltage and use each model's internal resistance and short-circuit current in DC protection and fuse selection.
- Separate the life assumption by capacity: 5-year design life for 28 Ah and below and 10-year above, then apply the replacement interval and temperature correction.
- Use model dimensions and weights (for example the 74.5 kg HRL12-780W) as inputs to handling, rack load and deflection checks.
- Match terminal type (F1-F14) and terminal position to the cabinet connection design.
Who should read it
Electrical engineers selecting VRLA batteries for UPS and EPS and designing DC protection and battery room layouts.
Document contents
- HR series summary and features
- Applications and standards
- Main parameters (HR6, HR12, HRL12, HS12 models)
Publication details
- Authors
- Ritar
- Publisher
- Ritar
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ritar Ritar Battery Catalogue: HR Series, pp.21–22. Ritar. https://www.solarworld.co.za/wp-content/uploads/2020/01/Ritar-Battery-Catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.